26
PKGP-PRC004-EN
Performance
Data
Table PD-13a — Belt Drive Evaporator Fan Performance WSC090AD,T Downflow Configuration (IP)
External Static Pressure (Inches of Water)
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor & Low Static Drive
2 HP Standard Motor & Drive
2400
—
—
—
—
670
0.57
720
0.66
768
0.76
810
0.84
850
0.93
888
1.02
925
1.12
961
1.22
2700
—
—
673
0.66
719
0.74
763
0.84
807
0.94
850
1.04
889
1.14
926
1.24
961
1.34
995
1.44
3000
680
0.76
727
0.87
770
0.95
810
1.05
849
1.16
890
1.27
929
1.38
967
1.50
1000 1.61
1034 1.72
3300
739
0.98
782
1.11
823
1.21
861
1.30
897
1.41
933
1.50
969
1.66
1006
1.78
1041 1.91
1074 2.03
3600
798
1.25
838
1.39
876
1.50
913
1.61
947
1.72
980
1.84
1013
1.97
1047
2.11
1080 2.24
1113 2.38
2 HP Standard Motor &
Hi Static Drive
External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
1.50
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
2 HP Standard Motor
2 HP Standard Motor &
& Drive
Hi Static Drive
2400
995
1.32
1027
1.42
1060
1.52
1091
1.62
1121
1.73
2700
1027
1.55
1059
1.65
1091
1.77
1121
1.88
1151
2.00
3000
1065
1.83
1095
1.94
1125
2.05
1154
2.17
1183
2.30
3300
1104
2.15
1134
2.27
1163
2.40
1191
2.52
1217
2.64
3600
1144
2.52
1173
2.65
1202
2.78
1229
2.91
1256
3.05
3 HP Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475
Factory Supplied Motors, In Commercial Equipment,
Are Definite Purpose Motors, Specifically Designed And Tested To
Operate Reliably And Continuously At All Cataloged Conditions.
Using The Full Horsepower Range Of Our Fan Motors As Shown In
Our Tabular Data Will Not Result In Nuisance Tripping Or Premature
Motor Failure. Our Product’s Warranty Will Not Be Affected.
Table PD-13 — Belt Drive Evaporator Fan Performance WSC090AD,T Downflow Configuration (SI)
External Static Pressure (Pascals)
25
50
75
100
125
150
175
200
225
250
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Standard Motor & Low Static Drive
1.50 Nom kW Standard Motor & Drive
4080
—
—
—
—
670
0.43
720
0.50
768
0.56
810
0.63
850
0.70
888
0.76
925
0.83
961
0.91
4590
—
—
673
0.49
719
0.55
763
0.63
807
0.70
850
0.78
889
0.85
926
0.93
961
1.00
995
1.08
5100
680
0.57
727
0.65
770
0.71
810
0.78
849
0.86
890
0.95
929
1.03
967
1.12
1000 1.20
1034 1.28
5610
739
0.73
782
0.83
823
0.90
861
0.97
897
1.05
933
1.12
969
1.23
1006
1.33
1041 1.42
1074 1.52
6120
798
0.94
838
1.04
876
1.12
913
1.20
947
1.28
980
1.37
1013
1.47
1047
1.57
1080 1.67
1113 1.77
1.50 Nom kW Standard Motor
& Hi Static Drive
External Static Pressure (Pascals)
275
300
325
350
375
m
3
/h
RPM
kW
RPM
kW
RPM
kW
RPM
kW
RPM
kW
1.50 Nom kW Std Motor
1.50 Nom kW Standard Motor &
& Drive
Hi Static Drive
4080
995
0.98
1027
1.06
1060
1.13
1091
1.21
1121
1.29
4590
1027
1.15
1059
1.23
1091
1.32
1121
1.40
1151
1.49
5100
1065
1.36
1095
1.45
1125
1.53
1154
1.62
1183
1.71
5610
1104
1.60
1134
1.70
1163
1.79
1191
1.88
1217
1.97
6120
1144
1.88
1173
1.98
1202
2.08
1229
2.17
1256
2.27
2.24 Nom kW Over-Sized Motor & Hi Static Drive
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139
Factory Supplied Motors, In Commercial Equipment, Are Definite
Purpose Motors, Specifically Designed And Tested To Operate
Reliably And Continuously At All Cataloged Conditions. Using The
Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular
Data Will Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.