
52
CLCH-SVX03C-EN
Coil Piping and Connections
Steam Coil Piping
M-Series air handlers fitted with steam coils have labeled holes for piping penetrations.
Figure 48
and
Figure 49
illustrate typical steam coil piping configurations. See
Table 14
for the codes of
system components in these figures.
The coil condensate return line must be piped full size of the condensate trap connection, except
for a short nipple screwed directly into the coil header’s condensate return tapping. Do not bush
or reduce the coil return trapping size.
Figure 48. Typical piping for Type N steam coils and
horizontal tubes for horizontal airflow
Figure 49. Typical piping for Type NS steam coils and
horizontal tubes for horizontal airflow
Table 14. Code of system components for piping figures
Code
System component
FT
Float and thermostatic steam trap
GV
Gate valve
OV
Automatic two-position (ON-OFF) control valve
VB
Vacuum breaker
ST
Strainer
AV
Automatic or manual air vent
MV
Modulating control valve