Section 12. Electrical - High Voltage

12.1 High Voltage Power Supply

The high voltage power supply must agree with 
the equipment nameplate.

Power wiring must comply with national, state, 
and local codes.

Follow instructions on unit wiring diagram located 
on the inside of the control box cover and in the 
Service Facts document included with the unit.

12.2 High Voltage Disconnect Switch

12.3 High Voltage Ground

Ground the outdoor unit per national, state, and 
local code requirements.

LIVE ELECTRICAL COMPONENTS!
During installation, testing, servicing, and 
troubleshooting of this product, it may be nec-
essary to work with live electrical components. 
Failure to follow all electrical safety precau-
tions when exposed to live electrical compo-
nents could result in death or serious injury.

WARNING

!

Install a separate disconnect switch at the 
outdoor unit.

For high voltage connections, flexible electri-
cal conduit is recommended whenever vibra-
tion transmission may create a noise problem 
within the structure.

Содержание 4TTR4018-060

Страница 1: ...proved matched indoor and outdoor systems Some of the benefits of installing approved matched indoor and outdoor split systems are maximum efficiency optimum performance and the best overall system re...

Страница 2: ...EN and APP APG011 EN or APP APG012 EN Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touches the rolled edge No torque...

Страница 3: ...x W in Weight lb 4TTR4018N 29 x 26 x 29 133 4TTR4019N 29 x 30 x 33 161 4TTR4024N 29 x 26 x 29 133 4TTR4025N 29 x 30 x 33 162 4TTR4030N 33 x 30 x 33 156 4TTR4036N 33 x 30 x 33 156 4TTR4042N 37 x 34 x...

Страница 4: ...ear Bedrooms Min 5 Unrestricted Access Panel Min 3 Unrestricted 2 2 Refrigerant Piping Limits 1 The maximum length of refrigerant lines from outdoor to indoor unit should NOT exceed sixty 60 feet 2 Th...

Страница 5: ...ound to the unit 2 4 Coastal Considerations If installed within one mile of salt water including seacoasts and inland waterways models without factory sup plied Seacoast Salt Shields require the addit...

Страница 6: ...ne length adders Line Length TUBING INFORMATION LINE TYPE REFRIGERANT TO ADD AT SPECIFIED ADDITIONAL LENGTH Suction Line Liquid Line 20 ft 30 ft 40 ft 50 ft 60 ft 3 4 3 8 3 oz 9 oz 15 oz 21 oz 27 oz 7...

Страница 7: ...ply with National State and Local Codes when isolating line sets from joists rafters walls or other structural elements Isolation From Joist Rafter Side View 8 Feet Maximum Secure Vapor line from jois...

Страница 8: ...e or other appropriate method every 8 ft 8 Feet Maximum Isolation Through Wall DO NOT hang line sets from ductwork Sealant Insulation Vapor Line Wall Ductwork Isolator Line Set Section 7 Refrigerant L...

Страница 9: ...orrect direction of refrigeration flow away from outdoor unit and toward evapo rator coil as illustrated Braze the filter drier to the Liquid Line Continue the dry nitrogen purge Do not remove the wet...

Страница 10: ...P 2 Check for leaks by using a soapy solu tion or bubbles at each brazed location Remove nitrogren pressure and repair any leaks before continuing Section 8 Refrigerant Line Leak Check 8 1 Check For L...

Страница 11: ...ete blank off the vacuum pump and micron gauge and close the valves on the manifold gauge set 1 MIN Section 10 Service Valves 10 1 Open the Gas Service Valve 0350 Microns ON OFF CAP 1 4 TURN ONLY COUN...

Страница 12: ...lve System Service Port 3 16 Hex Wrench Unit Side of Service Valve Extreme caution should be exercised when opening the Liquid Line Service Valve Turn counterclockwise until the valve stem just touche...

Страница 13: ...e 24 VAC HOT FAN 24 VAC Common SOV COOL HEAT 1st STAGE HEATING 2nd STAGE EMERGENCY HEAT Pink White O Y1 Y2 BK WH BLK BK WH BLK Thermostat Air Handler Outdoor Unit R G B W1 W2 B R G B C Yl W1 W2 Blue 2...

Страница 14: ...l to BK of the air handler TAM4 only Wire as shown no BK is available TAM7 only When using a BK enabled comfort control cut BK jumper on the AFC and connect BK from comfort control to BK of the air ha...

Страница 15: ...gh Voltage Ground Ground the outdoor unit per national state and local code requirements LIVE ELECTRICAL COMPONENTS During installation testing servicing and troubleshooting of this product it may be...

Страница 16: ...s to apply power to the indoor and outdoor units STEP 5 Set system thermostat to ON OFF DONE CANCEL ON OFF STEP 4 Wait one 1 hour before starting the unit if compressor crankcase heater acces sory is...

