7.1  Modify the Cooling Schedule 

1.) Slide the system switch to Cool 
2.) Repeat steps 2-6 from the heating schedule

7.2  Thermostat Settings

Resetting the Thermostat or Thermostat Settings
If the thermostat has good batteries, but has a blank display or 
does not respond to key presses, the thermostat should be reset by 

removing the batteries for 2 minutes. This reset will not change the 
menu settings or program. If the condition persists after reinstalling 
the batteries, replace the thermostat. 
To conveniently reset only the schedule and user settings back to 
factory defaults, press Menu and Backlight buttons at the same 
time and hold until the display goes blank and resets.

7.   Troubleshooting

SYMPTOM 

POSSIBLE CAUSE

CORRECTIVE ACTION 

No Heat/

No Cool/

No Fan

(common problem)

1.) Blown fuse or tripped circuit breaker

2.) Furnace power switch to OFF

3.) Furnace blower compartment door 

panel loose or not properly installed

4.) Loose connection to thermostat or 

system 

1.) Replace fuse or reset breaker 

2.) Turn switch to ON 

3.) Replace door panel in proper position to engage safety interlock or door switch 

4.) Tighten Connections 

No Heat 

1.) System Switch not set to Heat

2.) Loose connection to thermostat or 

system

3.) Heating System requires service or 

thermostat requires replacement

Verify thermostat and system wires are securely attached.

Diagnostic: Set System Switch to Heat and raise the setpoint above room temperature. Within 

five minutes the thermostat should make a soft click sound and “Heat On” should appear on 

display. This sound indicates the thermostat is operating properly. If the thermostat does not 

click, try the reset operation listed below. If the thermostat does not click after being reset, 

contact your heating and cooling service person or place of purchase for a replacement. If the 

thermostat clicks, contact the furnace manufacturer or a service person to verify the heating 

system is operating correctly.

No Cool 

1.) System Switch not set to Cool

2.) Loose connection to thermostat or 

system

3.) Cooling System requires service or 

thermostat requires replacement

Verify thermostat and system wires are securely attached.

Diagnostic: Set System Switch to Cool and lower setpoint below room temperature. Same 

procedures as diagnostic for “No Heat” condition except set the thermostat to Cool and lower 

the setpoint below the room temperature. There may be up to a five minute delay before the 

thermostat clicks in Cooling if the compressor lock-out option is selected in the installer menu. 

(see INSTALLER MENU, item 50)

Heat, Cool or Fan Runs 

Constantly 

Possible short in wiring, thermostat, heat, 

cool or fan system

Check each wire connection to verify they are not shorted or touching other wires. Try resetting 

the thermostat. If the condition persists contact your HVAC service person.

Thermostat Display & 

Thermometer Disagree 

Thermostat display requires adjustment 

Display can be ad/-5°. See User Menu item 04

Furnace (Air Conditioner) 

Cycles Too Fast or Slow 

(narrow or wide temperature 

swing) 

The location of the thermostat and/or 

the size of the Heating System may be 

influencing the cycle rate

Digital thermostats provide precise control and cycle faster than older mechanical models. The 

system turns on and off more frequently but runs for a shorter time. If you would like to increase 

cycle time, choose SLO for slow cycle in the Installer menu. (Reference menu items 30 & 35) If 

an acceptable cycle rate is not achieved, contact your HVAC service person.

“Call for Service” icon 

appears on displayed

1.) Heating system is not able to heat 

the space to within 10 degrees of the 

setpoint within 2 hours

2.) Cooling system is not able to cool 

the space to within 10 degrees of the 

setpoint within 2 hours

3.) If “--” is displayed for the Room 

Temperature, a replacement thermostat 

is needed

4.) None of the buttons operate on the 

thermostat

1.) See corrective action for “No Heat”

2.) See corrective action for “No Cool”

3.) Replace thermostat

4.) Make sure keypad lockout is not turned on (denoted by   icon) 

6.5

6.6

Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy efficient indoor 

environments for commercial and residential applications. For more information, please visit trane.com or 

tranetechnologies.com.

Trane has a policy of continuous data improvement and it reserves the right to change design and specifications without notice. We are committed to 

using environmentally conscious print practices.

© 2020 Trane

18-HD51D1-1C-EN

 

(09

 

Sept

 

2020)

 

Supersedes 

18-HD51D1-1B-EN

 (

27 Mar 2019

)

Содержание TCONT202

Страница 1: ...his Document is customer property and is to remain with this unit These instructions do not cover all variations in systems or provide for every possible contingency to be met in connection with the i...

Страница 2: ...erty damage if the outdoor temperature is below 55 F DO NOT operate the cooling system Do not allow the compressor to run unless the compressor oil heaters have been operational for six hours and the...

Страница 3: ...GUIDE Thermostat Applications Maximum Stages Heat Cool Gas Oil Electric mV and 24V Heat Only Cool Only or Heat Cool Systems 1 1 2 Product Specifications 3 General Information 3 1 Overview The 202 is a...

Страница 4: ...s 4 3 Battery Location Figure 2 LevelingThermostat Leveling is for appearance only and will not affect thermostat operation Battery Location Premium AA alkaline batteries are required when C wire is n...

Страница 5: ...ard 2 X2 is required to energize aux heat during defrost Cooling with TAM7 TAM9 24V Mode Indoor Unit Outdoor Unit Thermostat Rc Rh O B Y G W C R G W1 B B Y0 Y Y1 O NOTES 1 Wire third party condensate...

Страница 6: ...is required to energize aux heat during defrost Heat Cool Package with Variable Speed Blower Thermostat Rc Rh O B Y G W C R G W1 B Y1 NOTES 1 Wire third party condensate overflow switches between Y o...

Страница 7: ...rd 2 X2 is required to energize aux heat during defrost Heat Cool Package Thermostat Rc Rh O B Y G W C R G W1 B Y1 NOTES 1 Wire third party condensate overflow switches between Y of the thermostat and...

Страница 8: ...005 NOTES 1 Wire third party condensate overflow switches between Y of the thermostat and Y1 of the airflow control board 2 X2 is required to energize aux heat during defrost Cooling with GAT2 GAM2 TE...

Страница 9: ...ange Air Filter set up a monthly reminder OFF 1 to 12 reminder time months OFF no filter reminder 99 Keypad Lock prevent unwanted changes to the thermostat OFF On disable buttons OFF all buttons are a...

Страница 10: ...indicator 6 Cancels Hold Returns to Programmed Schedule 15 Day of the week used when programming a schedule 7 Raises Temperature Setting 16 Permanent hold bypassing the schedule 8 Access Menu Options...

Страница 11: ...momentarily press the Hold button Hold will be displayed Use or to adjust the temperature The thermostat will hold the room temperature at the selected setting until you press Run to start program op...

Страница 12: ...ic Set System Switch to Cool and lower setpoint below room temperature Same procedures as diagnostic for No Heat condition except set the thermostat to Cool and lower the setpoint below the room tempe...

Отзывы: