Trane XR202 Programmable Thermostat
Pub. No. 18HD51D1-1C-EN
09/2020
Part No.
37-7769005 9
4.6 Installer Menu
To prevent changes that may affect system performance, this thermostat has an INSTALLER MENU and a
USER MENU. The
INSTALLER MENU provides access to every option, while the USER MENU provides access to items that will not affect system
performance. To access the INSTALLER MENU
press the
Menu
button for 8 seconds. The display will show item 30 in the table below.
Use
Next
and
back
to navigate through menu items. Press
or or
to change a menu setting.
INSTALLER MENU
(HOLD MENU 8 SECONDS)
DESCRIPTION
DEFAULT
(FLASHING ICONS)
SETTINGS
(PRESS
OR
)
30
CR
Heat Cycle Rate (how often the heat will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
35
CR
Cool Cycle Rate (how often the cooling will turn on)
MEd
SLO – slow
MEd – medium
FAS – fast
50
CL
Compressor Lockout / Minimum Off Time
(protects the compressor from short cycling)
On
On – 5 minute delay
OFF – no delay
65
Maximum Heat Limit
(maximum set point for heat mode)
99
47 to 99
66
Minimum Cool Limit (minimum set point for cool mode)
45
45 to 97
74
Schedule Type
(set as either 7-Day, 5-1-1 Day or NonProgrammable)
5
7 – 7 Day
5 – 5-1-1 Day
0 – Non Programmable
76
E
Early Start (starts heating or cooling early so your programmed
temperature is reached by the programmed time)
OFF
On – start early
OFF – start at program period time
79
Fahrenheit or Celsius
°F
°F – Fahrenheit
°C – Celsius
81
Temperature Display Adjustment (adjust the displayed “Room
Temperature”)
0
-5 to +5
83
dL
Continuous Display Light
(keep the backlight always on – “C” wire required)
OFF
On – always on
OFF – momentarily
86
Change Air Filter (set up a monthly reminder)
OFF
1 to 12 – reminder time (months)
OFF – no filter reminder
99
Keypad Lock (prevent unwanted changes to the thermostat)
OFF
On – disable buttons
OFF – all buttons are active
5. Test Modes
Turn on power to the system.
5.1 Fan Operation
If your system does not have a G terminal connection, skip to
Heating System.
1.) Press the fan button to select the On position. The blower
should begin to operate.
2.) Press the fan button to select the Auto position. The blower
should stop immediately.
5.2 Heating System
1.) Move System Switch to Heat position.
2.) Press to adjust thermostat setting to 1° above room
temperature. The system should begin to operate and the
thermostat will indicate Heat On.
3.) Press to adjust thermostat setting to 1° below room
temperature. The heating system should stop operating and
the thermostat should indicate Heat.
5.3 Cooling System
1.) Move System Switch to Cool position.
2.) Press to adjust thermostat setting 1° below room
temperature. The blower should come on immediately on
high speed, followed by cold air circulation The thermostat
will indicate Cool On. There can be up to a 5 minute delay,
(see INSTALLER MENU, item 50).
3.) Press to adjust thermostat setting to 1° above room
temperature. The cooling system should stop operationg and
the thermostat will indicate Cool.
Note: If Starting Soon is shown on the display, the compressor lock-
out feature is operating. There will be up to a 5 minute delay before
the compressor turns on (see INSTALLER MENU, item 50).
CAUTION
!
To prevent compressor and/or property damage, if the outdoor temperature is below 55°F,
DO NOT operate the cooling system.
Do not allow the compressor to run unless the compressor oil heaters have been operational
for 6 hours and the system has not been operational for at least 5 minutes.