RLC-SVX19G-GB
131
11
UNT-PRC002-GB
Sound power levels
Discharge
Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
55
50
42
37
37
31
30
46
FWD 08
2
57
54
47
40
30
38
40
50
3
58
57
50
42
32
40
43
53
1
57
51
45
42
34
33
28
48
FWD 10
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
57
51
45
42
34
33
28
48
FWD 12
2
58
54
48
45
38
39
35
51
3
60
58
50
48
40
42
39
54
1
56
62
50
48
39
38
36
56
FWD 14
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
1
57
63
51
49
40
39
37
57
FWD 20
2
61
66
55
53
47
46
45
60
3
63
69
58
56
50
50
49
63
Intake
Measurement conditions:
Measurements taken at the horizontal air intake.
Fan
Power level in dB(A), per Hz frequency band
Overall power
Unit
speed
125
250
500
1000
2000
4000
8000
dB(A)
1
56
55
55
53
46
45
42
57
FWD 08
2
63
62
60
60
53
53
53
64
3
66
65
63
62
56
55
57
67
1
62
58
55
58
51
48
44
61
FWD 10
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
62
58
55
58
51
48
44
61
FWD 12
2
66
63
60
62
56
55
52
66
3
70
67
63
65
59
59
57
69
1
66
65
65
65
57
50
46
68
FWD 14
2
73
72
69
71
64
59
57
74
3
78
76
73
75
69
64
63
78
1
68
72
64
64
56
52
50
69
FWD 20
2
76
76
68
71
65
61
61
75
3
78
79
71
74
69
66
66
78
Optional Free-Cooling
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
RTAF
210
230
265
275
285
300
305
340
385
405
470
Partial Free Cooling type
Coils quantity (5)
#
Coils quantity (6)
#
Summer nominal water flow
(L/s)
Summer & Winter unit pressure drop
(kPa)
Glycol Pump Max Power input (kW)
(kW)
Glycol Pump Max Amps @ 110 V
(A)
Freeze protection - Max Power input
kW
Freeze protection - Max Amps
A
Additional Free Cooling weight
(without water) (5)
(kg)
Additional Free Cooling weight
(without water) (6)
(kg)
Additional water content (without Evap.) (5)
(L)
Additional water content (without Evap.) (6)
(L)
Glycol content (5)
(L)
Glycol content (6)
(L)
Additional baseframe length (5)
(m)
Additional baseframe length (6)
(m)
(1) SE-SN/HE-SN/HE-LN
(2) SE-LN/XE-SN/XE-LN/HSS-SN/HSS-LN/HSE-SN/HSE-LN
(3) SE-XLN/XE-XLN/HSS-SN/HSS-XLN/HSE-XLN
(4) Option is not define for size 250 option SE-SN/SE-LN/SE-XLN/HSS-LN/HSS-XLN
(5) Max Speed - range is 60% to 100% of max speed
(6) SE-SN/SE-LN/SE-XLN/HSS-SN/HSS-LN/HSS-XLN
(7) HE-SN/HE-LN/XE-SN/XE-LN/XE-XLN/HSE-SN/HSE-LN/HSE-XLN
Table 24d – General data for free cooling option sizes xxx - R1234ze (continued)