46
RT-SVX51H-EN
has been removed (for example, replaced faulty
sensor), the alarm can be cleared from the display.
N
No
otte
e:: If an alarm still exists after you clear it, it re-
displays within 5 seconds.
To Clear an Alarm
Once the alarm has been identified and the cause has
been removed (for example, replaced faulty sensor),
the alarm can be cleared from the display.
1. Navigate to the desired alarm.
2. Press
.
3.
“ERASE?” is displayed.
4. Press
.
5.
“ALARM ERASED” is displayed.
6. Press
(Menu Up) to complete the action and
return to the previous menu.
N
No
otte
e:: If an alarm still exists after you clear it, it re-
displays within 5 seconds.
Low Leak Economizer Fault Codes
Low Leak Economizer Alarms:
•
CO
2
Sensor Error
•
SYS Alarm
•
Actuator Undervoltage
•
Actuator Overvoltage
•
Actuator Stalled
The FDD system shall detect the following faults:
•
Air temperature sensor failure/fault
•
Not economizing when it should
•
Economizing when it should not
•
Damper not modulating
•
Excess outdoor air
The JADE controller is a certified FDD product (HJW10)
by California Title 24, Part 6. The FDD system is
required for meeting California Energy Commission's
Title 24 regulations.
shows the various
tests that can be performed (rows) and the five faults
that are defined by FDD (columns). The 'x' means that
the test has to be conducted to see if it is causing the
fault to occur.
Table 25.
FDD troubleshooting
FAULTS
TESTS
Air temp. sensor
failure / fault
Not economizing
when it should
Economizing when
it should not
Damper not
modulating
Excess
outdoor air
Damper Stuck Open
x
x
x
Damper Stuck at
Minimum
x
x
Bad or Unplugged
Actuator
x
x
x
Sensor Hard Failure
x
x
x
x
Actuator Mechanically
Disconnected
x
x
x
x
Resetting Cooling and Heating
Lockouts
Cooling Failures and Heating Lockouts are reset in an
identical manner.
Method 1 section explains resetting the system from
the space; Method 2 section explains resetting the
system at the unit.
N
No
otte
e:: Before resetting Cooling Failures and Heating
Lockouts check the Failure Status Diagnostics by
the methods previously explained. Diagnostics
will be lost when the power to the unit is
disconnected.
Method 1
To reset the system from the space, turn the “Mode”
selection switch at the thermostat to the “Off” position.
After approximately 30 seconds, turn the “Mode”
selection switch to the desired mode, i.e. Heat, Cool or
Auto.
Method 2
To reset the system at the unit, cycle the unit power by
turning the disconnect switch “Off” and then “On”.
Condensate Overflow Switch
When the condensate overflow switch is closed, a drain
pan overflow condition is indicated and it will shut unit
operations down.
Unit Economizer Control (ECA)
Verify Economizer Status by Economizer Actuator
(ECA) LED indicator:
•
OFF: No Power or Failure
•
ON: Normal, OK to Economize