background image

Installation

20

 GUNE-SVX001A-EN

Combustion Air

Notes:

Combustion and exhaust venting instructions below 
describe two-pipe venting of a duct furnace configured 
for separated combustion. 

If converting the duct furnace to separated 
combustion, use the air inlet conversion kit that 
shipped loose with the unit.

If venting a separated combustion duct furnace 
concentrically (through one roof or wall termination), a 
Combustion Air Inlet Kit (X7) is required and 
instructions included with the kit should be followed 
with regards to vent pipe installation.

To convert the unit to separated combustion remove 
screen and mounting plate from air inlet on top panel of 
unit by removing four (4) screws. Secure ship loose inlet 
collar and gasket to inlet opening re-using the four (4) 
screws removed in previous step. The access panel must 
also be sealed using the ship loose gasket. Cut gasket to 
lengths listed in 

Table 8

. Remove paper backing and 

adhere to access panel making certain that the entire 
perimeter is covered (see 

Figure 22, p. 26

). After supply 

power line is run to main control board, seal the gap 
between cord and hole in rear panel with silicone sealant.

1.

\

In the United States, the combustion air system 

installation must be in accordance with the latest 
edition of ANSI Z223.1 (NFPA 54) National Fuel Gas 
Code. In Canada, installation must be in accordance 
with CSA-B149.1 “Installation Code for Natural Gas 
Burning Appliances and Equipment” and CSA-B149.2 
“Installation Code for Propane Burning Appliances and 
Equipment.”

2. A Breidert Type L or Fields Starkap, furnished by the 

customer, must be installed at the termination point of 
the combustion air system. See 

Figure 11, p. 21

 and 

Figure 12, p. 22

.

3. Each duct furnace MUST have its own combustion air 

system. It MUST NOT be connected to other air intake 
systems.

4. Combustion air intake duct may be PVC, CPVC, Type B 

vent, single wall, double wall or other material 
approved by local code authority. Never use duct size 
other than diameter stated in these instructions.

5. Long runs of single wall combustion air piping passing 

through an unheated space may require insulating if 
condensation becomes noticeable.

6. The combustion air system must be installed to 

prevent collection of condensate. Pitch horizontal 
pipes downward 1/4 inches per foot (21 mm/m) toward 
the inlet cap to facilitate drainage. Vertical combustion 
air pipes should be piped as depicted in 

Figure 11

.

7.

The equivalent length of the combustion air system 
must not be less than 5 feet (1.5 m) and must not 
exceed 50 feet (15.2 m). Equivalent length equals the 
total length of straight pipe, plus 10 feet (3.05 m) for 
each 90° elbow and 4 feet (1.22 m) for each 45° elbow.

Note:

For optimum performance keep the combustion air 
system as straight as possible.

8. Each slip joint must be secured with at least three 

corrosion resistant screws. Two full turns of 3M™ #425 
Aluminum Foil Tape or its equivalent must then be 
used to seal each joint. General Electric RTV-108, 
Dow-Corning

®

 RTV-732 or an equivalent may be used 

instead of tape.

9. For horizontal combustion air systems longer than 

5 feet (1.5 m), the system must be supported from 
overheard building structures at 4 feet (1.22 m) 
maximum intervals in the United States and at 3 feet 
(1 m) maximum intervals in Canada.

WARNING

Carbon Monoxide Poisoning!

Never operate separated combustion duct furnaces 
without combustion air and flue gas piping in place. 
Each duct furnace MUST have its own combustion air 
system and MUST NOT be connected to other vent 
systems or to a chimney. Your venting system must not 
be blocked by any snow, snow drifts, or any foreign 
matter. Inspect your venting system to ensure adequate 
ventilation exists at all times! Failure to follow these 
instructions could result in Carbon Monoxide Poisoning 
(symptoms include grogginess, lethargy, inappropriate 
tiredness, or flu-like symptoms) which could result in 
death or serious injury.

Table 8.

