10
FWD-SVX01D-E4
Installation
Duct connections
FWD units can be fitted directly with
rectangular discharge and intake
ducts.
Warning.
The pressure loss caused
by the duct network and
accessories must not exceed the
unit’s available static pressure (see
selection chart).
The air intake can be located at the
back of the unit
➀
or underneath it
➁
.
DIMENSIONS OF DUCT CONNECTIONS
(INTAKE AND DISCHARGE)
Sizes
08
12
20
30
45
Length
748
948
1148
1148
1148
Width
198
248
298
598
598
Filtering: vital to ensure the unit runs
smoothly.
No filters are supplied with the unit,
but they can be ordered as
accessories:
- Filter box with EU2 filters to fix to
the unit’s intake.
(behind or underneath).
➁
➀
Figure 6 : Connection of ducts