PTAC-SVX01C-EN
11
Installation
Table 3.
Electric heat capacity and electrical data, models PTEE and PTHE
(i)
Nominal heating
Building circuit requirement
Voltage
(ii)
Electric
heater
Size (kW)
# of
stages
Btu/h at
230/208V
Btu/h at
265V
Total
watts
(iii)
Unit
total
amps
Minimum
ampacity
(iv)
Maximum
protection
(v)
Plug
230/208
2.0/1.6
1
6,800/
5,500
-
2000/
1600
8.9/7.9
11.4
15
6 - 15 P
230/208
3.0/2.4
1
10,200/
8,200
-
3000/
2400
13.4/11.8
17
20
6 - 20 P
230/208
5.0/4.0
1
17,100/
13,700
-
5000/
4000
22.2/19.7
28
30
6 - 30 P
265
2.0
1
-
6,800
2000
7.7
9.8
15
7 - 20 P
265
3.0
1
-
10,200
3000
11.6
14.7
15
7 - 20 P
265
5.0
1
-
17,100
5000
19.3
24.4
25
7 - 30 P
(i)
All heat pumps have electric heat.
(ii)
Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max-
imum is 292 volts.
(iii)
Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.
(iv)
Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.
(v)
Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-
style time delay fuses.
Table 4.
Power receptacle configurations
Unit
Voltage
Rating
230/
208
230/
208
230/
208
265
265
Unit plug
Plug amp
rating
15
20
30
15/20
30
NEMA
designation
6-15P
6-20P
6-30P
7-15P/7-20P 7-30P
Receptacle
Receptacle
amp rating
20
20
30
20
30
NEMA
designation
6-20R
6-20R
6-30R
7-20R
7-30R