18-AC51D1-10E-EN
23
1. Leak check refrigerant lines. ........................................ [ ]
2. Properly insulate suction lines and fittings. ................... [ ]
3. Properly secure and isolate all refrigerant lines. ........... [ ]
4. Seal passages through masonry.
If mortar is used, prevent mortar from coming
into direct contact with copper tubing. .......................... [ ]
5. Verify that all electrical connections are tight. ............... [ ]
6. Observe outdoor fan during on cycle for clearance
and smooth operation. .................................................. [ ]
Section 15. Checkout Procedures
15.1 Operational And Checkout Procedures
CHECKOUT PROCEDURE
After installation has been completed, it is recommended that the entire system be checked against the following list:
Final phases of this installation are the unit Operational and Checkout Procedures. To obtain proper performance, all units
must be operated and charge adjustments made.
Important:
Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if
necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and
properly secured.
7. Be sure that indoor coil drain line drains freely. Pour water
into drain pan. ............................................................... [ ]
8. Be sure that supply registers and return grilles are open
and unobstructed. ......................................................... [ ]
9. Be sure that a return air filter is installed. ..................... [ ]
10. Be sure that the correct airflow setting is used.
(Indoor blower motor) ................................................... [ ]
11. Operate complete system in each mode to
ensure safe operation. .................................................. [ ]
Section 16. Refrigerant Circuits
PRINTED FROM D157394P01
018N, 019N, 024N, 025N, 030N & 036N Models
024/25L, 030/31L, 036/37L & 036/37M Models
Содержание 4TTR4018-060
Страница 25: ...18 AC51D1 10E EN 25 PRINTED FROM D158513P01 018L Models PRINTED FROM D158515P01 060L Models...
Страница 26: ...26 18 AC51D1 10E EN Section 17 Wiring Diagrams 018N 019N 024N 025N 042N 049N Models...
Страница 27: ...18 AC51D1 10E EN 27 018N 019N 024N 025N 042N 049N Models...
Страница 28: ...28 18 AC51D1 10E EN PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 29: ...18 AC51D1 10E EN 29 PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 30: ...30 18 AC51D1 10E EN 060N Models...
Страница 31: ...18 AC51D1 10E EN 31 060N Models...
Страница 32: ...32 18 AC51D1 10E EN 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 33: ...18 AC51D1 10E EN 33 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 34: ...34 18 AC51D1 10E EN 060L Models...
Страница 35: ...18 AC51D1 10E EN 35 060L Models...