12
SPECIFICATIONS
Chilled Mode (continued)
There is an interval set for defrosting, however, the defrost timer is built intelligent - it
detects whether or not there is ice building up on the coil. If there is no ice building up
on the coil, it extends the defrost interval, and if there is Ice building up earlier on the
coil it reduces the defrost interval. The maximum interval is 48 hours.
Frozen mode
Every 8 hours of compressor operation. Defrost interval increases 2 hours each
timed defrost interval. Maximum time interval in Frozen mode is 24 hours.
Reset to Base Time
Defrost timer resets if the unit is off more than 12 hours, setpoint is changed more
than 5 C (9 F) or PTI pretrip test occurs.
Defrost Termination:
Defrost (Coil) Sensor
Chilled mode:
Terminates defrost when coil sensor temperature rises to 18 C (65 F).
Frozen mode:
Terminates defrost when coil sensor temperature rises to 18 C (65 F).
Termination Timer
Terminates defrost after 90 minutes at 60 HZ operation if coil sensor has not
terminated defrost (120 minutes at 50 Hz operation)
Power Off
Turning Unit On/Off switch Off terminates defrost
MP-4000 CONTROLLER SPECIFICATIONS (CONTINUED)
Содержание MP-4000
Страница 2: ...Magnum TK 61110 4 OP Rev 0 11 13 En ...
Страница 3: ......
Страница 10: ...7 UNIT INSPECTION ...
Страница 24: ...21 Controller Description ...
Страница 28: ...25 NAVIGATING THE CONTROLLER OPERATING MENU ...