Operator Display Setup Options
56
BMTW-SVU02C-EN
Calibrating the Operator-Display
Touch Screen
Occasionally, you may need to recalibrate the touch screen for accuracy of
the touch targets.
To recalibrate the touch screen:
1.
From the home screen press the Setup button. The Setup menu dis-
plays (see Figure 42 on page 51).
2.
Press the Calibrate Touch Screen button. The calibration screen dis-
plays with the calibration target in the upper left-hand corner of the
screen (see Figure 48).
Figure 48: Calibration Touch Target #1
CAUTION
AVOID EQUIPMENT DAMAGE!
Do not use sharp objects on the touch screen.
3.
Touch the target using your finger or a small, pliable, blunt object,
such as a pencil eraser. Hold until the beeping stops. The calibration
target appears at the bottom right-hand corner of the screen (see
Figure 49 on page 57).
Calibration target
Содержание BCU Operator Display
Страница 1: ...BMTW SVU02C EN Operations BCU Operator Display...
Страница 2: ......
Страница 3: ...Operations BCU Operator Display Tracer Summit BMTW SVU02C EN June 2006...
Страница 6: ......
Страница 10: ...Contents iv BMTW SVU02C EN...
Страница 60: ...Making a Timed Override Request 50 BMTW SVU02C EN...
Страница 70: ...Maintaining the Operator Display Touch Screen 60 BMTW SVU02C EN...
Страница 81: ......