Step 3 – Location and Recommendation Information
N
No
otte
e:: The unit is shipped for horizontal installation.
N
No
otte
e:: During heating operation, avoid supply air below
80 degrees F or return air below 50 degrees F to
prevent flue gas condensation.
H
Ho
orriizzo
on
ntta
all A
Aiirrffllo
ow
w U
Un
niittss
1. Location of the unit must allow service clearance
around it to ensure adequate serviceability,
maximum capacity, and peak operating efficiency.
2. These units are designed for outdoor installation.
They may be installed directly on a slab, wood
flooring, or on Class A, B, or C roof covering
material. The discharge air from the condenser fans
must be unrestricted for a minimum of 3 feet above
the unit.
3. The louvers above and below the flue hood in the
side panel must have adequate clearance around
the air opening into the combustion area. See
dimensional drawings preceding this section.
4. Examine all flue product-carrying areas of the
furnace, its vent system, and the main burner for
safe operation.
IIm
mp
po
orrtta
an
ntt:: A minimum 0" clearance to combustible
material shall be maintained on air
outlet duct.
5. Exhaust vents or other sources of contaminated air
must not be near the unit’s air inlet if outside air is
to be introduced as make-up air or a ventilation
feature is to be used. Contamination from exhaust
vents or chimneys may also foul the condenser
causing degraded performance.
6. Check the handling facilities to ensure the safety of
personnel and the unit(s).
7. The unit must be mounted level for proper drainage
of water through the drain holes in the base pan.
8. The unit should not be exposed to direct roof water
runoff.
9. Flexible duct connectors must be of a flame
retardant material. All duct work outside of the
structure must be insulated and weatherproofed in
accordance with local codes.
10. Holes through exterior walls or roof must be sealed
in accordance with local codes.
11. All fabricated outdoor ducts should be as short as
possible.
C
Clle
ea
arra
an
ncce
ess
1. See previous outline illustrations for single unit
installation clearances.
2. Any reduction of the unit clearances indicated in
these figures may result in condenser coil
starvation or the recirculation of warm condenser
air. Actual clearances, which appear to be
inadequate should be reviewed with a local
engineer.
3. See the unit’s nameplate for the absolute minimum
clearance between the unit and any combustible
surfaces.
D
Do
ow
wn
n A
Aiirrffllo
ow
w U
Un
niittss
1. Location of the unit must allow service clearance
around it to ensure adequate serviceability,
maximum capacity, and peak operating efficiency.
2. Refer to the Installation section for instruction on
converting the supply and return airflow covers to
down airflow.
3. The field assembled Roof Mounting Curb
(BAYCURB050A or BAYCURB051A) or a field
fabricated curb should be in place before the unit is
hoisted to the roof top.
The Roof Mounting Curb (frame) must be installed
on a flat, level section of the roof (maximum of 1/4"
per foot pitch) and provide a level mounting surface
for the unit. Also, be sure to provide sufficient
height above the roof to prevent water from
entering the unit.
4. Be sure the mounting curb spans structural
members (trusses) of the roof, thereby providing
sufficient support for the weight of the unit, the
curb, the duct(s), and any factory or field installed
accessories.
5. The unit must be mounted level for proper drainage
of water through the drain holes in the base pan.
6. Be sure the hole in the structure for the ducts is
large enough to accommodate the fabricated ducts
and the insulation surrounding them. Flexible duct
connectors must be of a flame retardant material.
All duct work outside of the structure must be
insulated and weatherproofed in accordance with
local codes.
7. Holes through exterior walls or roof must be sealed
in accordance with local codes.
8. These units are designed for outdoor installation.
They may be installed directly on a slab, wood
flooring, or on Class A, B, or C roof covering
material. The discharge air from the condenser fans
must be unrestricted for a minimum of 3 feet above
the unit.
9. The louvers above and below the flue hood in the
side panel must have adequate clearance around
the air opening into the combustion area.
10. Examine all flue product-carrying areas of the
furnace, its vent system, and the main burner for
safe operation.