Pub. No.  18-HD29D2-4

Installer’s Guide

Checkout

There are two methods of verifying that the Comfort Control
operates the system as intended.

Method 1:  Normal Mode

This can be accomplished by pressing the appropriate
keypad button(s) to cycle the system through each of the
available modes and increasing or decreasing the
setpoint to activate and deactivate the cycle.
The minimum on and off cycle time delays, selected
during the setup, will be enforced. Press the appropriate
keypad button for the filter timer, outdoor temperature
display and energy savings features to verify they are set
to the end user’s desired preference.

Method 2:  Manual Test Mode

The Comfort Control’s load outputs can be verified using
the manual test mode.  See Table 1 for navigating
through the manual test mode steps.

 To Enter The Manual Test Mode:

1.) Set System Mode to OFF

2.) Set Fan to AUTO

3.) Press and hold Mode and Down Arrow at the same

time.

Figure 8

Table 2

T deg F

RESISTANCE

(OHMS X 1000)

10K THERMISTOR

T deg F

RESISTANCE

(OHMS X 1000)

10K THERMISTOR

T deg F

RESISTANCE

(OHMS X 1000)

10K THERMISTOR

-15

138.9

35

30.0

80

9.3

-10

117.7

40

26.1

85

8.3

-5

99.9

45

22.7

90

7.3

0

85.1

50

19.9

95

6.5

5

72.7

55

17.4

100

5.8

10

62.3

60

15.3

105

5.2

15

53.5

65

13.5

110

4.7

20

46.1

70

11.9

115

4.2

25

39.8

75

10.5

120

3.8

30

34.5

Table 1        

Manual Test Mode

Menu Item

(Press Mode or Fan)

Default

Setting (Choices)

(Press Up or Down arrow)

Step

(Press Mode or Fan)

G - Fan Relay

Off

On / Off

70

Y - Compressor
     Contactor
(G - must be ON)

Off

On / Off

72

O - Switch Over Valve

Off

On / Off

74

W1 - Heating relay

Off

On / Off

75

W2 - Heating relay

Off

On / Off

76

LCD

_ _

All Icons On (See Fig. 8)
All Icons Off

78

Factory Use Only

Press and hold MODE to advance to
step 80 and press "$" Energy
Savings key to exit.

79 - 82

Note: Press "$" Energy Savings key to exit manual test mode at any time - Step 70  78.

"     "

"      "

"     "

"       "

"      "

"      "

The Manual test mode will time out and return to normal
operation after 1 minute from the last key press.

NOTE: The manual test mode allows the installer to ener-
gize the G fan relay , Table 1, Step 70, and then advance to
Step 72 to energize the Y compressor output with the fan
still operating. It is recommended that this method be used
to prevent damage to the compressor.

Содержание TCONT401AN21MA Comfort Control

Страница 1: ...e signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING sign...

Страница 2: ...thermostat is being replaced a Remove existing thermostat from wall b Disconnect wires from existing thermostat one at a time Be careful not to allow wires to fall back into the wall c As each wire i...

Страница 3: ...RT CONTROL TERMINAL BLOCK SINGLE STAGE OIL FURNACE SINGLE STAGE COOLING SINGLE STAGE AIR CONDITIONER FAN SOV COOLING HEATING 1st HEATING 2nd W2 X2 O SINGLE STAGE OIL FURNACE B C OD TEMP T R1 R1 Figure...

Страница 4: ...STANCE OHMS X 1000 10K THERMISTOR T deg F RESISTANCE OHMS X 1000 10K THERMISTOR 15 138 9 35 30 0 80 9 3 10 117 7 40 26 1 85 8 3 5 99 9 45 22 7 90 7 3 0 85 1 50 19 9 95 6 5 5 72 7 55 17 4 100 5 8 10 62...

Страница 5: ...ee increments 50 Compressor Cooling Cycle Minimum On Time Minutes 3 2 4 CPH 1 15 Minutes 5 CPH 1 7 Minutes 6 CPH 1 5 Minutes 20 Exit User Setup Press Mode SA CA Cancel SA Save US Default User Settings...

Страница 6: ...enough to prevent overshooting Set Control Response rate to Fast Step 33 Heating will not come on 1 System Mode not set to Heat 2 Minimum off time delay being enforced 3 Loose connection to control or...

Страница 7: ...n easily be determined by simply pressing the Filter OD keypad button once more Pressing and holding the Filter OD keypad button provides quick access to the filter timer value Keypad Lock Locking the...

Страница 8: ...hich will be added to actual temperature The number can range between 5 and 5 degrees in 1 2 degree increments Factory default is 0 This adjusted value will be used and displayed as actual temperature...

Отзывы: