CTV-PRB004-EN
59
Electrical System–Power Wire Sizing
Table 13. MCA look-up table for 90°C copper conductors rated for 0–2,000 Volts
(a)
Wire Size
1 Conduit
3 Wires
1 Conduit
6 Wires
2 Conduits
3 Wires ea.
3 Conduits
3 Wires ea.
2 Conduits
6 Wires ea.
4 Conduits
3 Wires ea.
5 Conduits
3 Wires ea.
6 Conduits
3 Wires ea.
8
55
6
75
4
95
3
115
2
130
1
145
0
170
272
340
510
544
680
850
1020
00
195
312
390
585
624
780
975
1170
000
225
360
450
675
720
900
1125
1350
0000
260
416
520
780
832
1040
1300
1560
250
290
464
580
870
928
1160
1450
1740
300
320
512
640
960
1024
1280
1600
1920
350
350
560
700
1050
1120
1400
1750
2100
400
380
608
760
1140
1216
1520
1900
2280
500
430
688
860
1290
1376
1720
2150
2580
600
475
760
950
1425
1520
1900
2375
2850
Note:
Use this table to select supply leads for all starters and motor leads for remote-mounted across-the-line, primary reactor, autotransformer, and
Adaptive Frequency Drives. Value in table must be larger than the MCA to use the wire combination.
(a) , Based on 2011 NEC Table 310.15(B)(16)
Table 14. MCA look-up table for 90°C copper conductors rated for 0–2,000 Volts
(a)
Wire Size
1 Conduit
6 Wires
2 Conduits
3 Wires ea.
2 Conduits
6 Wires ea.
4 Conduits
3 Wires ea.
3 Conduits
6 Wires ea.
6 Conduits
3 Wires ea.
8
75
94
6
103
129
4
131
163
3
158
198
2
179
224
1
200
250
0
234
293
469
586
703
879
00
269
336
537
672
806
1008
000
310
387
620
775
931
1163
0000
358
448
717
896
1075
1344
250
400
500
800
1000
1200
1500
300
441
551
882
1103
1324
1655
350
482
603
965
1206
1448
1810
400
524
655
1048
1310
1572
1965
500
593
741
1186
1482
1779
2224
600
655
819
1310
1637
1965
2456
Note:
Use this table to size motor leads from remote-mounted wye-delta and solid-state starters (inside-the-delta
designs only). Value in table must be larger than the MCA to use the wire combination.
(a) Based on 2011 NEC Table 310.15(B)(16)