22
18-CD31D1-5
Installer’s Guide
CONTROL AND SAFETY SWITCH
ADJUSTMENT
LIMIT SWITCH CHECK OUT
The limit switch is a safety device designed to close the gas
valve should the furnace become overheated. Since proper
operation of this switch is important to the safety of the
unit, it
must be checked out on initial start up by the
installer
.
To check for proper operation of the limit switches, set the
thermostat to a temperature higher than the indicated
temperature to bring on the gas valve. Restrict the airflow
by blocking the return air or by disconnecting the blower.
When the furnace reaches the maximum outlet tempera-
ture as shown on the rating plate, the burners must shut
off. If they do not shut off after a reasonable time and over-
heating is evident, a faulty limit switch is probable and the
limit switch must be replaced. After checking the operation
of the limit control, be sure to remove the paper or card-
board from the return air inlet, or reconnect the blower.
INDOOR BLOWER TIMING
Heating:
The Integrated Furnace Control (IFC) controls
the variable speed indoor blower. The blower “on” time is
fixed at 45 seconds after ignition. The FAN-OFF period
is field selectable by dip switches S7-3 and S7-4 on the
Integrated Furnace Control at 90, 120, 150, or 180 seconds.
The factory setting is 90 seconds (See unit wiring diagram).
Cooling:
The fan delay-off period is set by dip switches on
the Integrated Furnace Control. The options for cooling
delay off is field selectable by dip switches S4-1 and S4-2.
The following table and graph explain the delay-off set-
tings:
TABLE 12 COOLING OFF - DELAY OPTIONS
SWITCH SETTINGS
SELECTION
NOMINAL
AIRFLOW
S4-1 - OFF
S4-2 - OFF
NONE
SAME
S4-1 - ON
S4-2 - OFF
1.5 MINUTES
100% *
S4-1 - OFF
S4-2 - ON
3 MINUTES
50%
S4-1 - ON
S4-2 - ON
**
50 - 100%
▲
WARNING
!
Disconnect power to the unit before removing the blower
door. Failure to follow this warning could result in prop-
erty damage, personal injury or death.
This unit is equipped with a blower door switch which cuts
power to the blower and gas valve causing shutdown when
the door is removed. Operation with the door removed or
ajar can permit the escape of dangerous fumes. All panels
must be securely closed at all times for safe operation of the
furnace.
NOTE:
Direct drive motors have bearings which are permanently
lubricated and under normal use, lubrication is not recom-
mended.
ROOM AIR THERMOSTAT
HEAT ANTICIPATOR ADJUSTMENT
Set the thermostat heat anticipator according to the current
flow measured, or the settings found in the notes on the
furnace wiring diagram (found inside the furnace casing).
INSTRUCTIONS TO THE OWNERS
In the event that electrical, fuel, or mechanical fail-
ures occur, the owner should immediately turn the
gas supply off at the manual gas valve, located in the
burner compartment (See Figure 27).
Also turn off electrical power to the furnace and con-
tact the service agency designated by your dealer.
▲
WARNING
!
Should overheating occur, or the gas supply fail to shut
off, shut off the gas valve to the unit before shutting off
the electrical supply. Failure to follow this warning could
result in property damage, personal injury, or death.
OFF
50%
50%
80%
Dehumidify
Efficiency
Fast Cooling
1
minute
3
minutes
7.5
minutes
100% if necessary
OFF
See Wiring Diagram on the unit or in the Service Facts
for complete wiring setup for Enhanced Mode.
* - This setting is equivalent to BAY24X045 relay ben-
efit.
** - This selection provides ENHANCED MODE, which
is a ramping up and ramping down of the blower
speed to provide improved comfort, quietness,
and potential energy savings. See Wiring Diagram
notes on the unit or in the Service Facts for com-
plete wiring setup for ENHANCED MODE. The
graph which follows, shows the ramping process.
▲
WARNING
!
EXPLOSION HAZARD!
PROPANE GAS IS HEAVIER THAN AIR AND MAY COL-
LECT IN ANY LOW AREAS OR CONFINED SPACES. IN
ADDITION, ODORANT FADE MAY MAKE THE GAS UNDE-
TECTABLE EXCEPT WITH A WARNING DEVICE. IF THE
GAS FURNACE IS INSTALLED IN A BASEMENT, AN EXCA-
VATED AREA OR A CONFINED SPACE, IT IS STRONGLY
RECOMMENDED TO CONTACT A GAS SUPPLIER TO
INSTALL A GAS DETECTING WARNING DEVICE IN CASE
OF A GAS LEAK
.
NOTE:
The manufacturer of your furnace does NOT test any
detectors and makes no representations regarding any brand
or type of detector.