PTAC-SVX01C-EN
25
Operation
Table 19. Cooling temperature change - air conditioners
Room
air dry
bulb
Room air wet
bulb
PTEE0701 PTEE0702 PTEE0901 PTEE0902 PTEE1201 PTEE1202 PTEE1501 PTEE1502
Temperature across
indoor coil (
∆
T)
Temperature across
indoor coil (
∆
T)
Temperature across
indoor coil (
∆
T)
Temperature across
indoor coil (
∆
T)
Min
Max
Min
Max
Min
Max
Min
Max
Rating Btu/H
7200
7600
8800
9000
11700
12000
14100
14300
Rating cfm
230
260
240
270
300
330
315
355
90
85
1
3
2
6
1
5
1
4
80
8
13
11
14
9
13
8
12
75
19
22
19
22
18
22
16
20
70
30
33
28
30
26
30
25
27
85
80
4
9
7
11
5
10
5
8
75
14
19
15
18
13
18
12
16
70
23
27
23
25
21
25
20
23
65
34
36
31
33
29
33
28
30
80
75
9
14
11
14
9
13
8
12
70
18
21
18
20
15
20
15
18
65
26
29
24
27
23
26
21
24
60
35
36
32
33
29
33
29
30
75
70
12
16
13
16
10
15
10
14
65
18
22
18
21
15
20
15
19
60
25
28
23
26
21
25
20
24
55
31
34
28
31
26
30
26
28
70
65
12
15
12
14
9
13
9
13
60
17
20
16
18
13
17
13
17
55
22
24
20
22
18
21
17
21
Table 20. Cooling temperature change - heat pumps
Room
airdry
bulb
Room air wet
bulb
PTHE0701 PTHE0702 PTHE0901
PTHE0902 PTHE1201 PTHE1202 PTHE1501 PTHE1502
Temperature across
indoor coil (
∆
T)
Temperature
acrossndoor coil (
∆
T)
Temperature across
indoor coil (
∆
T)
Temperature across
indoor coil (
∆
T)
Min
Max
Min
Max
Min
Max
Min
Max
rating Btu/H
7300
7600
9000
9300
11800
12000
14000
14600
rating cfm
195
225
240
270
315
355
315
355
90
85
1
3
2
6
1
5
1
4
80
8
13
11
15
10
13
8
12
75
19
22
19
22
18
22
17
20
70
30
33
29
30
26
30
25
28
85
80
4
9
7
11
5
10
5
9
75
14
19
15
18
14
18
12
16
70
23
27
23
25
21
25
21
23
65
33
36
31
33
30
33
28
31
80
75
9
14
11
15
10
13
8
12
70
18
21
18
20
16
20
16
18
65
26
29
24
27
23
26
22
25
60
35
36
32
33
30
33
29
31
Содержание PTAC-SVX01C-EN