18-AC51D1-10E-EN
19
STEP 3
- Stabilize the system by operating for a
minimum of 20 minutes.
At startup, or whenever charge is removed or
added, the system must be operated for a mini-
mum of 20 minutes to stabilize before accurate
measurements can be made.
20 MIN.
Design Subcooling Value = __________º F
(from nameplate or Service Facts)
Subcooling Correction = __________º F
Final Subcooling Value = __________º F
036 & 037 Models
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET
)
10
20
25
30
40
60
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
Add 5°
Add 4°
Add 2°
Add 3° of Subcooling
Add 1° of Subcooling
042 & 043 Models
Add 6°
Add 5°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
048 Models
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
Add 6°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 5° of Subcooling
Add 4° of Subcooling
Add 3° of Subcooling
Add 2° of Subcooling
Add 1° of Subcooling
Design
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
060 Models
030 & 031 Models
Add 4°
Add 3°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 2° of Subcooling
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
018 Models
Add 3°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
024 & 025 Models
Add 4°
Add 2°
TOTAL REFRIGERANT LINE LENGTH (FEET)
REFRIGERANT LINE LIFT (FEET)
10
20
25
30
40
60
Add 1° of Subcooling
Use Design Subcool Value
60
50
40
30
25
20
15
10
0
SUBCOOL CHARGING CHART CORRECTIONS TABLE (FOR LINE LENGTH AND RISE)
For 018L, 024/25L, 030/31L, 036/37L, 036/37M, 042/43L, 048L and 060L Models:
Содержание 4TTR4018-060
Страница 25: ...18 AC51D1 10E EN 25 PRINTED FROM D158513P01 018L Models PRINTED FROM D158515P01 060L Models...
Страница 26: ...26 18 AC51D1 10E EN Section 17 Wiring Diagrams 018N 019N 024N 025N 042N 049N Models...
Страница 27: ...18 AC51D1 10E EN 27 018N 019N 024N 025N 042N 049N Models...
Страница 28: ...28 18 AC51D1 10E EN PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 29: ...18 AC51D1 10E EN 29 PRINTED FROM D157362P05 REVB 030N 036N 048N Models...
Страница 30: ...30 18 AC51D1 10E EN 060N Models...
Страница 31: ...18 AC51D1 10E EN 31 060N Models...
Страница 32: ...32 18 AC51D1 10E EN 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 33: ...18 AC51D1 10E EN 33 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...
Страница 34: ...34 18 AC51D1 10E EN 060L Models...
Страница 35: ...18 AC51D1 10E EN 35 060L Models...