background image

10

 GUNE-SVX001A-EN

Installation

Locating Units

Important:

Location of unit heaters is related directly to 
the selection of sizes. Basic rules are as 
follows,

Clearances

Maintain adequate clearances around air openings into 
the combustion chamber:

Accessibility Clearance

The duct furnace must have 18 inches (457 mm) clearance 
on the control cabinet end. Provision should also be made 
to assure accessibility for recurrent maintenance 
purposes.

Atmospheric Considerations

Atmospheres containing commercial solvents or 
chlorinated hydrocarbons will produce corrosive acids 

when coming in contact with the flames. This will greatly 
reduce the life of the gas duct furnace and may void the 
warranty. Avoid such areas.

Important:

If the gas duct furnace is to be used in a 
building classified as having a hazardous 
atmosphere, the installation must comply 
with the standards set by the National 
Board of Fire Underwriters. Consult the 
authorities having jurisdiction before 
starting the job.

The duct furnace must be installed on the positive 
pressure side of the air circulation blower.

Aircraft Hangars

In aircraft hangars, duct furnaces must be at least 10 feet 
(3.05 m) above the upper surface of wings or engine 
enclosures of the highest aircraft to be stored in the hangar 
and 8 feet (2.4 m) above the floor in shops, offices, and 
other sections of the hangar where aircraft are not stored 
and housed. Refer to current ANSI/NFPA No. 409, Aircraft 
Hangars. In Canada, installation is suitable in aircraft 
hangars when acceptable to the enforcing authorities.

Public Garages

In repair garages, duct furnaces must be installed in a 
detached building or room separated from repair areas as 
specified in the latest edition of NFPA 88B, Repair Garages.

In parking structures, duct furnaces must be installed so 
that the burner flames are located a minimum of 18 inches 
(457 mm) above the floor or protected by a partition not 
less than 18 inches (457 mm) high. Refer to the latest 
edition of NFPA 88A, Parking Structures.

In Canada, installation must be in accordance with the 
latest edition of CSA B149 “Installation Codes for Gas 
Burning Appliances and Equipment.”

Important:

The duct furnace must be installed such that the gas 
ignition control system is not directly exposed to water 
spray, rain, or dripping water. 

Duct furnaces should not be installed to maintain low 
temperatures and/or freeze protection of buildings. A 
minimum of 50°F (10°C) thermostat setting must be 
maintained. 

If duct furnaces are operated to maintain lower than 50°F 
(10°C), hot flue gases are cooled inside the heat exchanger 
to the point where water vapor (a flue gas by-product) 
condenses onto the heat exchanger walls. The result is a 
mildly corrosive acid that prematurely corrodes the 
aluminized steel heat exchanger and can actually drip 
water down from the duct furnace onto the floor surface 
below. Additional duct furnaces should be installed if a 
minimum 50°F (10°C) thermostat setting cannot be 
maintained.

NOTICE: 

Equipment Damage!

Do not install unit heaters in corrosive of flammable 
atmospheres! Premature failure of, or severe damage to 
the unit will result!

NOTICE: 

Equipment Damage!

Avoid locations where extreme drafts can affect burner 
operation. Duct furnaces must not be installed in 
locations where air for combustion would contain 
chlorinated, halogenated or acidic vapors. If located in 
such an environment, premature failure of the unit will 
occur!

WARNING

Combustible Materials!

Failure to maintain proper clearance between the unit 
heat exchanger, vent surfaces and combustible 
materials could cause a fire which could result in death 
or serious injury or property damage. Refer to 

Table 3

 

for proper clearances.

Table 3.

Minimum safety clearances

(a)

(a) When clearances required for accessibility are greater than the mini-

mum safety clearances, the accessibility clearances take precedence.

Sides

6 inches (152 millimeters)

Top

6 inches (152 millimeters)

Bottom

6 inches (152 millimeters)

Flue

6 inches (152 millimeters)

Содержание GUNE

Страница 1: ...c knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in th...

