background image

Installation

16

 CLCH-SVX08C-EN

Duct Connections

All duct connections to the gas heat section should be 
installed in accordance with the standards of the National 
Fire Protection Association (NFPA) and the Sheet Metal 
and Air Conditioning Contractors National Association, 
Inc. (SMACNA).

Combustion Air Duct

Outdoor units with internal vestibules have a rain hood 
that requires field mounting.

Outdoor units with external vestibules do not have a 
rain hood. Combustion air enters through openings in 
the bottom of the vestibule.

All indoor units ship with a screened opening on the 
combustion air inlet.

If combustion air is to be ducted to the gas heat vestibule, 
the unit’s capacity must be derated to account for the 
resistance in the air duct. For every 0.14 inches wg of duct 
resistance, unit capacity (MBh output) will reduce by five 
percent.

If combustion air is ducted to the vestibule air intake, the 
perforated inlet panel on the side of the vestibule needs to 
be cut out before ducting to the unit.

If combustion air is ducted to the vestibule, it is strongly 
recommended that an experienced gas heat technician 
check the system and emission levels in the exhaust flue at 
start up. Carbon dioxide should be between 8.2 and 9.4 
percent. This corresponds to the allowable range of excess 
air needed for combustion. The additional static pressure 
of the inlet air duct may change the fuel-air ratio slightly 
necessitating system adjustment. 

Separated combustion can be a desirable option, but will 
require more field-installation time and material. The 
burner fans are not sized to handle any static in the 
combustion air stream. A booster fan will likely be 
required to overcome combustion air duct static. 

Combustion air cannot be ducted directly to the 
combustion air fan. The airflow through the vestibule is 
needed to keep the temperatures in the vestibule down. 

Duct Transitions

When the gas heat section is the last section of the air 
handler, and duct transitions should be smooth and 
uniform from all sides. Follow recommendations for duct 
transitions from SMACNA.

Fasten the ductwork directly to the ductwork opening. 
When using lined ductwork, the insulation should not 
obstruct the discharge opening.

Airflow Direction

The airflow direction through the gas heater is important 
because it prevents localized “hot spots” on the heat 
exchanger. Airflow direction labels denoting correct 

airflow direction through the gas heat section are provided 
on the burner side of the heating section. See 

Figure 10

.

Airflow from the supply fan should enter on the drum (or 
primary) side of the heat exchanger (

Figure 11

) and exit on 

the tube (or secondary) side (

Figure 12

). 

Figure 10. Airflow direction label

Figure 11.

Entering airside (drum or primary) of gas 
heat section

Note: Reference burner nameplate for recommended gas manifold pressure at startup.

Содержание K01K12345

Страница 1: ...training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and...

Страница 2: ...n which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage o...

Страница 3: ...ion sizes for gas heat sections figure in Installation chapter Updated Duct Connection section in Installation chapter Added Gas heat internal piping penetration location and Gas heat external piping...

Страница 4: ...stalling Outdoor Flue Stacks 14 Installing Indoor Flue Stacks 15 Installing Rain Hood Combustion Air Inlet 15 Installing Flue Stack for Hurricane Applica tions 15 Duct Connections 16 Combustion Air Du...

Страница 5: ...handler section includes a nameplate label see Figure 1 which identifies the type of section customer tagging information the unit serial number the unit order number the build section position for in...

Страница 6: ..._________________________________________ Altitude Above Sea Level___________________________________________________________________ Calorific Value___________________________________________________...

Страница 7: ...gure 2 The external vestibule if required ships attached to the gas heat section Some heaters have gas train components in an internal vestibule see Figure 3 Refer to Table 2 for vestibule locations F...

Страница 8: ...25 560 Ext 50 1750 Ext 120 1000 Int 25 700 Ext 50 2000 Ext 120 1250 Int 25 860 Ext 57 560 Int 120 1500 Int 25 1000 Ext 57 700 Int 120 1750 Int 30 320 360 Int 57 860 Int 120 2000 Int 30 560 Int 57 100...

Страница 9: ...removed before assembly to the air handler Instruction Manuals Individual instruction manuals for all of the gas train components such as flame control relay valves pressure switches and actuators sh...

Страница 10: ...or units that will be installed indoors However when outdoor storage is necessary several things must be done to prevent damage Note Keep the equipment on the original wooden blocks skid for protectio...

Страница 11: ...ltage panel 61 61 61 61 61 61 61 61 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 64 D internal starter or VFD 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 48 E fan 48 48...

Страница 12: ...75 85 50 92 50 107 50 119 75 119 75 Width 93 50 100 00 112 50 125 50 125 50 140 50 140 50 154 50 182 00 Height for outdoor unit includes base drip lip b 69 25 75 00 75 00 84 38 94 13 97 63 112 63 124...

Страница 13: ...o the gas heat system if thesupply fan isshut off The gas heat system must not operate without the supply fan providing airflow All wiring must comply with applicable local and National Electric Code...

Страница 14: ...ove the flue from inside the unit once the unit is assembled Installation High Altitude Installations Adjustment of gas train linkages is not normally required However for high altitude installations...

Страница 15: ...r the combustion air opening ship loose and must be installed at the job site The assembly consists of the hood butyl tape and number 10 screws Install butyl tape between the hood and the side panel o...

Страница 16: ...additional static pressure of the inlet air duct may change the fuel air ratio slightly necessitating system adjustment Separated combustion can be a desirable option but will require more field insta...

Страница 17: ...on and Deadly Gases Never solder braze or weld on refrigerant lines or any unit components that are above atmospheric pressure or where refrigerant may be present Always remove refrigerant by followin...

Страница 18: ...he same side as the gas train located inside the piping vestibule Since the drain line is equipped with a shut off valve a condensate p trap is not required but may be installed for convenience to avo...

Страница 19: ...ield wiring poses FIRE and ELECTROCUTION hazards To avoid these hazards you MUST follow requirements for field wiring installation and grounding as described in NEC and your local state electrical cod...

Страница 20: ...power the transformer TRANS1 Low Voltage Wiring The gas heat control system requires a binary signal for on off control Provide an interlock in the start stop signal circuit with the air handler supp...

Страница 21: ...Wiring CLCH SVX08C EN 21 Figure 16 Natural gas 200 320 MBh 10 1 turndown...

Страница 22: ...Wiring 22 CLCH SVX08C EN Figure 17 Natural gas 360 1000 MBh 3 1 and 10 1 turndown and propane 200 1000 MBh...

Страница 23: ...Wiring CLCH SVX08C EN 23 Figure 18 Single phase natural gas and propane 1250 2000 MBh 3 1 and 10 1 turndown...

Страница 24: ...Wiring 24 CLCH SVX08C EN Figure 19 3 Phase propane and natural gas 1250 2000 MBh 3 1 and 10 1 turndown with power exhaust...

Страница 25: ...Wiring CLCH SVX08C EN 25 Figure 20 Natural gas and propane1250 2400 MBh 20 1 turndown...

Страница 26: ...w g Attach another manometer to the burner manifold if optional gauge or sensor is not selected to check the burner manifold pressure when the unit is operational Typical pressure should be between 2...

Страница 27: ...er assembly The following safety limit contracts should be closed HLl1 high temperature limit Al1 airflow interlock air handling fan should either be running or started 60 seconds after call for heat...

Страница 28: ...ignition transformer and automatic gas valves will energize With the manual gas cocks closed the burner should go into a safety lockout condition The flame safeguard will have to be reset manually Tur...

Страница 29: ...luminate The modulating gas valve actuator starts to open and the main light on the flame relay module should illuminate Note that it could take as long as 30 seconds for the actuator to fully open 6...

Страница 30: ...d drain any accumulated condensate 3 Check all electrical terminals for tight connections 4 Open all manual gas valves and ensure that these valves operate freely 5 Check the air shutter and modulatin...

Страница 31: ...densate from heat exchanger Weekly This task only needs to be done if the unit runs for extended hours at low fire Clean air inlet louver Monthly Use brush and vacuum cleaner Clean combustion air blow...

Страница 32: ...gh Limit This switch trips due to a high temperature condition in the gas heat section Allow the air handler fan to run and cool heat exchanger The switch must be manually reset when the heat exchange...

Страница 33: ...quate grounding and that it is properly located in the flame Also ensure that temperature at flame rod insulator is no greater than 500 F 260 C Perform Ignition Interference Test per component manufac...

Страница 34: ......

Страница 35: ......

Страница 36: ...and protect food and perishables and increase industrial productivity and efficiency We are a global business committed to a world of sustainable progress and enduring results ingersollrand com Ingers...

Отзывы: