9
SPECIFICATIONS
External Static
Pressure (water
column)
460/230V, 3 Phase, 60 Hz Power
380/190V, 3 Phase, 50 Hz Power
High Speed
Low Speed
High Speed
Low Speed
m
3
/hr
ft
3
/min
m
3
/hr
ft
3
/min
m
3
/hr
ft
3
/min
m
3
/hr
ft
3
/min
0 mm (0 in.)
6,560
3,860
3,170
1,865
5,480
3,225
2,710
1,595
10 mm (0.4 in.)
5,820
3,425
1,770
1,040
4,530
2,665
930
545
20 mm (0.8 in.)
5,000
2,940
—
—
3,750
2,205
—
—
30 mm (1.2 in.)
4,430
2,610
—
—
2,930
1,725
—
—
40 mm (1.6 in.)
3,520
2,070
—
—
1,870
1,100
—
—
Compressor Motor:
Type
460/380V, 60/50 Hz, 3 Phase
Kilowatts
4.48 kW @ 460V, 60 Hz
Horsepower
6.0 hp @ 460V, 60 Hz
RPM
3550 RPM @ 460V, 60 Hz
Locked Rotor Amps
70 amps @ 460V, 60 Hz
Condenser Fan Motor:
Type
460/380V, 60/50 Hz, 3 Phase
Kilowatts
0.55 kW @ 460V, 60 Hz
Horsepower
0.75 hp @ 460V, 60 Hz
Number: All Models
1
Motor:
RPM
1725 RPM @ 460V, 60 Hz
Full Load Amps
1.0 amps @ 460V, 60 Hz; 1.0 amps @ 380V, 50 Hz
Содержание MP-4000