Trane DD060R9V3F Series Скачать руководство пользователя страница 9

18-CD20D1-18

9

Installer’s Guide

3. The side panels on upflow furnaces include locating

notches which may be used as guides for cutting an
opening for return air.  Refer to Figure 12 and the
outline drawing on page 4 for duct connection dimen-
sions for various furnaces.

4. If a 3/4" flange is to be used for attaching the air inlet

duct, add to cut where indicated by solid lines in
Figure 12. Cut corners diagonally and bend outward to
form flange.

5. If flanges are not required, and a filter frame is installed,

cut along knockout guidelines.

6.

Upflow Furnaces: 

 a filter rack is factory supplied for

bottom or side return.  Use the filter rack on either side
or on the bottom if the filter is to be used within the
furnace cabinet.

When the upflow furnace is installed in the horizontal
right or left application and a return duct is attached to
the top side as shown in Figure 11, remove the filter
from the furnace and install in a remote location.

WARNING

!

TO PREVENT INJURY OR DEATH DUE TO CONTACT 
WITH MOVING PARTS, TURN THE POWER TO THE 
FURNACE OFF BEFORE SERVICING FILTERS.

Do not install the filter in the return duct directly above
the furnace in horizontal applications.

When the upflow furnace is installed in the horizontal
right or left application and a close coupled (less than
36") return duct is attached to the bottom side of the
furnace as shown in Figure 11, securely attach a 1/2"
mesh metal hardware cloth protective screen to the
inside bottom of the filter grill 

to prevent personal

injury from contacting moving parts when reach-
ing into the return opening to replace the filter.

Close coupled (less than 36") return (filter directly
beneath bottom side return) is not recommended due to
noise considerations.

Downflow Furnaces: 

 Brackets are factory supplied to

mount filters in the return air duct work.

7. Connect the duct work to the furnace.  See Outline

Drawing for supply and return duct size and location.
Flexible duct connectors are recommended to connect
both supply and return air ducts to the furnace.

If only the front of the furnace is accessible, it is recom-
mended that both supply and return air plenums are
removable.

8. When replacing a furnace, old duct work should be

cleaned out.  Thin cloths should be placed over the
registers and the furnace fan should be run for 10 min-
utes.  Don’t forget to remove the cloths before you start
the furnace.

RETURN AIR FILTERS

TYPICAL UPFLOW RETURN AIR FILTER INSTALLATIONS

Filters are factory supplied for these furnaces.  These fur-
naces require high velocity type air filters.  The filters may be
located within the furnace blower compartment for UPFLOW
furnaces in either a BOTTOM or SIDE (left side or right side)
return air inlet.  Some filters may need to be trimmed for
side or bottom filter use.

NOTE:
On upflow 5 or 6 ton airflow models, if the airflow require-
ment exceeds 1800 CFM, these models will require return
air openings and filters on both sides; OR 1 side and the
bottom; OR just the bottom.

WARNING

!

Do not install the filter in the return duct directly above the 
furnace in horizontal applications. Install the filter remotely. 
Installing the filter directly above the furnace in horizontal 
applications may cause property damage, serious injury or 
death.

FILTER

REMOVE FILTER FROM UPFLOW
FURNACE WHEN RETURN DUCT IS
ATTACHED TO FURNACE TOP SIDE
(HORIZONTAL LEFT OR RIGHT
APPLICATIONS) AS SHOWN.

Close coupled (less than 36")
return (filter directly beneath bottom
side return) not recommended due to
noise considerations. If used, securely
attach 1/2" mesh metal hardware cloth
protective screen to the inside bottom of
filter grill.

The upflow furnace blower door has a hinge at the bottom
which allows the door to tilt forward for filter replacement
without the door being removed.  The furnace filter in the
bottom or side configuration can be removed by simply
turning the two latches on the blower door and tilting the
door forward.

The filter rails are spring loaded for automatic adjustment to
allow standard size, locally obtainable replacement filters.
The filter rack itself slides to adjust to the required width
needed for bottom or side return.

q

*

SEE OUTLINE DRAWING

w

LOCATING
NOTCHES
PROVIDED
FOR SIDE
RETURN
CUTOUT

*

*

*

*

CUT OUT

FOR

SIDE

FILTER

FRONT

of Furnace

Содержание DD060R9V3F Series

Страница 1: ...est version USA CANADA ALTERNATE Category I Venting Guide Pub No 18 CH23D1 latest version Horizontal Conversion for these furnaces may be left or right side rotation ALL phases of this installation mu...

