background image

Removal and Installation

16

 COM-SVN003B-EN

vacuum with dry nitrogen and repeat evacuation 
process to 500 micron.

Once system is leak-tight, connect compressor repeat 
the vacuum procedure, break vacuum with dry 
nitrogen and evacuate to 500 microns. The vacuum 
should be able to be maintained for four hours. Isolate 
the vacuum pump so that the vacuum gauge only 
reads the system pressure.

Vacuum must be measured in the refrigeration system 
and not at the vacuum pump.

Charging the System

Use R-410A refrigerant only! Follow the instructions in the 
unit Installation, Operation, and Maintenance manual for 
proper charging methods.

If there are no instructions available, use these guidelines:

Evacuate the unit as described in 

“Vacuum Testing and 

Evacuation,” p. 15

.

Ensure that the oil level is at least 1/2-sight glass in the 
compressor

Do not use the compressor to pull refrigerant into the 
system.

Charge liquid refrigerant into the high-side of the 
unit—either into the condenser or liquid receiver, if so 
equipped.

Charge as much of the unit refrigerant charge as 
possible before starting the compressor.

Do not charge liquid refrigerant into the low side of the 
compressor without the compressor running. Small 
amounts of liquid may be metered through refrigerant 
gauges into the suction line while the compressor is 
operating.

If the unit is equipped with suction and discharge 
service valves, close them during the charging 
procedure.

Water chiller units

—Always operate the chilled water 

pumps while charging the unit to prevent freezing the 
evaporator.

Verification Before Start-Up

Follow the instructions in the unit Installation, Operation, 
and Maintenance manual. If there are no instructions 
available, use these guidelines:

Before starting the unit, verify that all service valves are 
open.

Energize the crankcase heater a minimum of 8 hours 
before starting the compressor.

If the compressor is a replacement for a failed compressor 
and has been charged in accordance with either the 
procedures in the unit IOM or 

“Charging the System,” p. 16

 

in this manual, the compressor could be immediately 
started after charging the system. The reason for this is 
that the refrigerant has not had sufficient time to migrate 
to the compressor and cause potential damage upon 
startup. The system should set for no more 8 hours or 
overnight with a refrigerant charge without crankcase 
heater operation. If the time exceeds 8 hours or the unit 
sits overnight, the crankcase heater must be operational 
for a minimum of 8 hours prior to starting the compressor.

If liquid refrigerant was charged into the suction or low 
side during the charging procedure, damage could still 
occur.

WARNING

Hazardous Pressures!

Failure to follow these instructions could result in a 
violent explosion, which could result in death or serious 
injury. If a heat source is required to raise the tank 
pressure during removal of refrigerant from cylinders, 
use only warm water or heat blankets to raise the tank 
temperature. Do not exceed a temperature of 150°F. Do 
not, under any circumstances apply direct flame to any 
portion of the cylinder.

NOTICE: 

Compressors Failure!

To protect compressors from premature failure the unit 
must be powered and crankcase heaters energized at 
least 8 hours BEFORE compressors are started. 

Содержание CSHW047

Страница 1: ...ing up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqual...

Страница 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Страница 3: ...hould only be mixed with dry nitrogen for pressurizing units Failure to follow these instructions could result in death or serious injury or equipment or property only damage WARNING Hazardous Service...

Страница 4: ...rmission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 5: ...8 Pre Installation Inspections 9 Repair Recommendations 9 Mechanical Failure 10 Electrical Failure 10 Two Types of Motor Failures 10 Removal and Installation 11 Removal 11 Compressor Replacement Tand...

Страница 6: ...1 step Unloading with solenoid not energized Digit 10 Design Sequence Factory Assigned Digit 11 Motor Protection Type 0 Internal Line Break Digit 12 Compressor Connections Variation 0 Standard Compres...

Страница 7: ...ion Some conditions will result in oil levels below the sight glass Off After several minutes theoil levels should be the same in each compressor and should be visible in the sightglass This is the be...

Страница 8: ...system charge exceeds 3 pounds per ton crankcase heaters are required If required heaters must be energized for a minimum of eight hours prior to starting the compressor to insure that liquid refrige...

Страница 9: ...ngs may not be of the same length Adjust as necessary for even unit lift Table 2 Compressor weight without oil charge Model Weight lb Weight kg CSHW 047 050 052 056 83 8 38 CSHW 052 2 86 39 CSHW 058 0...

Страница 10: ...rs using an acid test kit Use Trane Part Numbers CHM00414 and 45006 Two Types of Motor Failures Light If oil test kit is negative and oil is only slightly discolored treat in the same manner as a mech...

Страница 11: ...compressor Cut the refrigerant lines in a convenient location that allows reassembly with slip couplings Then unbraze the line from the compressor and reuse it when the replacement is installed WARNIN...

Страница 12: ...and shipping For single applications this equalizer port will need to be brazed shut with a 1 125 tube and cap If the replacement compressor requires a full oil charge then the compressor can be tipp...

Страница 13: ...of the refrigerant system iv Reinsert the tube into the compressor connection If the tubing does not stay fully inserted it must be restrained to prevent it from backing out of the compressor connecti...

Страница 14: ...order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions U...

Страница 15: ...equipment or property only damage Use only dry nitrogen with a pressure regulator for pressurizing unit Do not use acetylene oxygen or compressed air or mixtures containing them for pressure testing D...

Страница 16: ...ng the evaporator Verification Before Start Up Follow the instructions in the unit Installation Operation and Maintenance manual If there are no instructions available use these guidelines Before star...

Страница 17: ...ly when the compressor is operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation and Maintenance manual is 16 F 20...

Страница 18: ...eat sub cooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color Check electri...

Страница 19: ...mum of eight hours or it is defective Mechanical damage to the compressor has occurred Check compressor amperage It may also trip the compressor motor protection module or other unit electrical protec...

Страница 20: ...on Operation and Maintenance manual for possible diagnostics codes and corrective action Also check for Defective unit controls maximum 12 starts per hour Compressors cycling on safety controls Unit o...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...

Отзывы: