RT-SVX51H-EN
33
Emergency Stop
This input de-energizes the 24 Vac output from the
phase monitor and can be activated by opening a field
supplied device connected to the LTB.
JADE Controls - Low Leak
Economizer Sequence of
Operation
Table 10.
Dry bulb operation no DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
None
No
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
None
Yes
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off
(a)
MIN POS to Full-Open
Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
Table 11.
Dry bulb operation with DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
Below CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN
Closed
On
On
High
24-v/On
24-v/On
VENTMIN
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off
(a)
VENTMIN to Full-Open
Closed to Full-Open
Above CO
2
set
No
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX
Closed
On
Off
High
24-v/On
0-v/Off
VENTMIN to VENTMAX
Closed
On
On
High
24-v/On
24-v/On
VENTMIN to VENTMAX
Closed
Yes
Off
Off
High
0-v/Off
0-v/Off
VENTMIN to VENTMAX
Closed
On
Off
High
0-v/Off
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off
VENTMIN to Full-Open
Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.
Table 12.
Enthalpy operation no DCV (CO
2
sensor) - 1 speed fan
DCV
OA Good to
economize?
Y1-I
Y2-I
FAN SPD
Y1-O
Y2-O
Occupied
Unoccupied
None
No
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
24-v/On
0-v/Off
MIN POS
Closed
On
On
High
24-v/On
24-v/On
MIN POS
Closed
None
Yes
Off
Off
High
0-v/Off
0-v/Off
MIN POS
Closed
On
Off
High
0-v/Off
0-v/Off
MIN POS to Full-Open
Closed to Full-Open
On
On
High
24-v/On
0-v/Off
(a)
MIN POS to Full-Open
Closed to Full-Open
(a)
With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2-O after the delay if the call for Y1-I and Y2-I have
not been satisfied.