TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL

Pub. No. 18-HD25D18-3

9

69-1787—03

Number of 
Periods

0540

4

Four periods 
available (Wake, 
Leave, Return, 
Sleep)

2

Two periods available (Wake 
and Sleep)

Not shown if non-
programmable is 
selected. 2 or 4 
applies to all days 
of the week.

Minimum 
Compressor 
Off Time

0580

5

Five-minute 
minimum off time 
for compressor

0, 2, 3, 4 Minimum number of minutes 

compressor is off between 
calls for compressor

 Five minutes 
recommended.

Heat 
Temperature 
Range Stop

0600

90

Highest heating 
setpoint.

40 to 89

Temperature range (1°F 
increments) of heating 
setpoint.

Shown in 1/2 °C.

Cool 
Temperature 
Range Stop

0610

50

Lowest cooling 
setpoint.

51 to 99

Temperature range (1°F 
increments) of cooling 
setpoint.

Shown in 1/2 °C.

Clock Format 0640

12

12-hour clock 
format

24

24-hour clock format

Extended Fan 
on time Heat

0650

0

No extended fan 
operation after call 
for heat ends

90

Fan operation is extended 
90 seconds after call for heat 
ends.

Not shown if fan 
operation is set to 
fossil fuel or in 
Cool Only 
Systems

Extended Fan 
on time Cool

0660

0

No extended fan 
operation after call 
for cool ends

90

Fan operation is extended 
90 seconds after call for cool 
ends.

 Not shown in 
Heat Only 
Systems.

Keypad 
Lockout

0670

0

Unlocked keypad

1, 2

1

—partially locked keypad

2

—fully locked keypad

Unlocked—all 
functions are 
available.
Partially locked—
only temperature 
up and down keys 
and ability to 
enter and modify 
Installer Setup 
mode are 
available.                                  
Fully locked—
only ability to 
enter and modify 
Installer Setup 
mode are 
available.

Table 4. Installer Setup Menu. (Continued)

Select

Installer 

Setup 

Number

Factory Setting

Other Choices

Comments

Option

Description

Options

Description

Содержание 18-HD25D18-3

Страница 1: ...ON When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Installer must be a trained experienced s...

Страница 2: ...l codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selecte...

Страница 3: ...LY PER LOCAL CODES 3 PH ONLY INDOOR OUTDOOR ODT OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 RC S1 R S2 W1 Y G B H...

Страница 4: ...ng system from shutting down due to lack of battery power it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation When using batter...

Страница 5: ...ystem Off both heating and cooling are off Cool controls cooling system Auto automatically changes between heating and cooling systems depending on indoor temperature See Installer Setup section FAN S...

Страница 6: ...nds until screen changes 4 Release the two blank keys when the screen on the comfort control matches the screen below 5 See screen below to review how the comfort control keys are used during Installe...

Страница 7: ...stem Type Selection 0170 1 1 Heat 1 Cool System 1 6 1 1 heat 1 cool 2 single stage heat pump no aux heat 3 heat only no fan 4 heat only with fan 5 hot water Series 20 3 wire or normally open zone valv...

Страница 8: ...gs is disabled 2 Daylight savings is enabled start using in 2007 for areas that use the new 2007 DST calendar Set to 0 in areas that do not follow daylight savings Remote Temperature Sensor Outdoor or...

Страница 9: ...Clock Format 0640 12 12 hour clock format 24 24 hour clock format Extended Fan on time Heat 0650 0 No extended fan operation after call for heat ends 90 Fan operation is extended 90 seconds after cal...

Страница 10: ...ssive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot...

Страница 11: ...ial reading of the indoor or outdoor temperature sensor requires fives minutes to stabilize See the Sensor instructions for installation information CAUTION Equipment Damage Hazard Minimum compressor...

Страница 12: ...etup Number 0670 to change keypad lock options Heating or cooling does not come on Comfort control minimum off time is activated Wait up to five minutes for the system to respond System selection is n...

Отзывы: