background image

20 

 18-CD33D1-4

Installer’s Guide

CAUTION

!

When the vent pipe is exposed to temperatures below 

freezing, i.e., when it passes through unheated spaces, 

etc., the pipe must be insulated with 1/2 inch (22.7 mm) 

thick Armaflex-type insulation or equal.  If the space 

is heated sufficiently to prevent freezing, then the in-

sulation would not be required. If domestic water pipes 

are not protected from freezing then it is assumed the 

space meets the condition of a heated space.
HORIZONTAL VENTING THROUGH WALL
These furnaces may be installed as direct vent (as 
shipped) or as nondirect vent. Installation must con-
form to national, state, and local codes.

The vent & inlet terminals must be located at least 12" 
minimum above normally expected snow accumulation 
level (18" minimum in Canadian applications).
Avoid areas where staining or condensate drippage may 
be a problem.
Location of the vent/ wind terminal should be chosen to 
meet the requirements of Figure 24 for either direct or 
non-direct vent applications.

PITCH –

 Venting through the wall must maintain 1/4" 

per foot pitched upward to insure that condensate drains 
back to the furnace.

FLUE GAS DEGRADATION – 

The moisture content of 

the flue gas may have a detrimental effect on some build-
ing materials. This can be avoided by using the roof or 
chimney venting option. When wall venting is used on 
any surface that can be affected by this moisture, it is rec-
ommended that a corrosion resistant shield (24 inches 
square) be used behind the vent terminal. This shield can 
be wood, plastic, sheet metal, etc. Also, silicone caulk all 
cracks, seams and joints within 3 feet of the vent termi-
nal.

COMBUSTIBLE MATERIAL WALL

A minimum clearance of 1" to combustible materials must 
be maintained when using single wall stainless steel 
venting. See Figure 28.

Shield material to be a minimum of 24 gauge stainless 
or aluminized sheet metal. Minimum dimensions are 
12"x12". Shield must be fastened to both inside and out-
side of wall. Use screws or anchor type fasteners suited 
to the outside or inside wall surfaces.

NONCOMBUSTIBLE MATERIAL WALL

The hole through the wall must be large enough to main-
tain pitch of vent and properly seal.
Use cement mortar seal on inside and outside of wall. 
See Figure 29.

VENTING THROUGH THE ROOF

When penetrating roof with a 2" PVC vent pipe, a 2" elec-
trical conduit flashing may be used for a weather tight 
seal. Lubricate flexible seal on flashing before PVC pipe 
is pushed through the seal. (Field Supplied)

NOTE:

No vent cap as shown in Figure 33 is the preferred 

method for vertical vent termination in extremely cold 

climates.

In extreme climate conditions, insulate the exposed 

pipe above the roof line with Armaflex type insulation.

VENT

COMBUSTION

AIR

VENT

VENT

PLATE

VENT

CAP

12" MINIMUM

TO OVERHANG

MAINTAIN 12" MINIMUM CLEARANCE 

ABOVE HIGHEST ANTICIPATED SNOW 

LEVEL OR GRADE  WHICHEVER IS GREATER

SCREWS

(4 req.)

ANCHORS

(4 req.)

7.2"

3.2"

BAYVENT200B

h

j

BAYAIR30AVENTA

(Sidewall)

COUPLING
(PLASTIC
VENTING)

STUD

    PVC WALL
MOUNT FLANGE
   (OPTIONAL)

  APPROVED
TERMINATION

1” CLEARANCE
(AIR SPACE)

VENTING THROUGH COMBUSTIBLE WALLS
               Pitch - 1/4 Inch Per Foot

          CLEARANCE (0” ACCEPTABLE FOR PVC VENT PIPE)
(1” ACCEPTABLE FOR TYPE 29-4C STAINLESS STEEL VENT PIPE)

12” MINIMUM ABOVE
NORMALLY EXPECTED
SNOW ACCUMULATION
LEVEL 

6 IN. MIN.
(TO JOINT)

k

For Canadian applications only, IPEX 196006,  IPEX 081216, IPEX 
081218, and IPEX 081219 may be used for horizontal vent terminations.

For Canadian applications only, IPEX 196006,  IPEX 081216, IPEX 
081218, and IPEX 081219 may be used for horizontal vent terminations.

