background image

 

Page 27

Installer’s Guide

Service Maintenance

Service maintenance should be performed by qualified service 

personnel. 

Cooling Season

To keep the unit operating safely and efficiently, the manufacturer 

recommends that a qualified service technician check the entire 

system at least once each season or more often if needed. The 

service technician should examine these areas of the unit:

 

filters (for cleaning or replacement)

  motors and drive system components

 

economizer gaskets (for possible replacement)

 

safety controls (for mechanical cleaning)

 

electrical components and wiring (for possible replacement 

and connection tightness)

 

condensate drain (for proper sealing and cleaning)

 

unit duct connections (to see that they are physically sound 

and sealed to the unit casing)

 

unit mounting support (for structural integrity)

 

the unit (for obvious unit deterioration)

Owner Maintenance

Some of the periodic maintenance functions of the unit can be 

performed by the owner; this includes replacing the disposable 

or cleaning the permanent air filters, cleaning the unit cabinet, 

and conducting a general unit inspection on a regular basis.

Filters

When

 

the system is in constant operation,

 inspect the filters 

at least once each month.
If you have disposable-type filters, replace them with new filters 

of the same type and size.  

Do not attempt to clean dispos-

able filters.

Permanent-type filters can be cleaned by washing them with a 

mild detergent and water. Make sure that the filters are thoroughly 

dry before reinstalling them.

NOTE:

  

It may be necessary to replace permanent filters 

annually if washing fails to clean the filter or if the filter shows 

signs of deterioration.  Be sure to use the same type and 

size as was originally installed.

Condenser Coil

Be sure to keep all vegetation and debris away from the condenser 
coil area.

Maintenance

Heating Season

Complete the following unit inspections and service routines 

described at the beginning of each heating season.

 

Visually inspect the unit to ensure that the airflow required 

for combustion and condenser coil is not obstructed from the 

unit.

 

Inspect the control panel wiring to verify that all electrical 

connections are tight and that the wire insulation is intact.

 

Check the operation of the gas ignition system as follows: 

Turn off the gas supply with the unit operating to verify that 

the gas valve closes and that a re-ignition cycle is initiated 

by the unit. 

 

Visually inspect the inside of the burners and the burner ports 

for deposit buildup and corrosion.  Wipe and brush the inside 

of the burner and the burner ports and then clean with a dry 

cloth.  If the deposit buildup or corrosion is excessive, replace 

the burners.

FLUE CLEANING

Cooling Cycle:

 

Thermostate call for cooling (2-stage thermostat)

Call for 1st stage cooling only:

With the room thermostat set to 

COOL 

and the fan set to 

AUTO

power is supplied from the room thermostat "O" terminal to the 
unit switchover valve coil (SOV) and the "O" terminal on the 
ECMC board. This energizes the switchover valve (SOV) placing 
it in the position for cooling (it is in the position for heating when 
de-energized).  On a call for cooling, power is supplied to the unit 
from the room thermostat (Y1) and (G) terminal. (Y1) provides 
power to the compressor contactor (CC), the defrost control 
(DFC) and the electronically commutated motor control (ECMC). 
(G) provides power to the (ECMC) for low speed (ECM) indoor 
fan motor operation.

The energized compressor contactor (CC) completes the circuit 
to the compressor for 1st stage (Low) operation and the outdoor 
single speed fan motor (ODM). The (G) signal energizes the 
(ECMC) for the indoor fan motor (ECM) to operate at constant 
circulation. The thermostat will continue to cycle the compressor 
and fans to maintain the desired temperature.

Call for 2nd stage after 1st stage

On a call for 2nd stage cooling, power is supplied from the room 
thermostat (Y2) terminal to the compressor rectifier (ACR) and 
the (ECMC). This energizes the (ACR) switching the compressor 
to 2nd stage (High) operation. The (ECMC) is energized for indoor 
fan motor (ECM) high speed fan operation. The room thermostat 
will continue to cycle the system between 1st and 2nd stage to 
maintain the desired temperature.

EXPLOSION HAZARD!

To prevent an explosion or possible injury, death, and equip-

ment damage. Do not store combustible materials, gasoline, 

or other flammable vapors or liquids near the unit.

WARNING

!

Before each heating season, the flue should be inspected for signs 
of flaking rust and soot deposits.  

Dirty flues should be cleaned by 

qualified service personnel ONLY

 using the following procedure:

  1.  Turn the room thermostat to the OFF position.  Turn the main 

power disconnect OFF. Turn the manual gas valve OFF.

  2.  Remove the flue hood  and the CONTROL/HEAT access panel.

 3. Remove the combustion blower assembly from the flue box.  

Remove the flue box and the flue restrictors.

  4.  Remove all wires from the gas valve while carefully noting their 

locations.

  5.  Disconnect the gas supply line from the valve.

CAUTION

Never  use  combustible  cleaning  fluids  on  any  part  of  the 

furnace.

Содержание 4DCZ6036

Страница 1: ...erent hazards during installation and service the electrical supply must be disconnected and the main gas valve must be turned off If operating checks must be performed with the unit operating it is t...

Страница 2: ...ingpressureexceedsthelimitofR 22 Proper service equipment is required Failure to use proper service tools may result in equipment damage or personal injury SERVICE Use only R 410A Refrigerant and appr...

Страница 3: ...arefully before attempting to install oper ate or perform maintenance on this unit Installation and maintenance should be performed by qualified service techni cians only This unit is listed by Underw...

Страница 4: ...Guide Step 2 Determine Unit Clearances Figure 1 4DCZ6036 1 of 3 Figures 1 through 6 show the unit critical dimensions NOTE The view labeled Bottom Side represents the Base as viewed looking up from u...

Страница 5: ...Page 5 Installer s Guide Figure 2 4DCZ6036 2 of 3...

Страница 6: ...Page 6 Installer s Guide Figure 3 4DCZ6036 3 of 3...

Страница 7: ...Page 7 Installer s Guide Figure 4 4DCZ6048 through 4DCZ6060 1 of 3...

Страница 8: ...Page 8 Installer s Guide Figure 5 4DCZ6048 through 4DCZ6060 2 of 3...

Страница 9: ...Page 9 Installer s Guide Figure 6 4DCZ6048 through 4DCZ6060 3 of 3...

Страница 10: ...fer to the Installation section for instruction on converting the supply and return airflow covers to down airflow 3 The field assembled Roof Mounting Curb BAYCURB050A or BAYCURB051A or a field fabric...

Страница 11: ...clearance to combustible mate rial shall be maintained on air outlet duct Rooftop Installation Curb Mounting Convert Horizontal Airflow to Down Airflow The factory ships the unit for horizontal airflo...

Страница 12: ...he unit by attaching clevis hooks pins or bolts to the unit casing casing hardware corner lugs angles tabs or flanges Failure to observe these warnings may result in equipment damage 1 Before preparin...

Страница 13: ...r roof top applications using field fabricated ducts and sleeper rails rather than a curb or frame use the following procedure 1 Locate and secure the sleeper rails to the roof Three 3 sleeper rails a...

Страница 14: ...drawing The manufacturer is not responsible for the unauthorized use of this drawing and expressly disclaims any liability for damages resulting from such unauthorized use Gasket Seal Spreader Bars B...

Страница 15: ...rizontal Airflow Application with Frame Supply Air Return Air Roof Flashing Channel Iron Center Support Center Sup port required on all Frame Applications Angle Iron Frame Roof Flashing Return Air Ang...

Страница 16: ...ise and vibration transmission Elbows with turning vanes or splitters are recommended to minimize air noise and resistance The first elbow in the ductwork leaving the unit should be no closer than two...

Страница 17: ...making the gas pipe connection give serious consideration to providing the clearance necessary to remove the accesspanelsontheunit e g economizerandfilteraccesspanels NOTE In the absence of local cod...

Страница 18: ...chonthegasvalveinletboss connect the gas piping to the unit Check the completed piping for leaks using a soap and water solution or the equivalent 6 After installation of the gas pipe in the unit the...

Страница 19: ...Models that require 49 orifices for altitudes from 7000 8000 orifices must be changed to 50 HIGH ALTITUDE DERATE CHART NAT Altitude In Feet Inputs shown are with factory orifices 3 5 WC High Fire 1 8...

Страница 20: ...ed A brief explanation of each mode follows RESTRICTED In the restricted mode of operation an outdoor temperature sensor is used to cause the unit to operate in the heat pump mode above a selected out...

Страница 21: ...ns IMPORTANT Upon completion of wiring check all electrical connections including factory wiring within the unit Make sure all connections are tight Replace and secure all electrical box covers and ac...

Страница 22: ...Page 22 Installer s Guide Figure 22 4DCZ6 Field Wiring Diagram 4DCZ6 FIELD WIRING DIAGRAM Y2 YL RD 2NDSTAGECOMPRESSOR 1STSTAGECOMPRESSOR CONSTANTCIRCULATION...

Страница 23: ...h the compressor operating check the line voltage at the unit The voltage should be within the range shown on the unit nameplate If low voltage is encountered check the size and Step 5 Unit Startup le...

Страница 24: ...ot been purged and air is trapped in the gas line NOTE Blue smoke produced by the heat exchanger during the initial burner firing is caused by a thin film of oil on the surface of the heat exchanger T...

Страница 25: ...e After approximately 30 seconds the control energizes the indoor blower on high speed To maintain the indoor temperature at the desired setpoint the thermostat may operate the high fire gas heating c...

Страница 26: ...fter defrost terminates when the outdoor coil should be clear of frost When the measured delta T during heating operation reaches the calculated initiate delta T the demand defrost control DFC opens t...

Страница 27: ...he inside of the burners and the burner ports for deposit buildup and corrosion Wipe and brush the inside of the burner and the burner ports and then clean with a dry cloth If the deposit buildup or c...

Страница 28: ...fast flashes is 3 seconds Status LED Liteport LED IGN Diagnostic Indicators Flash Codes Figure 23 ECM Fan Control ECM Fan Motor Adjustments If the airflow needs to be increased or decreased see the A...

Отзывы: