UNT-PRC002-GB
Technical Data
FWD
08
12
20
30
45
Power supply
(V/Ph/Hz)
230/1/50
Capacities
Cooling capacity on water (1)
(kW)
5,2
8,3
15
18,8
30,1
Heating capacity on water (2)
(kW)
6,3
11,9
18,9
20,9
38,2
Fan motor
(type)
2 x direct drive centrifugal
Fan power input (3)
(kW)
0,23
0,46
0,65
1,04
1,51
Current amps (3)
(A)
1,1
2,2
3,1
4,7
5,5
Start-up amps
(A)
3,2
5,5
9,3
14,1
16,5
Air flow
minimum
(m
3
/h)
490
980
1400
1800
2700
nominal
(m
3
/h)
820
1650
2300
3000
4500
maximum
(m
3
/h)
980
1970
2600
3600
5400
Main coil
Water entering/leaving connections
(type)
ISO R7 rotating female
(Dia)
3/4"
3/4"
1 1/2"
1 1/2"
1 1/2"
Electric heater (accessory for blower only)
Electric power supply
(V/Ph/Hz)
230/1/50
230/1/50 or 400/3/50
400/3/50
400/3/50
400/3/50
Heating capacity
(kW)
2/4
8
10
12
12
Hot water coil (accessory for blower only)
Heating capacity (4)
(kW)
6,3
12
17,4
22,4
34,5
G2 filter (filter box accessory)
Quantity
2
2
2
2
2
Dimensions ( LxWxth)
(mm)
386x221x8
486x271x8
586x321x8
586*421*8
586*621*8
G4 filter (filter box accessory)
Quantity
-
2
2
2
2
Dimensions ( LxWxth)
(mm)
-
486x264x48
586x314x48
586*414*48
586*614*48
Condensate pump (accessory)
(type)
Centrifugal
Water flow - lift height
(l/h - mm)
24 - 500
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
(dB(A))
36/40/43
38/41/44
46/50/53
47/52/57
47/52/58
Sound power level (5)
(dB(A))
46/50/53
48/51/54
56/60/63
57/62/67
57/62/68
Unit dimensions
Width x Depth
(mm)
890 x 600
1090 x 710
1290 x 820
1290 x 970
1290 x 1090
Height
(mm)
250
300
350
450
650
Shipped unit dimensions
Width x Depth
(mm)
933 x 644
1133 x 754
1333 x 864
1333 x 1008
1333*1133
Height
(mm)
260
310
360
460
660
Weight
(kg)
32
46
61
76
118
Colour
galvanised steel
Recommended fuse size
Unit alone (aM/gI)
(A)
8/16
8/16
8/16
8/25
8/25
Unit with electric heater (gI)
(A)
16 (2kW),25 (4kW)
40 (230V),3*16 (400V)
3*20
3*25
3*25
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
Installation - Electrical
LonTalk Communication Interface - Optional
Tracer UC800 provides an optional LonTalk
Communication Interface (LCI-C) between the chiller and
a BAS. An LCI-C LLID shall be used to provide “gateway”
functionality between the LonTalk protocol and the
chiller.
Bacnet Communication Interface - Optional
Tracer UC800 provides an optional Bacnet
communication interface between the chiller and a BAS.
Bacnet communication capability is fully integrated on
UC800. For further information see Integration Guide.
Modbus Communication Interface - Optional
Tracer UC800 provides an optional Modbus
communication Interface between the chiller and a BAS.
Modbus communication capability is fully integrated on
UC800. For further information see the Integration guide.
Ice Making Contact - Optional
Tracer UC800 accepts a contact closure input to
initiate Ice Building. When in the ice building mode,
the compressor will be fully loaded (not given a low
setpoint) and will continue to operate until the ice
contacts open or the return water temperature reaches
the Ice Termination Setpoint. If terminated on return
setpoint, Tracer UC800 will not allow the chiller to restart
until the ice making contact is opened.
Ice Machine Control - Optional
Tracer UC800 provides an output contact closure that
can be used as a signal to the system that ice building
is in operation. This relay will be closed when ice
building is in progress and open when ice building has
been terminated by either Tracer UC800 or the remote
interlock. It is used to signal the system changes required
to convert to and from ice making.
External Chilled Water Setpoint - Optional
Tracer UC800 will accept either a 2-10 VDC or a 4-20 mA
input signal, to adjust the chilled water setpoint from a
remote location.
Auxiliary Chilled/Hot Setpoint Contact - Optional
Tracer UC800 accepts a contact closure input to switch
from BAS/External/Front Panel setpoint to a customer
defined auxiliary setpoint. By default, chilled water
auxiliary setpoint is set to 9°C and hot water auxiliary
setpoint is set to 33°C.
External Current Limit Setpoint - Optional
Tracer UC800 will accept either a 2-10VDC or a 4-20mA
input signal to adjust the current limit setpoint from a
remote location.
Percent Condenser Pressure Output - Optional
Tracer UC800 provides a 2-10 VDC analog output to
indicate condenser pressure in percent of software High
Pressure Cutout (soft HPC).
Percent HPC =(Lowest Condenser Pressure of all running
circuits (abs) / Soft HPC (abs))*100.
Refrigerant Differential Pressure Indication - Optional
Tracer UC800 provides a 2-10 VDC analog output
to indicate refrigerant differential pressure with the
endpoints customer defined.
Refrigerant Differential Pressure = Lowest of (condenser
refrigerant pressure cktx - evaporator refrigerant
pressure cktx).
Compressor Percent RLA Output - Optional
Tracer UC800 provides a 0-10 Vdc analog output to
indicate %RLA of compressor starter average phase
current. 2 to 10 Vdc corresponds to 0 to 120% RLA.