Страница 17: ...er to accurately charge the system in the cooling mode when outdoor ambient tempera ture is above 55 F STEP 1 Use the refrigerant line total length and lift measurements from Section 5 and use line le...

Страница 18: ...ooling 15 10 0 1 20 30 40 50 60 70 80 90 100 110 120 130 140 150 Add 4 Add 2 Add 1 Add 1 REFRIGERANT LINE LIFT FT SUBCOOL CHARGING CHART CORRECTIONS TABLE FOR LINE LENGTH AND RISE TOTAL REFRIGERANT LI...

Страница 19: ...bcooling Add 2 of Subcooling Add 1 of Subcooling Use Design Subcool Value 60 50 40 30 25 20 15 10 0 SUBCOOL CHARGING CHART CORRECTIONS TABLE FOR LINE LENGTH AND RISE Add 6 TOTAL REFRIGERANT LINE LENGT...

Страница 20: ...essure should be ap proximately 327 PSI This is the shown as the intersection of the Final Subcooling column and the Liquid Temperature row Table 14 2 8 9 10 11 12 13 14 179 182 185 188 191 195 198 19...

Страница 21: ...arged 2 Remove gages 3 Replace service port caps to prevent leaks Tighten finger tight plus an additional 1 6 turn STEP 8 Verify typical performance Refer to System Pressure Curves at the end of the d...

Страница 22: ...9 21 24 26 Using a digital psychrometer measure the return air wet bulb temperature at the unit just before the coil Also measure the outdoor dry bulb tem perature Use these temperatures to locate the...

Страница 23: ...erational and Checkout Procedures To obtain proper performance all units must be operated and charge adjustments made Important Perform a final unit inspection to be sure that factory tubing has not s...

Страница 24: ...24 18 AC51D1 10E EN 042N 048N Models 042 43L 048L Models PRINTED FROM D158514P01 049N 060N Models PRINTED FROM D159175...

Страница 25: ...18 AC51D1 10E EN 25 PRINTED FROM D158513P01 018L Models PRINTED FROM D158515P01 060L Models...

Страница 26: ...26 18 AC51D1 10E EN Section 17 Wiring Diagrams 018N 019N 024N 025N 042N 049N Models...

Страница 27: ...18 AC51D1 10E EN 27 018N 019N 024N 025N 042N 049N Models...

Страница 28: ...28 18 AC51D1 10E EN PRINTED FROM D157362P05 REVB 030N 036N 048N Models...

Страница 29: ...18 AC51D1 10E EN 29 PRINTED FROM D157362P05 REVB 030N 036N 048N Models...

Страница 30: ...30 18 AC51D1 10E EN 060N Models...

Страница 31: ...18 AC51D1 10E EN 31 060N Models...

Страница 32: ...32 18 AC51D1 10E EN 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...

Страница 33: ...18 AC51D1 10E EN 33 018L 024 25L 030 31L 036 37L 036 37M 042 43L 048L Models PRINTED FROM D157362P05 REVB...

Страница 34: ...34 18 AC51D1 10E EN 060L Models...

Страница 35: ...18 AC51D1 10E EN 35 060L Models...

Страница 36: ...OF OD TEMP ID W B 3 READ LIQUID 4 OR SUCTION 5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 305 PSIG LIQUID PRESSURE...

Страница 37: ...D W B 3 READ LIQUID 4 OR SUCTION 5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 286 PSIG LIQUID PRESSURE SHOULD BE 1...

Страница 38: ...5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 297 PSIG LIQUID PRESSURE SHOULD BE 10 PSI OF CHART 5 SUCTION PRESSURE...

Страница 39: ...UID 4 OR SUCTION 5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 309 PSIG LIQUID PRESSURE SHOULD BE 10 PSI OF CHART 5...

Страница 40: ...3 READ LIQUID 4 OR SUCTION 5 PRESSURE IN LEFT COLUMN EXAMPLE 1 OUTDOOR TEMP 82 F 2 INDOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 313 PSIG LIQUID PRESSURE SHOULD BE 10 PSI...

Страница 41: ...82 F 2 IN DOOR WET BULB 67 F 3 AT INTERSECTION ACTUAL 4 LIQUID PRESSURE 600 CFM IS 306 PSIG LIQUID PRESSURE SHOULD BE 10 PSI OF CHART 5 SUCTION PRESSURE 600 CFM IS 142 PSIG SUCTION PRESSURE SHOULD BE...

Страница 42: ...CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F TO CHECK COOLING PERFORMANCE SELECT THE PROPER INDOOR CFM ALLOW PRESSURES TO STABILIZE MEASURE INDOOR WET BULB TEMPERATURE OUTDOOR TEMPERATURE L...