34
CLCH-SVX03C-EN
Component Installation Requirements
Filter Installation
WARNING
Pressurized Cabinet!
Disconnect all electric power, including remote disconnects before opening door. Follow proper
lockout/tagout procedures to ensure the equipment cannot be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
To install filters:
1.
Disconnect the power to the unit.
2. Open the filter module access door.
3. Remove the block-off from the filter track.
4. Slide the filters into the tracks.
Note:
Bag filters must be installed with the pleats in the vertical plane.
5. Replace the block-off (see
Figure 27
).
Note:
The block-off is intended to make a seal when the access door is closed. It may require a few
adjustments to ensure a proper seal.
6. Close the access door and confirm that there is a good seal of the filter track block-off against
the access door.
Figure 27. Filter block-off placement