background image

26

 BAS-SVX10F-EN

Operation

Operation

This section describes sensor operations.

Changing Temperature Settings

To change temperature settings:

For sensors with temperature setpoint thumb wheels (located on top of the sensor), rotate the 
thumb wheel to the desired temperature setting.

Note:

If you need to change or replace a thumb wheel, see 

“Changing the Setpoint Thumb 

Wheel (optional),” p. 24

.

For sensors with dual temperature sliders (located on the right front of the sensor): Slide the 
blue (

cool

) slider to the desired maximum temperature setting. Slide the red (

heat

) slider to the 

desired minimum temperature setting.

For the display sensor, see 

“Changing Temperature Settings,” p. 30

 and 

“Changing Heating and 

Cooling Temperature Settings (dual setpoint systems only),” p. 30

.

Changing System Settings

To change system settings:

For sensors with system thumb wheels (located on the upper left side), rotate the thumb wheel 
to the desired setting.

For the display sensor, see 

“Changing System Settings,” p. 31

.

Notes:

Not all sensor models have all system setting options. 

The effect of setting changes are dependent on the unit controller. See specific unit controller 
manual for details.

Changing Fan Settings

To change fan settings:

For sensors with fan thumb wheels (located on the lower left side), rotate the thumb wheel to 
the desired setting.

For the display sensor, see 

“Changing Fan Settings,” p. 31

.

Notes:

Not all sensor models have all fan setting options. 

The effect of setting changes are dependent on the unit controller. See specific unit controller 
manual for details.

Содержание X1316105702

Страница 1: ...ng up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unquali...

Страница 2: ...the same potential impact to the environment Trane advocates the responsible handling of all refrigerants including industry replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and H...

Страница 3: ...SHA NFPA 70E or other country specific requirements for arc flash protection PRIOR to servicing the unit NEVER PERFORM ANY SWITCHING DISCONNECTING OR VOLTAGE TESTING WITHOUT PROPER ELECTRICAL PPE AND...

Страница 4: ...20 Mounting the Back Plate 20 Installing the COMM Module optional 23 Changing the Setpoint Thumb Wheel optional 24 Wiring the Sensor 24 Replacing the Cover 25 Operation 26 Changing Temperature Settin...

Страница 5: ...ult Modes of Operation 32 Measuring Output Resistance 33 Display Sensors 33 All Models Other Than the Display Sensor 33 Cleaning the Sensor 35 Replacing the Thumb Wheel 35 Wiring Diagrams 36 Temperatu...

Страница 6: ...vice tool for system communication Must be ordered separately Hot cold setpoint thumb wheel Optional accessory allows selecting a temperature setpoint by color red blue for hot cold on thumbwheel rath...

Страница 7: ...f Auto Heat No No X1379083701 BAYSENS108A SEN01513 Dual Auto High Cool Off Auto Heat No Yes 4 X1379084601 BAYSENS110A SEN01522 Single Auto High Cool Off Heat No No X1379083901 BAYSENS106A SEN01515 Sin...

Страница 8: ...n details The dimensions are the same for all models 2 9 in 73 5 cm 1 08 in 27 5 mm 4 68 in 118 9 mm 1 45 in 36 8 mm 0 63 in 15 9 mm 0 31 in 8 mm 0 12 in 3 mm TYP R 07 in R1 9 mm 3 39 in 86 mm 2 48 in...

Страница 9: ...fic areas to reduce accidental damage or tampering Height Requirements The recommended maximum mounting height is 54 inches from the bottom of the back plate to the floor If a parallel approach by a p...

Страница 10: ...ler that there is continuity between the sensor location and the controller and that the wires are accurately labeled or identified by color Mounting the Back Plate WARNING Hazardous Voltage Disconnec...

Страница 11: ...BAS SVX10F EN 11 Installation and Configuration Display Sensor 3 Feed the wires through the opening in the back plate...

Страница 12: ...To wire the sensor to the unit controller 1 Ensure that the wires are connected to the appropriate terminals at the unit controller Note Ensure that the GROUND terminal 10 and the SIGNAL COMMON termi...

Страница 13: ...tion Display Sensor 6 Push the excess wire into the wall cavity and plug it with nonflammable insulation to prevent drafts from affecting the sensor Important Do not coil excess wire inside the back p...

Страница 14: ...he sensor is in configurationmode a wrench symbol appears on the display and the menus are separated by lines as illustrated below 1 Press the center button on the keypad to begin the configuration pr...

Страница 15: ...grees Setpoint Deadband available for dual setpoint system only Note Deadband refers to the minimum difference between the heating and cooling setpoints System a Single setpoint System continued b Dua...

Страница 16: ...sed for 10 minutes Fan Note Not all fan options are available for all systems Occupancy timed override Setting Configuration options auto off low med high auto off low high auto off off high on off lo...

Страница 17: ...r the temperature default or setpoint To select either option 1 Verify that the sensor is in operating mode and at the home screen 2 Press the up and down arrows for 3 seconds The arrow indicates setp...

Страница 18: ...the down arrow to select the fan menu Use the left or right arrow to choose the setting Fan menu 3 Press the left and right arrows for 4 seconds The lock symbol will appear on the display to indicate...

Страница 19: ...BAS SVX10F EN 19 Installation and Configuration Display Sensor 2 Secure the cover by installing the security screw into the bottom of the cover Security screw...

Страница 20: ...sensor location and the wire is accessible through the hole The technician should assume that the wires are attached to the appropriate unit controller that there is continuity between the location an...

Страница 21: ...ving the cover 3 Remove the circuit board by pressing the thumb catch on the left side of the board Use the terminal block to lift the circuit board from the back plate Terminal Thumb catch 4 Feed the...

