Trane XR202 Programmable Thermostat
SPECIFICATION DESCRIPTION
Product Models
TCONT202
Product
XR 202
Size
3-3/4” x 6” x 1-1/8 (HxWxD)
Configurations
Heat / Cool
Maximum Number of Stages
1H, 1C
Operating Temperature
32°F to 105°F (0 to +41°C) / 90% RH Non Condensing
Shipping Temperature Range
-20 to 150°F (-29 to +65°C)
Input Power (DC)
Two 1.5V AA Alkaline
Input Power (AC)
20 - 30 VAC, NEC Class ll, 50/60 HZ
Wire Usage
18 AWG
System Modes
Heating, Cooling, Off
Fan Modes
Auto, On
Cooling Setpoint Temperature Range
45°F to 99°F, 1°F resolution
Heating Setpoint Temperature Range
45°F to 99°F, 1°F resolution
Temperature Display Range
32°F to 99°F, 1°F resolution
Minimum Cycle Off Time Delay
Compressor: 5 minutes, Indoor Heat; 1 minute
Terminal Load
1.0A per terminal, 1.5A maximum all terminals combined
Operating Ambient
32°F to +105°F (0° to +41°C)
Shipping Temperature Range
-20°F to +150°F (29° to +65°C)
RATED DIFFERENTIALS
FAST
MEDIUM
SLOW
Heat (@ 6°F/Hr)
0.5°F
0.75°F
1.9°F
Cool (@ 6°F/Hr)
0.9°F
1.2°F
1.7°F
THERMOSTAT APPLICATION GUIDE
Thermostat Applications
Maximum Stages Heat/Cool
Gas, Oil, Electric, (mV and 24V), Heat Only, Cool Only or Heat/Cool Systems
1/1
2. Product Specifications
3. General Information
3.1 Overview
The 202 is a programmable push button single stage
thermostat with a 3.5’’ backlit display. The 202 features a
scheduling mode that can operate a 7-day program, 5-1-1
program or operate in a non-programmable mode.
3.2 Contents
— 1-Thermostat
— 1-Sub-base
— 2-Phillips slotted head mounting screws
— 2-Nylon Drywall Anchors
— 1-Installation Guide / User Guide
3.3 Accessories
Wall Cover Plate (BAYCOVR200A)
4. Installation
4.1 Location
The
202
is designed for installation in climate controlled living
spaces. Place the unit in a central location with good circulation.
For proper temperature sensing, avoid exposing the
202 to heat
radiated from lamps, sun light, fireplaces or any other radiant heat
source.
Avoid locations close to windows, behind doors or alcoves with
poor air circulation, adjoining outside walls, or doors that lead to
the outside.
Select a location that prevents the 202 from being directly exposed
to air currents from supply registers or ceiling fans.
Mount the Control on a section of interior wall that does not
contain hot or cold water pipes or duct work.