Страница 2: ...and your local state electrical codes WARNING Personal Protective Equipment PPE Required Installing servicing this unit could result in exposure to electrical mechanical and chemical hazards Before in...

Страница 3: ...lane hangars when installed in accordance with current ANSI NFPA No 409 and in public garages when installed in accordance with current NFPA No 88A and NFPA No 88B If installed in Canada the installat...

Страница 4: ...e service panel and the heater To ensure a proper ground the grounding means must be tested by a qualified technician Do not insert fingers or foreign objects into the heater or its combustion air mov...

Страница 5: ...de 12 Gas Pipe Sizing 13 Pipe Sizing 13 Pipe Installation 14 Venting 16 Venting for Power Vented Duct Furnaces Category III 16 Vertically Vented Duct Furnaces Category III 17 Horizontally Vented Duct...

Страница 6: ...nic Modulating w Room Sensing J Electronic Modulating w Duct Thermostat L Electronic Modulation w External 4 20 mA Input M Electronic Modulation w External 0 10 Vdc Input T Single Stage Direct Spark I...

Страница 7: ...t Furnace is a factory assembled power vented and low static pressure type duct furnace with a low profile cabinet The duct furnace can also be easily field converted to separated combustion The desig...

Страница 8: ...33 5 33 5 33 5 831 831 831 851 851 851 851 F Flue Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 G Air Inlet Size Diameter 5 5 5 6 6 6 6 127 127 127 152 152 152 152 Gas Inlet Natural Gas inc...

Страница 9: ...ations between 0 and 2 000 feet 610m 2 For unit installations in U S A above 2 000 feet 610 m the unit input must be field derated 4 percent for each 1 000 feet 305 m above sea level refer to local co...

Страница 10: ...by a partition not less than 18 inches 457 mm high Refer to the latest edition of NFPA 88A Parking Structures In Canada installation must be in accordance with the latest edition of CSA B149 Installat...

Страница 11: ...ibration Air Flow The installation is to be adjusted to obtain an air throughput within the range specified on the appliance rating plate Combustion Inlet Air Ventilation Inlet Air From Another Room I...

Страница 12: ...reen and block off plate locations once the unit has been flipped However due to combustion noise it is recommended to keep the air inlet screen on top for overhead installations Important If unit acc...

Страница 13: ...on for use with propane bottled gas must be made by a qualified LP gas dealer or installer He She will ensure that proper joint compounds are used for making pipe connections that air is purged from l...

Страница 14: ...ze in Internal Diameter in Length of Pipe feet meters 10 20 30 40 50 60 70 80 90 100 125 150 175 200 3 0 6 1 9 1 12 2 15 2 18 3 21 3 24 4 27 4 30 5 38 1 45 7 53 3 61 0 1 2 0 622 175 120 97 82 73 66 61...

Страница 15: ...Damage Do not over tighten the inlet gas piping into the valve This may cause stresses that will crack the valve Figure 8 Pipe installation standard controls Table 5 Gas supply pressure a a Applicabl...

Страница 16: ...rom the venter outlet before installing an elbow in the vent system An elbow should never be attached directly to the venter Any run of single wall vent pipe exposed to cold air or passing through an...

Страница 17: ...ew elbows as possible 5 Avoid running vent pipe through unheated spaces 6 When this cannot be avoided insulate the pipe to prevent condensation of moisture on the walls of the pipe 7 Do not damper the...

Страница 18: ...sance or hazard or could be detrimental to the operation of regulators relief valves or other equipment Figure 10 p 19 and Table 7 p 17 for vent terminal height and snow consideration requirements 6 T...

Страница 19: ...Vertical Flue Height 1 4 per foot Min Slope 21 mm m Thimble Roof Use Insulated Stack Outdoors Approved Vent Terminal Figure 10 Horizontally vented Category III standard combustion D9378B Condensate Dr...

Страница 20: ...ameter stated in these instructions 5 Long runs of single wall combustion air piping passing through an unheated space may require insulating if condensation becomes noticeable 6 The combustion air sy...