Страница 22: ...h the opening in the circuit board 8 Replace the circuit board by sliding the right side of the board under the two catches on the right side of the back plate while aligning slot on board with tab on...

Страница 23: ...a local RJ22 connection to a Trane service tool for maintenance use It must be ordered separately Install the COMM module before wiring the sensor 1 Slide the two cutouts on the right side of the COMM...

Страница 24: ...curely onto the back plate 3 Rotate the replacement thumb wheel until the stop is opposite the flat portion of the potentiometer Push down on the thumb wheel until the ribs touch the potentiometer Aft...

Страница 25: ...Sensor Replacing the Cover To replace the cover 1 Hook the cover over the top of the back plate Apply light pressure to the bottom of the cover until it snaps in place 2 Secure the cover by installing...

Страница 26: ...d ChangingHeatingand Cooling Temperature Settings dual setpoint systems only p 30 Changing System Settings To change system settings For sensors with system thumb wheels located on the upper left side...

Страница 27: ...with Occupied Unoccupied buttons To select temporary occupancy press the Occupied button Figure 2 for 0 2 6 seconds The following occurs Space temperature output is driven to 10 nominal The output gen...

Страница 28: ...support occupancy and must be in operating mode see Configuring the Display Sensor p 13 To initiate a service pin request 1 With the sensor in operating mode navigate to the occupancy menu 2 Press the...

Страница 29: ...is communicated Double star A value of 44 6 F 7 C is communicated Figure 4 Star Double star on thumb wheel Display Sensor The display sensor supports the star and double star functions if the sensor i...

Страница 30: ...and Cooling Temperature Settings dual setpoint systems only Some systems allow you to select both heating and cooling room temperature settings If your system has this option this symbol appears when...

Страница 31: ...icates fan speed 3 high 2 medium 1 low The example shown indicates a fan on high speed Not all systems offer all three speeds Indicates fan is Off Requesting Temporary Occupancy Select to request occu...

Страница 32: ...normal heating operation Blinks to indicate a heating system failure System LED green The green system LED indicates the state of the system Stays on solid to during normal operation Blinks to indicat...

Страница 33: ...Measure between the SYS FAN MODE terminal 4 and the SIGNAL COMMON terminal 2 Compare resistance measurements to those in Table 2 p 34 NOTICE Potential Equipment Damage Because the output circuits are...

Страница 34: ...setpoint systems Cooling setpoint varies 10 at 70 F 21 1 C varies at 110 at endpoints of scale Heating setpoint varies 20 at 70 F 21 1 C varies at 120 at endpoints of scale 34 BAS SVX10F EN Maintenan...

Страница 35: ...cloth and gently wiping the face including the buttons and LCD display Use of a pre moistened towelette designed for lens or screen cleaning is also acceptable Avoid inadvertent pressing buttons on se...

Страница 36: ...270 3435 B Zone temperature Signal common Setpoint 1 2 3 Calibration potentiometer Pot 2 see Note NOTE POT 1 and POT2 are factory calibrated Field adjustment voids warranty Zone temperature Signal com...

Страница 37: ...tor 10 k at 25 C W 1 2 4 Calibration Pot 1 see Note 1 RT1 Note 1 Pot 1 is factory calibrated Field adjustment voids warranty 3 R1 4 87 kW R2 2 32 kW Auto Off R11 zero W Signal common Cool setpoint CSP...

Страница 38: ...temperature Mode System switch TB1 Dwg source X39641098 01 X1379085101 Timed override Cancel SW4 R9 1 5 kW Timed override On SW3 Thermistor 10 k at 25 C W 1 2 4 Calibration Pot 1 see Note 1 RT1 Note 1...

Страница 39: ...Pot 5 1 kW Fan SW1 Dwg source X39641088 01 X1379084101 Timed override Cancel SW4 R9 1 5 kW Timed override On SW3 Thermistor 10 k at 25 C W 1 2 4 Calibration Pot 1 see Note 1 RT1 Note 1 Pot 1 is factor...

Страница 40: ...CSP Heat Setpoint HSP Zone temperature TB1 Mode Sys Fan switch System SW1 Fan SW2 Cool setpoint Pot 4 1 k Dwg source X39641094 01 RT1 thermistor 10 k at 25 C W Temperature setpoint Pot 5 1 kW 1 2 4 Ca...

Страница 41: ...g source X39641084 01 RT1 thermistor 10 k at 25 C W 1 2 4 Calibration Pot 1 see Note 1 R7 3 92 kW Note 1 Pot 1 and Pot 2 are factory calibrated Field adjustment voids warranty 3 5 R6 8 45 kW Auto On R...

Страница 42: ...setpoint Pot 5 1 kW System SW1 Fan SW2 Dwg source X39641086 01 2 4 Calibration Pot 1 see Note 1 Note 1 Pot 1 is factory calibrated Field adjustment voids warranty 3 R6 8 45 kW Auto On R1 4 87 kW R2 2...

Страница 43: ...2 1 COMM Module J1 2 3 Optional COMM module X1365146702 BAS SVX10F EN 43 Wiring Diagrams...

Страница 44: ...ousing material Polycarbonate ABS blend UV protected UL 94 5VA flammability rating suitable for application in a plenum Mounting Fits a standard 2 in by 4 in junction box vertical mount only Mounting...

Страница 45: ...EN55011 2006 Class B limit Harmonic EN61000 3 2 Class A limit Flicker EN61000 3 3 1995 A1 2001 A2 2006 Electromagnetic Immunity for Industrial by Council Directive 89 336 EEC EN61326 1 2006 EN61000 2...

Страница 46: ......

Страница 47: ......

Страница 48: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: