Introduction

CVHM-SVN001C-EN

This 

Installation, Operation, and Maintenance

 manual 

applies to CenTraVac™ chillers with R-514A and OIL00334/
OIL00335.

Important:

Verify proper refrigerant and oil for your 
chiller before proceeding!

Factory Warranty Information

Compliance with the following is required to preserve the 
factory warranty:

All Unit Installations

Startup MUST be performed by Trane, or an authorized 
agent of Trane, to VALIDATE this WARRANTY. Contractor 
must provide a two-week startup notification to Trane (or 
an agent of Trane specifically authorized to perform 
startup).

Additional Requirements for Units Requiring 
Disassembly and Reassembly

When a new chiller is shipped and received from our Trane 
manufacturing location and, for any reason, it requires 
disassembly or partial disassembly, and reassembly—
which could include but is not limited to the evaporator, 
condenser, control panel, compressor/motor, economizer, 
purge, factory-mounted starter or any other components 
originally attached to the fully assembled unit—
compliance with the following is required to preserve the 
factory warranty:

Trane, or an agent of Trane specifically authorized to 
perform start-up and warranty of Trane

®

 products, will 

perform or have direct on-site technical supervision of 
the disassembly and reassembly work.

The installing contractor must notify Trane—or an 
agent of Trane specifically authorized to perform 
startup and warranty of Trane

®

 products—two weeks 

in advance of the scheduled disassembly work to 
coordinate the disassembly and reassembly work.

Start-up must be performed by Trane or an agent of 
Trane specifically authorized to perform startup and 
warranty of Trane

®

 products.

Trane, or an agent of Trane specifically authorized to 
perform start-up and warranty of Trane

®

 products, will 

provide qualified personnel and standard hand tools to 
perform the disassembly and reassembly work at a 
location specified by the contractor. The contractor shall 
provide the rigging equipment such as chain falls, 
gantries, cranes, forklifts, etc. necessary for the 
disassembly and reassembly work and the required 
qualified personnel to operate the necessary rigging 
equipment.

WARNING

Follow EHS Policies!

Failure to follow instructions below could result in 
death or serious injury.

All Trane personnel must follow the company’s 
Environmental, Health and Safety (EHS) policies 
when performing work such as hot work, electrical, 
fall protection, lockout/tagout, refrigerant handling, 
etc. Where local regulations are more stringent than 
these policies, those regulations supersede these 
policies. 

Non-Trane personnel should always follow local 
regulations.

WARNING

Refrigerant under Positive Pressure!

Failure to follow instructions below could result in an 
explosion which could result in death or serious injury 
or equipment damage. System contains oil and 
refrigerant and may be under positive pressure. 
Recover refrigerant to relieve pressure before opening 
the system. See unit nameplate for refrigerant type. Do 
not use non-approved refrigerants, refrigerant 
substitutes, or refrigerant additives.

NOTICE: 

Equipment Damage!

Mixing refrigerants or oils could result in equipment 
damage including bearing damage, introduction of 
acids into the chiller, or continuous purge pump-out in 
high-head/high ambient applications. CenTraVac 
chillers are manufactured with different refrigerant/oil 
systems: R-123 chillers using OIL00022 and R-514A 
chillers using OIL00334/OIL00335. Verify proper 
refrigerant and oil for your chiller and do NOT mix 
refrigerants or oils!

Содержание CenTraVac CVHM

Страница 1: ...stallation starting up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqualified person could result in death or serious injury When working on the equipment observe all precautions in the literature and on the tags stickers and labels that are attached to th...

Страница 2: ...y hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment or property damage only accidents WARNING Proper Field Wiring and Grounding Required Failure to follow code could result in death or serious injury All field wiring MUST be performed by qualified pers...

Страница 3: ... Trane products Trane or an agent of Trane specifically authorized to perform start up and warranty of Trane products will provide qualified personnel and standard hand tools to perform the disassembly and reassembly work at a location specified by the contractor The contractor shall provide the rigging equipment such as chain falls gantries cranes forklifts etc necessary for the disassembly and r...

Страница 4: ...r in part without written permission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks referenced in this document are the trademarks of their respective owners Revision History Updated information for AFD drive ...

Страница 5: ...10 Contractor Responsibilities 10 Wiring Disassembly 11 Adaptive Frequency Drive Removal 11 Purge Unit Removal 12 Control Panel Removal 13 Tracer AdaptiView Display Arm Removal 14 Compressor Motor Assembly Removal 14 Economizer Removal 17 Condenser Evaporator Disassembly 18 Reassembly 19 Tightening Flanges 20 Brazing 21 Final Installation Procedures 21 ...

Страница 6: ... are metric except waterbox and oil system hardware Note Use only new O rings and gaskets Do NOT reuse O rings or gaskets Components Figure 1 CVHM components page 1 of 2 Detail A Motor Cooling Return Tube Motor Casting Compressor Base Condenser Evaporator Economizer ...

Страница 7: ...Weights CVHM SVN001C EN 7 Figure 1 CVHM components page 2 of 2 1st Volute Discharge 2nd Volute Discharge Wrap Around Pipe See Detail A Condenser Discharge Connection Drive Removed for Clarity Drive Removed for Clarity ...

