Possible cause
A)The electric cabinet is not connected.
B) The control circuit is not powered up.
A) The thermostat is not controlling the
unit.
A) The electric motors are not powered up.
B)The thermal protection of the motors
has been cut.
A) The unit is not operating.
B) The thermostat settings are incorrect.
C) Insufficient air flow
D) Insufficient chilled water flow
E) Chilled water temperature too high.
F) The thermostat is not operating
correctly.
G) Heat load is greater than expected.
A) Clogged filters.
B) The fans are rotating the wrong way
C) The air flow is obstructed.
Solution
Check the unit’s general disconnect switch
is closed.
Check the control circuit’s fuse.
Check the thermostat is plugged in (also
refer to the thermostat’s instruction
manual).
Check the fan motors are powered up and
the fan circuit-breakers are reset.
Check the motor winding resistance after
resetting. Check the power supply voltage
and the input current.
See“The unit is not operating”.
Check the set point.
See “No air flow”
Checked the chilled water flow. Check the
gate valves and the water circuit.
Check the unit’s chilled water production.
Refer to the thermostat’s instruction
manual.
Check the zone’s heat load (too much fresh
air).
Check the extent of infiltration of outside
air.
Clean or replace the recycling filters.
Check and correct
Symptom
The unit is not powered up.
The unit does not operate
The fan motors do not operate.
Room temperature too high
Room temperature too low
No airflow
Maintenance
18
Troubleshooting
Содержание FWD 08
Страница 1: ...Ductable water unit FWD 08 12 20 30 45 Installation Operation Maintenance FWD SVX01D E4 ...
Страница 11: ...11 FWD SVX01D E4 ...
Страница 12: ...12 FWD SVX01D E4 ...
Страница 13: ...13 FWD SVX01D E4 ...
Страница 14: ...FWD SVX01D E4 Space requirement plans 14 ...
Страница 15: ...FWD SVX01D E4 15 ...
Страница 19: ...19 FWD SVX01D E4 Notes ...