PKGP-PRC004-EN
27
Performance
Data
Table PD-14 — Belt Drive Evaporator Fan Performance WSC090AD,T Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Mtr & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4080
—
—
686
0.43
737
0.49
787
0.57
831
0.64
870
0.70
908
0.76
944
0.84
980
0.92
1015 0.99
4590
718
0.53
753
0.59
792
0.65
839
0.72
882
0.80
922
0.88
958
0.95
992
1.02
1026 1.10
1058 1.18
5100
789
0.71
822
0.78
853
0.84
892
0.91
935
0.99
974
1.08
1011
1.18
1044
1.25
1076 1.33
1106 1.41
5610
862
0.93
892
1.01
921
1.08
951
1.15
988
1.22
1026
1.31
1062
1.42
1096
1.52
1129 1.61
1158 1.69
6120
934
1.20
963
1.28
990
1.35
1016
1.43
1045
1.51
1079
1.59
1115
1.69
1148
1.80
1180 1.91
1210 2.02
1.50 Nom kW Standard Motor &
2.24 Nom kW OS
Hi Static Drive
Motor & Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are Definite
Purpose Motors, Specifically Designed And Tested To Operate
Reliably And Continuously At All Cataloged Conditions. Using The
Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular
Data Will Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Pascals)
275
300
325
350
375
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Hi Static Drive
4080
1051
1.07
1085
1.15
1118
1.23
1152
1.31
1185
1.39
4590
1090
1.27
1122
1.36
1153
1.45
1185
1.53
1216
1.62
5100
1136
1.49
1165
1.59
1194
1.68
1223
1.78
1251
1.88
5610
1187
1.78
1214
1.86
1242
1.96
1269
2.06
1296
2.17
6120
1239
2.12
1266
2.21
1291
2.30
1317
2.39
1343
2.49
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Table PD-14a — Belt Drive Evaporator Fan Performance WSC090AD,T Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & Low Static Drive
2 HP Standard Motor & Drive
2400
—
—
686
0.58
737
0.66
787
0.76
831
0.85
870
0.93
908
1.02
944
1.12
980
1.23
1015 1.33
2700
718
0.71
753
0.79
792
0.87
839
0.96
882
1.08
922
1.18
958
1.27
992
1.36
1026 1.47
1058 1.59
3000
789
0.96
822
1.04
853
1.13
892
1.22
935
1.33
974
1.45
1011
1.58
1044
1.68
1076 1.78
1106 1.88
3300
862
1.25
892
1.35
921
1.44
951
1.54
988
1.64
1026
1.76
1062
1.90
1096
2.04
1129 2.16
1158 2.27
3600
934
1.61
963
1.71
990
1.81
1016
1.92
1045
2.02
1079
2.13
1115
2.27
1148
2.41
1180 2.57
1210 2.71
2 HP Standard Motor & Static Drive
2 HP Std Motor & Hi Static Drive
3 HP Over-Sized Motor
& Hi Static Drive
Factory Supplied Motors, In Commercial Equipment Are Definite
Purpose Motors, Specifically Designed And Tested To Operate
Reliably And Continuously At All Cataloged Conditions. Using The
Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular
Data Will Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & Hi Static Drive
2400
1051
1.44
1085
1.54
1118
1.64
1152
1.75
1185
1.86
2700
1090
1.70
1122
1.82
1153
1.94
1185
2.06
1216
2.18
3000
1136
2.00
1165
2.13
1194
2.26
1223
2.39
1251
2.52
3300
1187
2.39
1214
2.50
1242
2.63
1269
2.76
1296
2.90
3600
1239
2.84
1266
2.96
1291
3.08
1317
3.20
1343
3.34
3 HP Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Содержание Precedent WSC060AD
Страница 1: ...Packaged Heat Pumps Precedent WSC060 120 50 Hz PKGP PRC004 EN February 2004 ...
Страница 50: ...50 PKGP PRC004 EN ...
Страница 51: ...PKGP PRC004 EN 51 ...