Страница 8: ...oles on the top of the drive can be used for lifting the drive Figure 2 CVHM drive dimensions in 56 5 8 15 11 16 5 5 8 22 1 7 8 CENTER OF GRAVITY 26 TO 31 CENTER OF GRAVITY 10 TO 12 72 5 16 1 11 16 51 5 16 6 1 8 39 1 3 8 1 3 4 35 7 16 34 1 16 5 8 13 16 ...

Страница 9: ...re required for lifting the compressor assembly metric threads Note Wrap pipe requires three 5 8 in shackles Trane recommends using Crosby screw pin shackles model S 209 stock number 1018482 with 5 8 in pin Table 1 Maximum CVHM unit component weights Component Maximum Weight lb kg Condenser without waterboxes 4253 1934 Condenser waterboxes 923 420 Evaporator without waterboxes 6095 2771 Evaporator...

Страница 10: ...ing refrigerants or oils could result in equipment damage including bearing damage introduction of acids into the chiller or continuous purge pump out in high head high ambient applications CenTraVac chillers are manufactured with different refrigerant oil systems R 123 chillers using OIL00022 and R 514A chillers using OIL00334 OIL00335 Verify proper refrigerant and oil for your chiller and do NOT...

Страница 11: ...ed spaces or the AFD cabinet shipped disassembled from the chiller use the following general information and instructions The maximum weight of the drive is 1900 lb 862 kg Note For specific weights of the AFD cabinet refer to submittal package 1 Remove the AFD upper support bracket bolts at the wrap around pipe side There are two bolts in each bracket 2 Close the isolation valves for the AFD cooli...

Страница 12: ...led to ensure no contaminates are allowed into the system Due to the hygroscopic nature of the oil install a new filter after the chiller has passed through the restricted space Installation of the AFD cabinet is essentially the reverse of the removal procedure All mounting bolts should be torquedtoANSIstandardsbased onthe boltdiameter The motor power wires connecting to the drive output terminals...

Страница 13: ...ur bolts from the bottom of the panel which secure the panel to the lower mounting brackets 3 Loosen the two bolts on the back of the panel which secure the panel to the top mounting brackets See Figure 5 Figure 3 Purge unit Figure 4 Purge unit detail WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury...

Страница 14: ...embling the chiller Cap or cover open lines to prevent entry of foreign material Figure 6 Control panel mounting brackets details WARNING Hazardous Voltage w Capacitors Failure to disconnect power and discharge capacitors before servicing could result in death or serious injury Disconnect all electric power including remote disconnects and discharge all motor start run capacitors before servicing ...

Страница 15: ...n shackle model S 209 stock number 1018482 with a 5 8 in pin is acceptable as shown in Figure 10 Figure 8 Lubrication system Figure 9 Lubrication system detail WARNING Heavy Objects Failure to follow instructions below or properly lift component could result in component dropping and possibly crushing operator technician which could result in death or serious injury and equipment or property only ...

Страница 16: ...ve the two piece wrap pipe The wrap pipe can be disassembled at the mid flange joint a Lift the wrap pipe from the chiller being careful to avoid damaging flange surfaces b Install protective covers on the evaporator wrap pipe and compressor connections Plastic secured with duct tape makes an adequate cover if no heavy objects are set on the openings c Remove the second stage volute to condenser b...

Страница 17: ...et it on a pallet Cover all openings to prevent the entry of foreign material into the economizer condenser and compressor 10 Use the reverse order to reassemble the economizer on the chiller Be sure to install new O rings at the appropriate joints NOTICE Handle with Care Failure to follow instructions below could result in equipment damage The cast iron base of the compressor and the discharge fl...

Страница 18: ...shell support see Figure 16 Then remove the bolts from the flanges connecting the shells 4 Reassemble the evaporator and condenser shells in the reverse order Note Install the top bolts first as these have limited clearance and act as dowel pins 5 Torque all bolts to specifications listed in Table 2 p 20 WARNING Heavy Objects Failure to follow instructions below or properly lift component could re...

Страница 19: ... base plate to protect the bare metal Install two new roll pins into the compressor casting Align the pins into the compressor mounting base Insert the bolts in the compressor base and discharge flange connections 4 Tighten the compressor base and discharge flange bolts See Table 2 p 20 for bolt torque specifications 5 Remove the lifting equipment 6 Set up dial indicators on the compressor end of ...

Страница 20: ...d 13 Torque all bolts to specifications listed in Table 2 14 Reconnect the previously cut compressor supply and return lines oil supply and return lines and the motor cooling lines using the factory supplied couplings Tightening Flanges Flanges with 8 or 12 Bolts Tighten all bolts to a snug tightness following the numerical sequence for the appropriate bolt pattern as shown below Repeat this seque...

Страница 21: ...nstallation can proceed for unit piping wiring etc After installation has been completed fill out CTV ADF001 EN CenTraVac Installation Completion Check Sheet and Request for Trane Service to schedule the startup the chiller commissioning process can be completed by Trane or under the supervision of authorized Trane personnel Note CTV ADF001 EN is also included in the Forms section of CVHM SVX001 E...

Страница 22: ......

Страница 23: ......

Страница 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial and residential applications For more information please visit trane com or tranetechnologies com CVHM SVN001C EN 28 Aug 2020 Supersedes CVHM SVN001B EN Feb 2019 ...

Отзывы: