background image

RLC-SVX023A

25

11

UNT-PRC002-GB

Sound power levels

Discharge

Measurement conditions:
Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 m
long) fixed to its discharge opening.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

55

50

42

37

37

31

30

46

FWD 08

2

57

54

47

40

30

38

40

50

3

58

57

50

42

32

40

43

53

1

57

51

45

42

34

33

28

48

FWD 10

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

57

51

45

42

34

33

28

48

FWD 12

2

58

54

48

45

38

39

35

51

3

60

58

50

48

40

42

39

54

1

56

62

50

48

39

38

36

56

FWD 14

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

1

57

63

51

49

40

39

37

57

FWD 20

2

61

66

55

53

47

46

45

60

3

63

69

58

56

50

50

49

63

Intake

Measurement conditions:
Measurements taken at the horizontal air intake.

Fan

Power level in dB(A), per Hz frequency band

Overall power

Unit

speed

125

250

500

1000

2000

4000

8000

dB(A)

1

56

55

55

53

46

45

42

57

FWD 08

2

63

62

60

60

53

53

53

64

3

66

65

63

62

56

55

57

67

1

62

58

55

58

51

48

44

61

FWD 10

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

62

58

55

58

51

48

44

61

FWD 12

2

66

63

60

62

56

55

52

66

3

70

67

63

65

59

59

57

69

1

66

65

65

65

57

50

46

68

FWD 14

2

73

72

69

71

64

59

57

74

3

78

76

73

75

69

64

63

78

1

68

72

64

64

56

52

50

69

FWD 20

2

76

76

68

71

65

61

61

75

3

78

79

71

74

69

66

66

78

Installation - Electrical

The Tracer UC800 Service Tool (TU) is used to install and 
assign any of the above listed events or status to each of 
the 4 relays. The default assignments for the 4 available 
relays are listed below.

LLID Name

LLID Software

Relay Designation

Output Name

Default

Operating Status 

Programmable Relays

Relay 0

Status Relay 1, J2-1,2,3

Evaporator Freeze Avoidance 

Request

Relay 1

Status Relay 2, J2-4,5,6

Condenser Freeze Avoidance 

Request

Relay 2

Status Relay 3, J2-7,8,9

Compressor Running

Relay 3

Status Relay 4, J2-10,11,12

Latching Alarm

If the evaporator/condenser pump request relays are 
not used to manage the evaporator/condenser water 
pumps then the evaporator/condenser freeze avoidance 
request relays must be connected to the water pump 
management system to switch the water pumps ON 
when the Tracer UC800 identifies a risk of freeze up. 

Latching input

The Tracer UC800 provides auxiliary control for a 
customer specified/installed latching trip out. When 
this customer-furnished remote contact is provided, 
the chiller will run normally when the contact is closed. 
When the contact opens, the unit will trip off on a 
manually resettable diagnostic. This condition requires 
manual reset at the chiller switch on the front of the 
control panel.

External Auto/Stop

If the unit requires the external Auto/Stop function, the 
installer must provide leads from the remote contacts to 
the proper terminals of the LLID on the control panel. The 
chiller will run normally when the contacts are closed. 
When the contact opens, the compressor(s), if operating, 
will go to the RUN : UNLOAD operating mode and cycle 
off. Unit operation will be inhibited. Re-closure of the 
contacts will permit the unit to automatically return to 
normal operation.

NOTE:

 A “panic “ stop (similar to “emergency “ stop) can 

be manually commanded by pressing the STOP button 
twice in a row, the chiller will immediately shut down, 
but without creating a latching diagnostic.

Soft Loading

Soft loading will prevent the chiller from going to full 
capacity during the pull-down period. The Tracer UC800 
control system has two soft loading algorithms running 
all of the time. They are capacity control soft loading and 
current limit soft loading. These algorithms introduce the 
use of a Filtered Chilled Water Setpoint and a Filtered 
Current Limit Setpoint. After the compressor has been 
started, the starting point of the filtered chilled water 
setpoint is initialized to the value of the Evap Leaving 
Water Temperature. The filtered current limit setpoint 
is initialized to the value of the Current Limit Softload 
Starting Percent. These filtered setpoints allow for a 
stable pull-down that is user adjustable in duration. They 
also eliminate sudden transients due to setpoint changes 
during normal chiller operation.

3 settings are used to describe the behavior of soft 
loading. The setup for soft loading can be done using TU.

•  Capacity Control Softload Time: This setting controls the 

time constant of the Filtered Chilled Water Setpoint. It is 
settable between 0 and 120 min.

•  Current Limit Control Softload Time: This Setting 

controls the time constant of the Filtered Current Limit 
Setpoint. It is settable between 0 and 120 minutes.

•  Current Limit Softload Starting %: This setting controls 

the starting point of the Filtered Current Limit Setpoint. 
It is adjustable from 20 to 100% RLA.

Содержание City RTSF050

Страница 1: ...RLC SVX023A Water cooled Liquid Chillers with Helical Rotary Compressors RTSF 180 385kW R1234ze Installation Operation Maintenance...

Страница 2: ...54 56 60 63 57 62 67 57 62 68 Unit dimensions Width x Depth mm 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644...

Страница 3: ...oderate injury It may also be used to alert against unsafe practices or for equipment or property damage only accidents Safety Recommendations To avoid death injury equipment or property damage the fo...

Страница 4: ...ax 11 bars Introduction Unit Description The RTSF units are helical rotary type water cooled liquid chillers designed for installation indoors The RTSF units are packaged with an evaporator and conden...

Страница 5: ...denserTemp H Cooling Mode Above 50 C Leaving CondenserTemp L Heat pump Below 50 C Leaving CondenserTemp M Heat pump Above 50 C Leaving CondenserTemp Digit 17 Refrigerant Z R1234ze unit with Factory ch...

Страница 6: ...size Unit alone aM gI A 8 16 8 16 8 16 8 25 8 25 Unit with electric heater gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet tempera...

Страница 7: ...t power factor 0 95 0 95 0 95 0 95 0 95 0 95 Short Circuit Unit Capacity kA 35 35 35 35 35 35 Max Power cable cross mm 1x 240 1x 240 1x 240 1x 240 1x 240 1x 240 Disconnect switch size 3 A 400 400 400...

Страница 8: ...1290 x 1090 Height mm 250 300 350 450 650 Shipped unit dimensions Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour...

Страница 9: ...install valves in the water piping upstream and downstream of the evaporator and condenser to isolate the heat exchangers for maintenance and to balance trim the system Supply and install flow switch...

Страница 10: ...ganization and the appropriateTrane sales office NOTE Pressure will be approximately 1 0 bar if shipped with the optional nitrogen charge Noise Considerations Refer to Engineering Bulletin for sound c...

Страница 11: ...HUETTERUNGEN UNBEDINGT VERMEIDEN SPECIAL LIFTING AND MOVING INSTRUCTIONS IT IS RECOMMENDED TO USE THE SPECIAL BUILT IN RIGGING POINTS SHOWN IN THE DIAGRAM AND TO FOLLOW THE FOLLOWING INSTRUCTIONS 1 CA...

Страница 12: ...e blower unit Heat exchanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute se...

Страница 13: ...general locations are given below Entering Chilled Water Piping Air vents to bleed air from system Water pressure gauges with shutoff valves Pipe unions Vibration eliminators rubber boots Shutoff iso...

Страница 14: ...rature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Installation Mechanical Water Pressure Relief Valves Install a pressure relief valve in both evaporator and condenser water sys...

Страница 15: ...50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 125 250 500 1000 2000 4000 8000 dB A 1 56...

Страница 16: ...with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is...

Страница 17: ...Recommended LRTC C Minimum Recommended LWTC C 0 0 0 0 0 2 8 0 0 0 0 2 8 2 0 6 1 4 2 2 0 6 1 4 2 2 4 1 3 2 1 1 5 1 2 2 0 1 6 5 1 7 2 5 1 1 1 5 2 3 1 3 6 2 0 2 9 0 7 1 8 2 6 1 0 8 2 8 3 6 0 0 2 5 3 3 0...

Страница 18: ...hanger operating limits FWD water temperature max 100 C absolute service pressure min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 b...

Страница 19: ...59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52...

Страница 20: ...r gI A 16 2kW 25 4kW 40 230V 3 16 400V 3 20 3 25 3 25 1 Conditions Water entering leaving temperature 7 12 C Air inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving te...

Страница 21: ...tor start run and AFD Adaptive Frequency Drive capacitors before servicing Follow proper lockout tagout procedures to ensure the power cannot be inadvertently energized For variable frequency drives o...

Страница 22: ...project engineer Water Pump Power Supply Provide power supply wiring with fused disconnect for both the chilled water and condenser water pumps Electrical Panel Power Supply Power supply wiring instr...

Страница 23: ...2 LRA At 240 VAC 5 0 amp resistive 2 0 amp pilot duty 250 W 3 6 FLA 21 3 LRA Installation Electrical Whenever a dry contact input binary input is referenced the electrical rating is 24VDC 12 mA Whene...

Страница 24: ...s Installation Electrical Condenser Water Pump Control Tracer UC800 provides a contact closure output to start and stop the condenser water pump It will allow to run the condenser pump after compresso...

Страница 25: ...ut TheTracer UC800 provides auxiliary control for a customer specified installed latching trip out When this customer furnished remote contact is provided the chiller will run normally when the contac...

Страница 26: ...LCI C between the chiller and a BAS An LCI C LLID shall be used to provide gateway functionality between the LonTalk protocol and the chiller Bacnet Communication Interface Optional Tracer UC800 provi...

Страница 27: ...top condition Diagnostic information is provided to allow the operator to identify system malfunctions Note To ensure proper diagnosis and repair contact a qualified service organization if a problem...

Страница 28: ...pressure min 1 bar max 11 bars Operating Principles Mechanical Cycle Description The refrigeration cycle for the chiller can be described using the pressure enthalpy diagram shown in Figure 5 Key Stat...

Страница 29: ...55 52 66 3 70 67 63 65 59 59 57 69 1 62 58 55 58 51 48 44 61 FWD 12 2 66 63 60 62 56 55 52 66 3 70 67 63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 6...

Страница 30: ...min 1 bar max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Operating Principles Mechanical Compressors The compressor used by...

Страница 31: ...61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horizontal air intake Fan Power level in dB A per Hz frequency band Overall power Unit speed 1...

Страница 32: ...op of the oil separator and is discharged into the condenser Oil that collects in the bottom of the oil separator at condensing pressure during compressor operation therefore oil is constantly moving...

Страница 33: ...4 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 1 57 63 51 49 40 39 37 57 FWD 20 2 61 66 55 53 47 46 45 60 3 63 69 58 56 50 50 49 63 Intake Measurement conditions Measurements taken at the horiz...

Страница 34: ...inlet temperature 27 19 C DB WB Nominal air flow 2 Conditions Water entering leaving temperature 50 45 C Air inlet temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water e...

Страница 35: ...on is complete before starting the unit the following prestart procedures must be reviewed and verified 1 Inspect all wiring connections in the compressor power circuits disconnects terminal block con...

Страница 36: ...ering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the b...

Страница 37: ...t up procedures as follows 1 Check the evaporator refrigerant pressure and the condenser refrigerant pressure under Refrigerant Report on theTD7 2 Check the EXV sight glasses after enough time has ela...

Страница 38: ...minal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water temperature m...

Страница 39: ...r can not be inadvertently energized Failure to disconnect power before servicing could result in death or serious injury Shut down the chiller once each year to check the following Perform all weekly...

Страница 40: ...e 20 C DB Nominal air flow 5 A rectangular glass wool duct 1m50 long is placed on the blower The measurement is taken in the room containing the blower unit Heat exchanger operating limits FWD water t...

Страница 41: ...63 65 59 59 57 69 1 66 65 65 65 57 50 46 68 FWD 14 2 73 72 69 71 64 59 57 74 3 78 76 73 75 69 64 63 78 1 68 72 64 64 56 52 50 69 FWD 20 2 76 76 68 71 65 61 61 75 3 78 79 71 74 69 66 66 78 Maintenance...

Страница 42: ...max 11 bars Accessories Hot water coil water temperature min 2 C max 100 C absolute service pressure min 1 bar max 11 bars Maintenance Procedures Table 6 POE Oil Properties Description Acceptable Leve...

Страница 43: ...c Loss of oil at the compressor stopped will be generated if the oil lines are not full on start up To properly charge the system with oil follow the steps below 1 Locate the 1 4 schrader valve on the...

Страница 44: ...s Width x Depth mm 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333 1133 Height mm 260 310 360 460 660 Weight kg 32 46 61 76 118 Colour galvanised steel Recommended fuse size Unit alone aM gI A 8 16 8...

Страница 45: ...refrigerant Once the problem is repaired follow the procedures below for evacuating and charging the unit Refrigerant recovery 1 Insure that the water flow is maintained on condenser and evaporator d...

Страница 46: ...let temperature 20 C DB Nominal air flow 3 At high speed with nominal air flow 4 Water entering leaving temperature 90 70 C air inlet temperature 20 C DB Nominal air flow 5 A rectangular glass wool du...

Страница 47: ...newal To ensure a long lifetime forTrane compressors system oil and vibration are regularly analyzed These tests build a detailed picture of the condition of internal system components Over time they...

Страница 48: ...rtfolio of advanced controls and HVAC systems comprehensive building services and parts For more information visit www Trane eu Trane has a policy of continuous product and product data improvement an...

Отзывы: