PKGP-PRC004-EN
25
Performance
Data
Table PD-12 — Belt Drive Evaporator Fan Performance WSC072AD,T Horizontal Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
1.12 Nom kW Standard Motor & Drive
3260
535
0.21
595
0.26
654
0.32
703
0.36
750
0.42
794
0.48
838
0.55
882
0.61
923
0.67
963
0.73
3670
590
0.29
638
0.34
695
0.40
745
0.46
789
0.51
830
0.58
871
0.65
910
0.72
950
0.79
987
0.86
4080
647
0.38
686
0.43
737
0.49
787
0.57
831
0.64
870
0.70
908
0.76
944
0.84
980
0.92
1015 0.99
4490
703
0.50
740
0.55
781
0.61
828
0.68
872
0.77
911
0.84
948
0.91
983
0.98
1016 1.06
1049 1.14
4890
761
0.64
795
0.70
828
0.76
871
0.83
913
0.91
953
1.00
990
1.08
1023
1.15
1055 1.23
1086 1.31
1.12 Nom kW Standard Motor & Drive
1.12 Nom kW Standard Motor &
Hi Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Hi Static Drive
3260
1002
0.80
1038
0.87
1073
0.94
1107
1.01
1140
1.09
3670
1025
0.93
1060
1.00
1096
1.07
1129
1.15
1162
1.23
4080
1051
1.07
1085
1.15
1118
1.23
1152
1.31
1185
1.39
4490
1081
1.23
1113
1.31
1146
1.40
1178
1.49
1208
1.57
4890
1117
1.40
1147
1.49
1178
1.59
1206
1.68
1236
1.77
1.50 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
Factory Supplied Motors, In Commercial Equipment, Are Definite
Purpose Motors, Specifically Designed And Tested To Operate
Reliably And Continuously At All Cataloged Conditions. Using The Full
Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data
Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our
Product’s Warranty Will Not Be Affected.
Table PD-12a — Belt Drive Evaporator Fan Performance WSC072AD,T Horizontal Configuration (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
1-1/2 HP Standard Motor & Drive
1920
535
0.28
595
0.34
654
0.42
703
0.49
750
0.56
794
0.65
838
0.73
882
0.82
923
0.90
963
0.99
2160
590
0.39
638
0.45
695
0.53
745
0.62
789
0.69
830
0.77
871
0.87
910
0.96
950
1.06
987
1.15
2400
647
0.51
686
0.58
737
0.66
787
0.76
831
0.85
870
0.93
908
1.02
944
1.12
980
1.23
1015 1.33
2640
703
0.67
740
0.74
781
0.82
828
0.92
872
1.03
911
1.13
948
1.22
983
1.31
1016 1.42
1049 1.53
2880
761
0.85
795
0.94
828
1.02
871
1.11
913
1.22
953
1.34
990
1.45
1023
1.55
1055 1.65
1086 1.75
1-1/2 HP Standard Motor & Drive
1-1/2 HP Std Motor & Hi Static Drive
Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose
Motors, Specifically Designed And Tested To Operate Reliably And
Continuously At All Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In
Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will
Not Be Affected.
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Hi Static Drive
1920
1002
1.08
1038
1.17
1073
1.27
1107
1.36
1140
1.46
2160
1025
1.25
1060
1.34
1096
1.44
1129
1.54
1162
1.65
2400
1051
1.44
1085
1.54
1118
1.64
1152
1.75
1185
1.86
2640
1081
1.65
1113
1.76
1146
1.88
1178
1.99
1208
2.10
2880
1117
1.88
1147
2.00
1178
2.13
1206
2.25
1236
2.38
2 HP Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
2 HP – Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500