TCONT800AS11AA TOUCH SCREEN PROGRAMMABLE COMFORT CONTROL

Pub. No. 18-HD25D18-3
69-1787—03

8

Continuous 
Backlight

0280

0

Backlight not on 
continuously. 
Comfort control 
backlight comes 
on with each key 
press.

1

Backlight is on continuously 
(comfort control must have a 
common wire attached for 
this function).

Option is always 
shown; however, 
continuously on 
backlight works 
only if comfort 
control is wired 
with 24 Vac 
Common.

Changeover

0300

0

Manual changeover 1

1—auto changeover

 —

Deadband

0310

3

Heating and cooling 
setpoints can be set 
no closer than 
3°F (1.5°C)

2 thru 9

Heating and cooling 
setpoints can be set no 
closer than chosen       
value:                                                                                    

2

—2°F (1°C)

3

—3°F (2°C)

4

—4°F (2.5°C)

5

—5°F (3°C)

6

—6°F (3.5°C)

7

—7°F (4°C)

8

—8°F (4.5°C)

9

—9°F (5°C)

Shown only if 
automatic 
changeover is 
selected.

Temperature 
Indication 
Scale

0320

0

Temperature is 
displayed in °F.

1

Temperature is displayed 
in °C.

 —

Daylight 
Savings

0330

1

Daylight savings 
enabled (use 
through 2006 and 
for areas that do not 
use the new 2007 
DST calendar).

0,2

0

—Daylight savings is 

disabled.

2

—Daylight savings is 

enabled (start using in 2007, 
for areas that use the new 
2007 DST calendar).

Set to 0 in areas 
that do not follow 
daylight savings.

Remote 
Temperature 
Sensor 
(Outdoor or 
Indoor)

0340

0

No remote 
temperature sensor

1,3

1

—outdoor temperature 

sensor for display only.

3

—indoor temperature 

sensor.

Defaults and 
Options depend 
on System Type 
selected. Indoor 
Temperature 
Sensor uses an 
averaging 
network and does 
not include on-
board sensor.

Furnace Filter 
Change 
Reminder

0500

0

Furnace filter 
change reminder off

1-6

1—

10 run time days

2—

30 run time days

3—

60 run time days

4—

90 run time days

5—

120 run time days

6—

365 run time days 

Run time based 
on call for fan.

Humidifier 
Pad 
Replacement 
Reminder

0510

0

Humidifier pad 
replacement 
reminder off

1-3

1—

90 calendar days

2—

180 calendar days

3—

365 calendar days

Adaptive 
Intelligent 
Recovery™ 

0530

1

Adaptive Intelligent 
Recovery™ control 
is activated (system 
starts early so 
setpoint is reached 
by start of program 
period).

0

0—

conventional recovery 

(system starts recovery at 
programmed time)

Table 4. Installer Setup Menu. (Continued)

Select

Installer 

Setup 

Number

Factory Setting

Other Choices

Comments

Option

Description

Options

Description

Содержание 18-HD25D18-3

Страница 1: ...ON When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Installer must be a trained experienced s...

Страница 2: ...l codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selecte...

Страница 3: ...LY PER LOCAL CODES 3 PH ONLY INDOOR OUTDOOR ODT OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 RC S1 R S2 W1 Y G B H...

Страница 4: ...ng system from shutting down due to lack of battery power it is not recommended that the comfort control be solely powered with the three AAA batteries during normal system operation When using batter...

Страница 5: ...ystem Off both heating and cooling are off Cool controls cooling system Auto automatically changes between heating and cooling systems depending on indoor temperature See Installer Setup section FAN S...

Страница 6: ...nds until screen changes 4 Release the two blank keys when the screen on the comfort control matches the screen below 5 See screen below to review how the comfort control keys are used during Installe...

Страница 7: ...stem Type Selection 0170 1 1 Heat 1 Cool System 1 6 1 1 heat 1 cool 2 single stage heat pump no aux heat 3 heat only no fan 4 heat only with fan 5 hot water Series 20 3 wire or normally open zone valv...

Страница 8: ...gs is disabled 2 Daylight savings is enabled start using in 2007 for areas that use the new 2007 DST calendar Set to 0 in areas that do not follow daylight savings Remote Temperature Sensor Outdoor or...

Страница 9: ...Clock Format 0640 12 12 hour clock format 24 24 hour clock format Extended Fan on time Heat 0650 0 No extended fan operation after call for heat ends 90 Fan operation is extended 90 seconds after cal...

Страница 10: ...ssive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot...

Страница 11: ...ial reading of the indoor or outdoor temperature sensor requires fives minutes to stabilize See the Sensor instructions for installation information CAUTION Equipment Damage Hazard Minimum compressor...

Страница 12: ...etup Number 0670 to change keypad lock options Heating or cooling does not come on Comfort control minimum off time is activated Wait up to five minutes for the system to respond System selection is n...

Отзывы: