82
SS-SVX11K-EN
W
WA
AR
RN
NIIN
NG
G
H
Ha
azza
arrd
do
ou
uss V
Vo
olltta
ag
ge
e!!
F
Fa
aiillu
urre
e tto
o d
diisscco
on
nn
ne
ecctt p
po
ow
we
err b
be
effo
orre
e sse
errv
viicciin
ng
g cco
ou
ulld
d
rre
essu
ulltt iin
n d
de
ea
atth
h o
orr sse
erriio
ou
uss iin
njju
urry
y..
D
Diisscco
on
nn
ne
ecctt a
allll e
elle
eccttrriicc p
po
ow
we
err,, iin
nccllu
ud
diin
ng
g rre
em
mo
otte
e
d
diisscco
on
nn
ne
eccttss b
be
effo
orre
e sse
errv
viicciin
ng
g.. F
Fo
ollllo
ow
w p
prro
op
pe
err
llo
occkko
ou
utt//tta
ag
go
ou
utt p
prro
occe
ed
du
urre
ess tto
o e
en
nssu
urre
e tth
he
e p
po
ow
we
err
cca
an
n n
no
ott b
be
e iin
na
ad
dv
ve
errtte
en
nttlly
y e
en
ne
errg
giizze
ed
d.. V
Ve
erriiffy
y tth
ha
att n
no
o
p
po
ow
we
err iiss p
prre
esse
en
ntt w
wiitth
h a
a v
vo
ollttm
me
ette
err..
Wire the sensor in accordance with field connection
diagram, numbers 2307-9122 (for 20-60) and 2307-9144
(for 80-120). As shipped from the factory, a resistor
(7R1) is installed on terminal board 1TB8 terminals 5 &
6). Remove this resistor when the sensor is installed.
Shielded cable (Belden 8760 or equivalent) must be
used when wiring the sensor to the terminal board
inside the unit’s control panel.
When the sensor is installed, it serves two functions;
•
It sends the supply air temperature to the master
energy controller (MEC), in the form of an analog
input, to assist in the rate at which the system
changes the space temperature. By offsetting the
actual zone thermostat setpoint, up or down, the
MEC can closer control the zone comfort level.
•
It serves as a low limit for the system when the
supply air temperature reaches too high a delta tee
between the actual supply air temperature and the
zone temperature to help prevent overshooting of
the zone thermostat setpoint.
EVP Chiller Control
Each unit ordered for EVP Chiller applications (digit 9 in
the model number), is shipped with the following
controls:
•
EVP Remote Panel w/ W7100G Controller
•
Freezestat (6S12)
•
Chiller Water Temperature Sensor (6RT2)
•
Freezestat Bulb well
•
Chilled Water Temperature Sensor Well
The installation of the freezestat bulb well, freezestat
bulb, and the chilled water temperature sensor was
discussed in the “Chilled Water Piping” section. Refer
to that section for their installation locations and
dimensional data.
The chiller control (located in the remote panel)
controls the system operation by responding to the
leaving water temperature. The remote panel must be
mounted indoors and within 20 feet of the chiller.
Figure below illustrates the remote panel dimensional
data, the component locations, the locations for the
ship-with items, grounding lugs, and the field
connection terminal board 6TB9. Refer to the field
connection diagram illustrated in
(20 to
60 ton units) and
(80 to 120 ton units)
for the interconnecting points between the remote
panel and the unit’s control panel.
Figure 56.
EVP chiller remote panel
19.4”
1”
1”
1.25”
12.5”
1.25”
Freezestat
Bulbwell
Temperature
Sensor
15.000
REF
RESISTORS
21.4”
6U11
6S12
6T2
LOAD
LINE
6T
B
9
8
7
6
GND
TR
TR
12
1
Содержание RAUJ-C20
Страница 6: ...6 SS SVX11K EN Wiring Diagrams 128 T Ta ab bl le e o of f C Co on nt te en nt ts s...
Страница 117: ...SS SVX11K EN 117 S St ta ar rt t U Up p...
Страница 129: ...SS SVX11K EN 129 N No ot te es s...
Страница 130: ...130 SS SVX11K EN N No ot te es s...
Страница 131: ...SS SVX11K EN 131 N No ot te es s...