Страница 2: ...temperature rise and venting according to the manufacturer s instructions 10 This product must be gas piped by a Licensed Plumber or Gas Fitter in the Commonwealth of Massachusetts Safety signal word...

Страница 3: ...n these instructions Category I defined on page 13 CAUTION To prevent shortening its service life the furnace should not be used as a Construction Heater during the finishing phases of construction un...

Страница 4: ...4 18 CD20D1 18 Installer s Guide From Dwg 21C341699 Rev 4 UD R9V K OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 5: ...wg 21C341700 Sh 1 Rev 0 DD R9V F OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES MODEL A B C D DD060R9V3F DD080R9V3F 17 1 2 9 5 8 16 1 4 16 DD100R9V5F 21 13 1 16 19 3 4 19 1 2 DD120R9V5F 24 1 2 15 5 16 2...

Страница 6: ...looring For vertical downflow application subbase BAYBASE205 must be used between the furnace and combustible flooring When the downflow furnace is installed vertically with a cased coil a subbase is...

Страница 7: ...lated caulked vapor barrier etc may need additional air provided as described for con fined space Confined spaces are installations with less than 50 cu ft of space per 1000 BTU hr input from all equi...

Страница 8: ...vibration to the annoyance level When the furnace is located in a utility room adjacent to the living area the system should be carefully designed with returns which minimize noise transmission throu...

Страница 9: ...ace If only the front of the furnace is accessible it is recom mended that both supply and return air plenums are removable 8 When replacing a furnace old duct work should be cleaned out Thin cloths s...

Страница 10: ...ALLATION With the filter removed the filter rack is compressed and then inserted into the bottom of the furnace The retaining screw pin on each side inserts into engagement holes at the bottom of the...

Страница 11: ...Leave the bottom panel in place e After the side cutout is made following the directions in the Return Air Duct Connections section on pages 8 and 9 compress the filter rack and reinstall in the side...

Страница 12: ...mine the location to be used The furnace cabinet has dimples for location of the alternate furnace clips Side return only Pre drill clearance holes with a 3 16 drill Bottom return holes are pre drille...

Страница 13: ...X20X1 13 1 8 24 1 2 2 16X20X1 11 5 8 Location dimension is from end of duct to the screw holes for the bracket VENT PIPING These furnaces have been classified as Fan Assisted Combus tion System Catego...

Страница 14: ...other good venting practices as stated in the venting section of the National Fuel Gas Code ANSI Z223 1 latest edition 10 Vent connectors serving appliance vented by natural draft or non positive pre...

Страница 15: ...ircuit board must be cut if optional humidistat is used The jumper must also be cut when applying an airflow command signal to the BK input such as with the variable speed single zone and multi zone s...

Страница 16: ...ABLE SPEED 2 STAGE FURNACE 1 STAGE HEATING 1 STAGE COOLING USING A 1 STAGE HEATING 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER W14 OUTDOOR UNIT NO TRANSFORMER SEE NOTE 6 SEE NOTE 7...

Страница 17: ...BK on the circuit board must be cut if an optional Humidistat is installed h HUMIDISTAT HOOKUP If an optional humidistat is to be connected between R and BK the factory installed jumper between R and...

Страница 18: ...e gas supply piping system at test pressures equal to or less than 1 2 psig CAUTION Use a backup wrench on the gas valve when installing gas piping to prevent damage to the gas valve and manifold asse...

Страница 19: ...times to verify regulator setting e For the White Rodgers gas valve model 36G 1 Adjust low fire by removing the low adjustment regulator cover screw See Figure 29 2 To increase outlet pressure turn th...

Страница 20: ...Important Reinstall the propane orifices to the same depth as the orifices supplied with the equipment See Table 14 for help in selecting orifices if orifice change is required Furnace input rate and...

Страница 21: ...W1 thermostat contacts close signaling the control module to run its self check routine After the control module has verified that the 1st stage pressure switch contacts are open and the limit switch...

Страница 22: ...d gas valve causing shutdown when the door is removed Operation with the door removed or ajar can permit the escape of dangerous fumes All panels must be securely closed at all times for safe operatio...

Страница 23: ...ntrol module has shut the system down and gone into lockout the system must be manu ally reset before the unit will restart To reset turn the system power off then on then off and then on again within...

Страница 24: ...place IFC Continuous OFF Check Power 2 Flashes System Lockout Retries or Recycles exceeded 3 Flashes Draft Pressure Error Possible problems a Venting problem b Pressure switch problem c Inducer proble...

Отзывы: