Trane 18-HD25D18-3 Скачать руководство пользователя страница 3

TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL

Pub. No. 18-HD25D18-3

3

69-1787—03

Fig. 5. Typical hookup of single-stage heat and cool 

system with single transformer (1H/1C).

Fig. 6. Typical hookup of single-stage heat and cool 

system with two transformers (1H/1C).

Fig. 7. Typical hookup of single-stage heat pump with no auxiliary/backup heat (1H/1C heat pump).

1

M22656

FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 

ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  

FROM THE THERMOSTAT CABLE.

1

2

2

RC

S1

R

S2

W1

Y

G

B

HEAT/COOL

T

B/C

W3

W2

W1

G

Y

R

AIR 

HANDLER

Y

B

COOLING UNIT

O.D. SECTION

(SINGLE STAGE)

TO POWER SUPPLY

PER LOCAL CODES

(3 PH 

ONLY)

INDOOR

OUTDOOR

ODT

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 

ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  

FROM THE THERMOSTAT CABLE.

1

1

RC

S1

R

S2

W1

Y

G

B

HEAT/COOL

T

B/C

W

T

T

G

Y

R

OIL

FURNACE

Y

B

COOLING UNIT

O.D. SECTION

(SINGLE STAGE)

TO POWER SUPPLY

PER LOCAL CODES

(3 PH 

ONLY)

M22657

OIL BURNER PRIMARY

INDOOR

OUTDOOR

PM-A

1

M22658

FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR. 

AVAILABLE ON SELECT MODELS.  WIRES MUST HAVE

A CABLE SEPARATE FROM THE THERMOSTAT CABLE.

1

2

2

RC

S1

R

S2

O
Y

G

B

HEAT PUMP

T

T

B/C

W2

W1

G

Y

R

AIR 

HANDLER

Y

B

HEAT PUMP

O.D. SECTION

(SINGLE STAGE)

TO POWER SUPPLY

PER LOCAL CODES

(3 PH 

ONLY)

INDOOR

OUTDOOR

O

R

O

BR/X2

OR BK

ODT-1

ODT-2

F

BR(T)

W3

TO POWER

SUPPLY PER 

LOCAL 

CODES AND 

AS DEFINED 

IN FIELD 

WIRING TABLE

SUPPL. HTR.

CONTROL BOX

I-PF

REQ.

FOR

3 PH

Содержание 18-HD25D18-3

Страница 1: ...ON When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Installer must be a trained experienced s...

Страница 2: ...l codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selecte...

Страница 3: ...LY PER LOCAL CODES 3 PH ONLY INDOOR OUTDOOR ODT OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 RC S1 R S2 W1 Y G B H...

Страница 4: ...ng system from shutting down due to lack of battery power it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation When using batter...

Страница 5: ...ystem Off both heating and cooling are off Cool controls cooling system Auto automatically changes between heating and cooling systems depending on indoor temperature See Installer Setup section FAN S...

Страница 6: ...nds until screen changes 4 Release the two blank keys when the screen on the comfort control matches the screen below 5 See screen below to review how the comfort control keys are used during Installe...

Страница 7: ...stem Type Selection 0170 1 1 Heat 1 Cool System 1 6 1 1 heat 1 cool 2 single stage heat pump no aux heat 3 heat only no fan 4 heat only with fan 5 hot water Series 20 3 wire or normally open zone valv...

Страница 8: ...gs is disabled 2 Daylight savings is enabled start using in 2007 for areas that use the new 2007 DST calendar Set to 0 in areas that do not follow daylight savings Remote Temperature Sensor Outdoor or...

Страница 9: ...Clock Format 0640 12 12 hour clock format 24 24 hour clock format Extended Fan on time Heat 0650 0 No extended fan operation after call for heat ends 90 Fan operation is extended 90 seconds after cal...

Страница 10: ...ssive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot...

Страница 11: ...ial reading of the indoor or outdoor temperature sensor requires fives minutes to stabilize See the Sensor instructions for installation information CAUTION Equipment Damage Hazard Minimum compressor...

Страница 12: ...etup Number 0670 to change keypad lock options Heating or cooling does not come on Comfort control minimum off time is activated Wait up to five minutes for the system to respond System selection is n...

Отзывы: