22
RT-SVX51H-EN
Control Power Transformer
The 24-volt control power transformers are to be used
only with the accessories called out in this manual.
Transformers rated greater than 50 Vac are equipped
with internal circuit breakers. If a circuit breaker trips,
turn “Off” all power to the unit before attempting to
reset it.
The transformer is located in the control panel. The
circuit breaker is located on the left side of the
transformer and can be reset by pressing in on the
black reset button.
Controls using 24 Vac
Before installing any connecting wiring, refer to
for the electrical access
locations provided on the unit and
for AC
conductor sizing guidelines.
N
NO
OT
TIIC
CE
E
U
Usse
e C
Co
op
pp
pe
err C
Co
on
nd
du
ucctto
orrss O
On
nlly
y!!
F
Fa
aiillu
urre
e tto
o u
usse
e cco
op
pp
pe
err cco
on
nd
du
ucctto
orrss cco
ou
ulld
d rre
essu
ulltt iin
n
e
eq
qu
uiip
pm
me
en
ntt d
da
am
ma
ag
ge
e a
ass tth
he
e e
eq
qu
uiip
pm
me
en
ntt w
wa
ass n
no
ott
d
de
essiig
gn
ne
ed
d o
orr q
qu
ua
alliiffiie
ed
d tto
o a
acccce
ep
ptt o
otth
he
err tty
yp
pe
ess o
off
cco
on
nd
du
ucctto
orrss..
1. Use copper conductors unless otherwise specified.
2. Ensure that the AC control wiring between the
controls and the unit’s termination point does not
exceed three (3) ohms/conductor for the length of
the run.
N
No
otte
e:: Resistance in excess of 3 ohms per conductor
could cause component failure due to
insufficient AC voltage supply.
3. Be sure to check all loads and conductors for
grounds, shorts, and mis-wiring.
4. Do not run the AC low voltage wiring in the same
conduit with the high voltage power wiring.
5. Route low voltage wiring as per
Table 2. Electromechanical thermostat 24V AC conductors with electromechanical unit
Distance from Unit to Control
Recommended Wire Size
0 - 30 feet
22 gauge
0 - 9.1 m
0.33 mm^2
31 - 50 feet
20 gauge
9.5 - 15.2 m
0.50 mm^2
51 - 75 feet
18 gauge
15.5 - 22.9 m
0.75 mm^2
76 - 125 feet
16 gauge
23.1 - 38.1 m
1.3 mm^2
126 - 200 feet
14 gauge
38.4 - 60.9 m
2.0 mm^2
Содержание Foundation GBC180