Installation
20
AH-SVX008C-EN
drain line must be located so it will not be exposed to
freezing temperatures. The drain line should be the full
size of the connection. See the installation drawing
provided with your unit for the size and location of the
condensate drain line.
NOTICE
Coil Fins Damage
Do not use chloride-based water conditioning additives
in the condensate drain pans. They cause corrosion on
the coil fins.
Important:
Properly size and vent the P-trap according
to applicable codes and best practices.
Note:
During normal operation the optional humidifier
drains hot water into the condensate drain line. As
an option, a separate drain line may be provided for
the humidifier.
Condensate Pump
A condensate pump (see figure below) is used to
automatically remove condensate from the air conditioner
and flush water from the humidifier (if applicable). A P-trap
is installed for proper condensate drainage. The height of
the trap is a minimum of 2 in. on most standard systems
to ensure proper water drainage of the drain pan. The
condensate pump discharge line should be 1/2 in. I.D.
(maximum) vinyl tubing or 1/2 in. O.D. (maximum) copper
pipe to prevent excessive back flow to pump.
Figure 14.
Condensate pump
Note:
Pour some water into the condensate drain(s) prior
to start-up. This fills the trap and prevents air from
being drawn up the drain lines.
Humidifier (Optional)
CeilAir systems may include an optional electrode steam
humidifier. The humidifier empties into the condensate
drain pan during the flush/drain cycle. A water supply line
must be connected to the humidfier copper tubing inlet
connection supplied by the factory. Refer to the installation
drawing provided with your unit for the size and location
of the connection. The humidifier requires normal tap
water as the water supply. If the supply water is high in
particulates, an external filter may be needed.
NOTICE
Humidifier Damage
Do not use demineralized water in the humidifier.
Note:
Refer to the humidifier operator's manual supplied
with the TR-OHS unit for complete manufacturer's
information on the humidifier and for supply water
recommendations.
Utility Connections
Main Power
CeilAir units are available in single- or three-phase
variations and a wide range of voltages. Examine the unit
nameplate, located on the outside of the cabinet in close
proximity of the electric box, to determine the operating
voltage, frequency and phase of the system (see
). (Note that the unit serial and model numbers are
also found on the nameplate.) Provided power must meet
the listed specifications. The supply voltage measured at
the unit must be within ±10% of the voltage specified on
the system nameplate, with the exceptions noted below.
The nameplate also provides the full load amps (FLA) the
unit will draw under full design load, the minimum circuit
ampacity (MCA) for wire sizing, and the maximum fuse
size (MAX FUSE) for circuit protection.
Important:
If the nameplate states MAX FUSE/CKT
BKR, fuses or an HACR type circuit breaker
are required to protect the system. Other
protection devices are not allowed based
upon the product listing.
The unit is provided with terminals for all required field-
wiring. It is important to identify the options that were
purchased with the unit in order to confirm which field
connections are required. Refer to the electrical drawing(s)
supplied with the unit for information about power and
control field-wiring.