Содержание ADH1B040A9H21B

Страница 1: ...his installation must comply with NATIONAL STATE AND LOCAL CODES IMPORTANT This Document is customer property and is to remain with this unit Please return to service information pack upon completion...

Страница 2: ...ameplate marking e 100 of the furnace combustion air requirement must come from outside the structure WARNING CARBON MONOXIDE POISONING HAZARD Failure to follow the steps outlined below for each ap pl...

Страница 3: ...ation If damage to contents is found report the damage immediately to the delivering agency Codes and local utility requirements governing the instal lation of gas fired equipment wiring plumbing and...

Страница 4: ...garage it must be installed so that the burners and the ignition source are located not less than 18 inches above the floor and the furnace must be located or protected to avoid physical damage from...

Страница 5: ...H OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES NOTES 1 UH1C100A9H41 UH1D120A9H51 REQUIRE 3 DIAMETER VENT PIPE 2 DIAMETER OF VENT PIPE MAY BE LIMITED TO 2 1 2 OR 3 ON SOME MODELS AT DIFFERENT ALTITUDES...

Страница 6: ...6 18 CD33D1 4 Installer s Guide From Dwg 21C341885 DH1 H DOWNFLOW HORIZONTAL OUTLINE DRAWING ALL DIMENSIONS ARE IN INCHES...

Страница 7: ...point either toward or away from the furnace See the 2 4TXC coil Installer s Guide for more details The cased coil is secured to the furnace and both the fur nace and the cased coil must be properly...

Страница 8: ...ovisions of the local building codes Special conditions created by mechanical exhausting of air and fireplaces must be con sidered to avoid unsatisfactory furnace op eration OUTSIDE AIR IS RECOMMENDED...

Страница 9: ...d space shall be considered in making this determination Refer to Ta ble 2 for minimum open areas requirements 2 All air from outdoors as in Figure 9 The confined space shall be provided with two perm...

Страница 10: ...MS Where there is no complete return duct system the return connection must be run full size from the fur nace to a location outside the utility room basement attic or crawl space Do Not install retur...

Страница 11: ...des or 2 1 side and the bottom or 3 just the bottom The furnace and the bottom filter rack BAYRACK960 in stallation can be seen in Figure 11 The furnace filter in the bottom or side configuration can...

Страница 12: ...Return Air Duct Connections section on page 10 d Compress the filter rack and reinstall in the side position on the furnace Confirm that the upper retaining pin screw locks into the engagement hole i...

Страница 13: ...of the cabinet i Airflow DOWNFLOW HORIZONTAL DOWNFLOW Airflow o TYPICAL DOWNFLOW FURNACE RETURN AIR FILTER INSTALLATIONS These furnaces require high velocity type air filters Downflow furnace filters...

Страница 14: ...nace Proper installation of the vent system is necessary to assure drainage of the conden sate and prevent deterioration of the vent system American Gas Association has certified the design of condens...

Страница 15: ...2 ASTM D2846 F441 SCH 40 80 212 ASTM F441 F442 SDR SERIES 212 ASTM F442 ABS ASTM STANDARD PIPE TYPE ALLOWABLE TEMPERATURE MARKING D2661 SCH 40 DWV 180 ASTM D2661 F628 SCH 40 DWV CELLULAR CORE 180 ASTM...

Страница 16: ...r in staller If the installer chooses separate pressure zones for the terminals the combustion air inlet termination must be in the higher more positive pressure zone HORIZONTAL VENTING NOTE Vent term...

Страница 17: ...ian applications ONLY IPEX 196006 may be used for horizontal and vertical terminations IPEX 081216 IPEX 081218 and IPEX 081219 may only be used for horizontal vent terminations Equivalent lengths are...

Страница 18: ...pliance 6 inches 15 cm for appliances 10 000 Btuh 3 kw 12 inches 30 cm for appliances 10 000 Btuh 3 kw and 100 000 Btuh 30 kw 36 inches 91 cm for appliances 100 000 Btuh 30 kw 6 inches 15 cm for appli...

Страница 19: ...r the combustion air inlet to any other appliance 6 inches 15 cm for appliances 10 000 Btuh 3 kw 12 inches 30 cm for appliances 10 000 Btuh 3 kw and 100 000 Btuh 30 kw 36 inches 91 cm for appliances 1...

Страница 20: ...nce of 1 to combustible materials must be maintained when using single wall stainless steel venting See Figure 28 Shield material to be a minimum of 24 gauge stainless or aluminized sheet metal Minimu...

Страница 21: ...R OTHER SUITABLE SUPPORTS AT MAXIMUM OF 3 0 INTERVALS COMBUSTION AIR INLET USE ONLY APPROVED TERMINATION TEE 3 PIPING 2 2 1 2 or 3 PIPING REDUCING COUPLING FIELD SUPPLIED IF NEEDED SEAL ALL WALL CAVIT...

Страница 22: ...nnected into a condensate drain pump an open or vented drain or it can be connected to the out let hose of the furnace s condensate trap Outdoor draining of the furnace and coil condensate is per miss...

Страница 23: ...me of completion of installation the owner shall have a period of thirty 30 days to comply with the above requirements provided however that during said thirty 30 day period a battery operated carbon...

Страница 24: ...UPLING AND METAL PANEL WITH HI TEMP RTV SILICONE SEALANT CLEARANCE 0 ACCEPTABLE FOR PVC VENT PIPE 1 ACCEPTABLE FOR TYPE 29 4C STAINLESS STEEL VENT PIPE SUPPORT THE SINGLE WALL FLUE PIPE AND CENTER IT...

Страница 25: ...fitting is needed See Figure 44 To change to a right side drain remove the drain lines from the trap rotate the trap 180 so it exits to the right then reconnect the lines Start with a 1 2 90 CPVC str...

Страница 26: ...s that may result in damage to plants NOTE Use 1 2 or larger PVC or CPVC pipe and fittings as re quired for drain connections fittings pipe and solvent cement not provided NOTE A corrosion resistant c...

Страница 27: ...eaner and or humidifier is provided on the integrated control Refer to the SERVICE FACTS literature and unit wiring diagram attached to furnace diagram attached to furnace TWINNING FURNACES These furn...

Страница 28: ...NG 1 STAGE COOLING THERMOSTAT OUTDOOR SECTION WITHOUT TRANSFORMER TWIN TWIN R1 R1 TWINNING CONNECTION DIAGRAM FOR TWINNING 1 STAGE FURNACES WITH SINGLE WIRE TWINNING FEATURE 1 STAGE HEATING ONLY THERM...

Страница 29: ...s and Propane Installation Code CSA B149 1 The upflow horizontal furnace is shipped standard for left side installation of gas piping A knockout is provided on the right side for an alternate gas pipi...

Страница 30: ...VE WITH MANUAL SHUTOFF MAIN MANUAL SHUTOFF VALVE GROUND UNION JOINT DRIP LEG THE DOWNFLOW VERTICAL MAY BE INSTALLED LEFT OR RIGHT SIDE GAS PIPING HORIZONTAL FURNACE GAS PIPING MAY BE FROM EITHER SIDE...

Страница 31: ...titude d Replace and tighten the regulator cover screw securely 6 Cycle the valve several times to verify regulator set ting a Repeat steps 5 6 if needed 7 Turn off all electrical power to the system...

Страница 32: ...ll plugs removed or loosened when adjusting gas pressure Leak check the fittings before placing the furnace into regular service Failure to follow this warning could result in fire explo sion or prope...

Страница 33: ...46 47 42 44 45 46 47 48 43 44 45 47 47 48 43 44 45 47 47 49 43 45 46 47 48 49 44 45 47 48 48 49 44 46 47 48 49 50 45 47 48 49 49 50 46 47 48 49 50 51 47 48 50 50 51 52 54 55 56 57 58 54 55 56 58 59 5...

Страница 34: ...e ignitor warm up period will begin The ignitor will heat for approximately 20 seconds then the gas valve is energized to permit gas flow to the burners The flame sensor confirms that igni tion has be...

Страница 35: ...as CONDITIONS AFFECTING FURNACE OPERATION 1 EXCESSIVE COMBUSTION PRESSURE WIND IN EXCESS OF 40 M P H VENT OR FLUE BLOCK AGE If pressure against induced draft blower outlet be comes excessive the press...

Страница 36: ...recommends that users of gas burning appli ances install carbon monoxide detectors as well as fire and smoke detectors per the manufacturers installation instructions to help alert dwelling occupants...

Отзывы: