CLCH-SVX03C-EN
47
Component Installation Requirements
When attaching a bypass duct to a downstream fan module, it may be necessary to cut a hole in
the fan module panel. When cutting a penetration, it is important the cutting have the same cross
sectional area as the bypass duct. In other words the length of the opening should be the same as
the height of the duct (see
Figure 43
,
Figure 44
, and
Figure 45
.)
When bypassing into an access module, remove a panel. it is not necessary to cut an opening.
Figure 43. External face-and-bypass with vertical duct configuration
Figure 44. External face-and-bypass with duct configuration designed to bypass air around one
coil
Duct
Fan
External
Face and Bypass
Coil
Fan
Coil
Coil
External
Face and Bypass
Duct