Installation
22
AH-SVX008C-EN
Controls
If the unit is equipped with an A-Tech controller, see the
Robertshaw 9701i/9725i2 User's Manual shipped with the
unit for programming instructions. Wiring contacts on the
single and dual-stage versions of the A-Tech controller are
shown in
. If the unit is equipped with an E²
controller, see the Series Microprocessor Controller IOM
manual shipped with your unit. For utility connections
refer to the appropriate manual above and the wiring
diagram(s) provided with the unit.
The unit is provided with a pilot hole for a conduit
connection for control wiring. The hole is located near the
electric box in close proximity to the main power pilot
hole. The sizing of the conduit must be per the National
Electrical Code and local code requirements.
Note:
Customer-provided wiring must be in accordance
with the National Electrical Code and local code
requirements for Class 2 circuits.
A-Tech 1.1 Programmable Thermostat
The thermostat requires four conductors wired to the
control terminal board located within the unit electric box.
The thermostat has a terminal strip with box type lugs for
wire connections. See
and refer to the
electrical drawing for proper wire terminations.
A-Tech 1.2 Programmable Thermostat
The thermostat requires seven conductors wired to the
control terminal board located within the unit electric box.
The thermostat provides a terminal strip with box type
lugs for wire connections. See
and refer to
the supplied electrical drawing for proper wire
terminations.
Figure 16.
A-Tech 1.1 (top) and 1.2 (bottom) controller
wiring contacts
Air-Cooled Split Systems
The system interconnecting field wiring illustrations in
through
detail the number
of conductors required for a typical system. Additional
control conductors may be required depending on the
options purchased with the equipment. Refer to the
electrical drawing to determine the total number of
interconnecting conductors required for your system. It is
important to note that the control transformer(s) supplied
with the equipment have been sized and selected based
upon the expected loads for the system.
Y1
R
C
E/W1
O B G
See OHS Electrical Drawing
for Equivalent Terminal Point
C -
24VAC
Common
R -
24VAC
Y1
- 1st stage cooling
E/W1 - 1st stage heating or emergenc
W2 - 2nd stage heating
Y2
- 2nd stage cooling
L
- System fault indicator
O
- Cool active reversing valve
B
- Heat active reversing valve
G -
Fan
TERMINAL DESIGNATORS
W2
Y2
C
R
Y1
E/W1
W2
L
G
B
L
O
Y1
R
C
E/W1
O B G
G
Y1
R
W1
C
B
O
See OHS Electrical Drawing
for Equivalent Terminal Points
A-Tech 1.1 Single-Stage Controller
C -
24VAC
Common
R -
24VAC
Y1
- 1st stage cooling
W1 - 1st stage heating
O
- Cool active reversing valve
B
- Heat active reversing valve
G -
Fan
TERMINAL DESIGNATORS
A-Tech 1.2 Two-Stage Controller
Y2