System Configuration and Pre-Start
42
OAU-SVX006E-EN
AO-01
Hot Gas Reheat Valve
Command
0–100
%
Analog hot gas reheat output.
AO-02
Supply Fan Speed
Command
0–100
%
Supply fan speed output.
AO-03
Compressor Speed
Command Circuit 1
0–100
%
Speed control for circuit 1 digital scroll or variable
speed
compressor.
AO-04
Exhaust Fan Speed
Output Command
0–100
%
Exhaust fan speed output
AO-05
Outdoor Air Damper
Position Command
0–100
%
Position command for outdoor air damper. Return
air
damper position is inverse to this output.
AO-06
Energy Recovery
Outdoor Air Bypass
Position Command
0–100
%
Analog output for modulating ERV outdoor air
bypass.
AO-07
Condenser Fan Speed
Command
0–100
%
Analog condenser fan speed command.
AO-08
Compressor Speed
Command Circuit 2
0–100
%
Speed control for circuit 1 digital scroll or variable
speed
compressor.
AO-09
Chilled Water Valve
Command
0–100
%
Analog chilled water actuator valve output
command.
AO-10
Energy Recovery Wheel
Speed
Command
0–100
%
Analog ERV VFD command.
AO-11
Heating Output
Command
0–100
%
Analog heating output command. Modulating
burner only
for gas heat.
AO-12
Second Stage
Condenser Fan Speed
Command
0–100
%
Analog condenser fan speed command for the
second
stage.
AO-13
Energy Recovery
Exhaust Air Bypass
Position Command
0–100
%
Analog output for modulating ERV exhaust air
bypass.
AV-01
Occupied Cooling
Setpoint
●
72°F
55–85
°F
Space cooling setpoint used in occupied mode.
AV-02
Occupied Heating
Setpoint
●
70°F
55–85
°F
Space heating setpoint used in occupied mode.
AV-04
Heat Pump Disable
Temperature
●
25°F
0–60
°F
Heat pump operation is disabled when the outdoor
air
temperature falls below this setpoint.
AV-05
Dehumidification
Temperature Active
-58–482
°F
Temperature reading for dehumidificaiton. For OAN
Rev. 6 cabinets this is discharge air dewpoint, all
other it's indoor
coil leaving temperature.
AV-07
Space Humidity Active
0–100
%
Actively used space relative humidity.
AV-08
Space Humidity BAS
●
0–100
%
Communicated space relative humidity. Takes
priority over
hardwired input when put In Service.
AV-10
Outdoor Air Dewpoint
Enable Setpoint
●
55°F
45–100
°F
Setpoint used to put the unit into dehumidification.
AV-11
Outdoor Air Dewpoint
-10–150
°F
Dewpoint of the outdoor air. This point is calculated
within
the program.
AV-12
Exhaust Fan Tracking
Offset Setpoint
●
0.9
0–150
%
Setpoint used to track with the supply fan speed.
Factory default is Out of Service. When put In
Service it takes priority over other exhaust fan
control schemes.
Table 8.
Chart of analog and binary input/output (continued)
#
BACnet Point Name
Write
Default
Range
Units
Description