12
BAS-SVX10F-EN
Installation and Configuration: Display Sensor
4. Hold the back plate against the mounting surface and mark the screw locations.
5. Secure the back plate to the mounting surface using the included hardware.
Wiring the Sensor
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote disconnects before servicing. Follow proper
lockout/tagout procedures to ensure the power can not be inadvertently energized. Failure to
disconnect power before servicing could result in death or serious injury.
NOTICE:
Equipment damage!
Applying excessive voltage to the sensor will permanently damage it.
To wire the sensor to the unit controller:
1. Ensure that the wires are connected to the appropriate
terminals at the
unit controller.
Note:
Ensure that the GROUND (terminal 10) and the SIGNAL COMMON (terminal 2) wires
share a common ground with the transformer
2. Insert each wire into the appropriate location in the terminal block (see the table in
). Tighten the terminal screw.
Note:
The wire connections can be made while the terminal block is either on the circuit board,
or removed from it.
3. Perform a pull test to ensure that the wires are properly connected.
4. If you want the sensor to read an external thermistor, reset the jumper to the external position
.
5. If the terminal block was removed from the circuit board, attach it to the pins inside the sensor
).