Страница 21: ...stems longer than 5 feet 1 5 m the system must be supported from overheard building structures at 4 feet 1 22 m maximum intervals in the United States and at 3 feet 1 m maximum intervals in Canada 9 T...

Страница 22: ...Leg and Cleanout Cap Roof Flashing Breidert Type L or Fields Approved Terminal 10 ft 3 04m Min to Wall or Adjoining Building 2 ft 609m Min Plus Max Snow Depth for Area 3 ft 1m Min Plus Max Snow Depth...

Страница 23: ...Installation GUNE SVX001A EN 23 Figure 14 Vertical arrangement single wall vent system to single wall termination Figure 15 Horizontal arrangement single wall vent system to single wall termination...

Страница 24: ...Installation 24 GUNE SVX001A EN Figure 16 Vertical arrangement single wall vent system to double wall termination Figure 17 Horizontal arrangement single wall vent system to double wall termination...

Страница 25: ...Outside walls or areas where drafts may affect the operation of the control 2 Hot Areas Areas where the sun s rays radiation or warm air currents may affect the operation of the control 3 Dead Areas A...

Страница 26: ...al Connections 26 GUNE SVX001A EN Figure 21 Tubular duct furnaces equipped with natural gas or propane LP gas single stage Figure 22 Tubular duct furnaces equipped with natural gas or propane LP gas t...

Страница 27: ...mperature of the space being heated The thermostat must be mounted on a vertical vibration free surface free of air currents and in accordance with the furnished instructions also refer to Electrical...

Страница 28: ...ust be maintained for proper operation of the duct furnace If the duct furnace is equipped with a pressure regulator on the combination gas valve follow Step 1 through Step 4 above If the duct furnace...

Страница 29: ...2 2292 96 3 001 4 000 916 1 220 2 9 722 8 4 2092 92 4 001 5 000 1 221 1 525 2 7 673 7 7 1918 88 5 001 6 000 1 526 1 830 2 4 598 7 0 1744 84 6 001 7 000 1 831 2 135 2 2 548 6 4 1594 80 7 001 8 000 2 1...

Страница 30: ...owed when the equipment was installed Have all field installed controls been installed Do you understand all the controls on this equipment If not contact your wholesaler or rep DO NOT START this equi...

Страница 31: ...ir inlet for blockage debris Clear if any found 7 Reassemble the duct furnace by replacing all parts in reverse order 8 Complete the appropriate unit start up procedure as given in the Operation secti...

Страница 32: ...lar duct furnace component index 1 Vestibule panel tube assembly heat exchanger 2 Manifold 3 Manifold bracket sub assembly 4 Inshot burner 5 Burner orifice 6 Gas valve 7 Gas inlet pipe 8 Gas inlet gro...

Страница 33: ...nd the following information to your local representative if further assistance is needed contact the manufacturer s customer service department Unit number Serial number Part description and number a...

Страница 34: ...logged main burners Clean main burner ports Misaligned orifices Replace manifold assembly Insufficient combustion air Refer to Clearances p 10 and Venting p 16 to ensure unit is properly mounted and v...

Страница 35: ...inal strip R and W Shorted circuit Check thermostat circuit for shorts or any staples piercing wires Defective thermostat If thermostat is calling after set point has been satisfied replace Defective...

Страница 36: ...or 24 V on terminals R and W1 on terminal strip Loose wiring or connection Check all wiring in the power vent circuit to ensure good connection including neutral Motor overload protection is tripping...

Страница 37: ...tus Indicates Check Repair Slow Flash Control OK no call for heat Not Applicable Fast Flash Control OK call for heat present Not Applicable Steady Off Internal control fault or no power 1 Line voltage...

Страница 38: ...drocarbons precipitated in the air to any workmanship of the installer of the Product This limited warranty is conditional upon advising the installing contractor who in turn notify the distributor or...

Страница 39: ...lio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane com Trane has a policy of continuous product and product data improvement and r...

Отзывы: