Disassembly
CVHM-SVN001C-EN
13
2. Disconnect and mark all piping and wiring attached to
the purge unit. Sand all paint off at points and use a
tubing cutter where cuts are to be made. See Figure 3,
p. 13 and Figure 4, p. 13.
3. Remove the fasteners connecting the purge unit base
to its mounting bracket.
4. Two people will be needed to lift purge unit clear of the
chiller. Refer to Table 1, p. 9, for purge unit weight.
Store the purge unit in a clean dry area.
Reassemble the purge unit in reverse order when the
process is complete.
Control Panel Removal
Use the following steps to remove the control panel if
additional vertical clearance is required.
Note:
The control panel can be rotated back and
downward on two mounting bolts with wiring
remaining intact.
1. Mark and disconnect incoming wiring to the control
panel.
2. Remove the four bolts from the bottom of the panel
which secure the panel to the lower mounting brackets.
3. Loosen the two bolts on the back of the panel which
secure the panel to the top mounting brackets. See
Figure 5.
Figure 3.
Purge unit
Figure 4.
Purge unit detail
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer’s
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06A-EN
Figure 5.
Control panel mounting brackets