17
STEP 1
- Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recom-
mended method of charging above 55º F ambi-
ent outdoor temperature.
Note:
For Superheat (In Cooling Mode), refer to
the Superheat Charging Table
For best results the indoor temperature should
be kept between 70º F to 80º F.
Note:
It is important to return in the spring or
summer to accurately charge the system in the
cooling mode when outdoor ambient tempera-
ture is above 55º F.
STEP 1
- Use the refrigerant line total length
and lift measurements from Section 5 and use
line length adders as shown in Section 5.2 if
required.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
Section 14. System Charge Adjustment
14.1 Temperature Measurements (Systems can be rated with TXV, EEV or Piston. Ensure charging method
is correct).
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
Indoor Temp
80º F
70º F
Outdoor Temp
55º F
120º F
LIFT
Содержание 4TTR4018-060
Страница 25: ...18 AC51D1 10E EN 25 PRINTED FROM D158513P01 018L Models PRINTED FROM D158515P01 060L Models...
Страница 26: ...26 18 AC51D1 10E EN Section 17 Wiring Diagrams 018N 019N 024N 025N 042N 049N Models...
Страница 27: ...18 AC51D1 10E EN 27 018N 019N 024N 025N 042N 049N Models...
Страница 28: ...28 18 AC51D1 10E EN PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 29: ...18 AC51D1 10E EN 29 PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 30: ...30 18 AC51D1 10E EN 060N Models...
Страница 31: ...18 AC51D1 10E EN 31 060N Models...
Страница 32: ...32 18 AC51D1 10E EN 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 33: ...18 AC51D1 10E EN 33 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 34: ...34 18 AC51D1 10E EN 060L Models...
Страница 35: ...18 AC51D1 10E EN 35 060L Models...