Gasket lengths

Unit 
Size

Top/Bottom 

Gasket Length (in) Qty

Right/Left 

Gasket Length (in) Qty

010

8-3/4

2

28-1/8

2

015

12

2

28-1/8

2

020

15-1/4

2

28-1/8

2

025

18-1/2

2

28-1/8

2

030

21-3/4

2

28-1/8

2

035

25

2

28-1/8

2

040

28-1/4

2

28-1/8

2

Содержание GUNE

Страница 1: ...c knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in th...

Страница 2: ...and your local state electrical codes WARNING Personal Protective Equipment PPE Required Installing servicing this unit could result in exposure to electrical mechanical and chemical hazards Before in...

Страница 3: ...lane hangars when installed in accordance with current ANSI NFPA No 409 and in public garages when installed in accordance with current NFPA No 88A and NFPA No 88B If installed in Canada the installat...

Страница 4: ...e service panel and the heater To ensure a proper ground the grounding means must be tested by a qualified technician Do not insert fingers or foreign objects into the heater or its combustion air mov...

Страница 5: ...de 12 Gas Pipe Sizing 13 Pipe Sizing 13 Pipe Installation 14 Venting 16 Venting for Power Vented Duct Furnaces Category III 16 Vertically Vented Duct Furnaces Category III 17 Horizontally Vented Duct...

Страница 6: ...nic Modulating w Room Sensing J Electronic Modulating w Duct Thermostat L Electronic Modulation w External 4 20 mA Input M Electronic Modulation w External 0 10 Vdc Input T Single Stage Direct Spark I...

Страница 7: ...t Furnace is a factory assembled power vented and low static pressure type duct furnace with a low profile cabinet The duct furnace can also be easily field converted to separated combustion The desig...

Страница 8: ...33 5 33 5 33 5 831 831 831 851 851 851 851 F Flue Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 G Air Inlet Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 Gas Inlet Natural Gas inc...

Страница 9: ...ations between 0 and 2 000 feet 610m 2 For unit installations in U S A above 2 000 feet 610 m the unit input must be field derated 4 percent for each 1 000 feet 305 m above sea level refer to local co...

Страница 10: ...by a partition not less than 18 inches 457 mm high Refer to the latest edition of NFPA 88A Parking Structures In Canada installation must be in accordance with the latest edition of CSA B149 Installat...

Страница 11: ...ibration Air Flow The installation is to be adjusted to obtain an air throughput within the range specified on the appliance rating plate Combustion Inlet Air Ventilation Inlet Air From Another Room I...

Страница 12: ...reen and block off plate locations once the unit has been flipped However due to combustion noise it is recommended to keep the air inlet screen on top for overhead installations Important If unit acc...

Страница 13: ...on for use with propane bottled gas must be made by a qualified LP gas dealer or installer He She will ensure that proper joint compounds are used for making pipe connections that air is purged from l...

Страница 14: ...ze in Internal Diameter in Length of Pipe feet meters 10 20 30 40 50 60 70 80 90 100 125 150 175 200 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622 175 120 97 82 73 66 61...

Страница 15: ...Damage Do not over tighten the inlet gas piping into the valve This may cause stresses that will crack the valve Figure 8 Pipe installation standard controls Table 5 Gas supply pressure a a Applicabl...

Страница 16: ...rom the venter outlet before installing an elbow in the vent system An elbow should never be attached directly to the venter Any run of single wall vent pipe exposed to cold air or passing through an...

Страница 17: ...ew elbows as possible 5 Avoid running vent pipe through unheated spaces 6 When this cannot be avoided insulate the pipe to prevent condensation of moisture on the walls of the pipe 7 Do not damper the...

Страница 18: ...sance or hazard or could be detrimental to the operation of regulators relief valves or other equipment Figure 10 p 19 and Table 7 p 17 for vent terminal height and snow consideration requirements 6 T...

Страница 19: ...Vertical Flue Height 1 4 per foot Min Slope 21 mm m Thimble Roof Use Insulated Stack Outdoors Approved Vent Terminal Figure 10 Horizontally vented Category III standard combustion D9378B Condensate Dr...

Страница 20: ...ameter stated in these instructions 5 Long runs of single wall combustion air piping passing through an unheated space may require insulating if condensation becomes noticeable 6 The combustion air sy...

Страница 21: ...stems longer than 5 feet 1 5 m the system must be supported from overheard building structures at 4 feet 1 22 m maximum intervals in the United States and at 3 feet 1 m maximum intervals in Canada 9 T...

Страница 22: ...Leg and Cleanout Cap Roof Flashing Breidert Type L or Fields Approved Terminal 10 ft 3 04m Min to Wall or Adjoining Building 2 ft 609m Min Plus Max Snow Depth for Area 3 ft 1m Min Plus Max Snow Depth...

Страница 23: ...Installation GUNE SVX001A EN 23 Figure 14 Vertical arrangement single wall vent system to single wall termination Figure 15 Horizontal arrangement single wall vent system to single wall termination...

Страница 24: ...Installation 24 GUNE SVX001A EN Figure 16 Vertical arrangement single wall vent system to double wall termination Figure 17 Horizontal arrangement single wall vent system to double wall termination...

Страница 25: ...Outside walls or areas where drafts may affect the operation of the control 2 Hot Areas Areas where the sun s rays radiation or warm air currents may affect the operation of the control 3 Dead Areas A...

Страница 26: ...al Connections 26 GUNE SVX001A EN Figure 21 Tubular duct furnaces equipped with natural gas or propane LP gas single stage Figure 22 Tubular duct furnaces equipped with natural gas or propane LP gas t...

Страница 27: ...mperature of the space being heated The thermostat must be mounted on a vertical vibration free surface free of air currents and in accordance with the furnished instructions also refer to Electrical...

Страница 28: ...ust be maintained for proper operation of the duct furnace If the duct furnace is equipped with a pressure regulator on the combination gas valve follow Step 1 through Step 4 above If the duct furnace...

Страница 29: ...2 2292 96 3 001 4 000 916 1 220 2 9 722 8 4 2092 92 4 001 5 000 1 221 1 525 2 7 673 7 7 1918 88 5 001 6 000 1 526 1 830 2 4 598 7 0 1744 84 6 001 7 000 1 831 2 135 2 2 548 6 4 1594 80 7 001 8 000 2 1...

Страница 30: ...owed when the equipment was installed Have all field installed controls been installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equi...

Страница 31: ...ir inlet for blockage debris Clear if any found 7 Reassemble the duct furnace by replacing all parts in reverse order 8 Complete the appropriate unit start up procedure as given in the Operation secti...

Страница 32: ...lar duct furnace component index 1 Vestibule panel tube assembly heat exchanger 2 Manifold 3 Manifold bracket sub assembly 4 Inshot burner 5 Burner orifice 6 Gas valve 7 Gas inlet pipe 8 Gas inlet gro...

Страница 33: ...nd the following information to your local representative if further assistance is needed contact the manufacturer s customer service department Unit number Serial number Part description and number a...

Страница 34: ...logged main burners Clean main burner ports Misaligned orifices Replace manifold assembly Insufficient combustion air Refer to Clearances p 10 and Venting p 16 to ensure unit is properly mounted and v...

Страница 35: ...inal strip R and W Shorted circuit Check thermostat circuit for shorts or any staples piercing wires Defective thermostat If thermostat is calling after set point has been satisfied replace Defective...

Страница 36: ...or 24 V on terminals R and W1 on terminal strip Loose wiring or connection Check all wiring in the power vent circuit to ensure good connection including neutral Motor overload protection is tripping...

Страница 37: ...tus Indicates Check Repair Slow Flash Control OK no call for heat Not Applicable Fast Flash Control OK call for heat present Not Applicable Steady Off Internal control fault or no power 1 Line voltage...

Страница 38: ...drocarbons precipitated in the air to any workmanship of the installer of the Product This limited warranty is conditional upon advising the installing contractor who in turn notify the distributor or...

Страница 39: ...lio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and r...

Отзывы: