Introduction

4

 COM-SVN003B-EN

Copyright

This document and the information in it are the property of 
Trane, and may not be used or reproduced in whole or in 
part without written permission. Trane reserves the right 
to revise this publication at any time, and to make changes 
to its content without obligation to notify any person of 
such revision or change.

Trademarks

All trademarks referenced in this document are the 
trademarks of their respective owners. 

Revision History

Added 047 to Non-Loading CSHW values in Model 
Number Description chapter.

Running edits.

Содержание CSHW047

Страница 1: ...ing up and servicing of heating ventilating and air conditioning equipment can be hazardous and requires specific knowledge and training Improperly installed adjusted or altered equipment by an unqual...

Страница 2: ...hazardous situation which if not avoided could result in minor or moderate injury It could also be used to alert against unsafe practices NOTICE Indicates a situation that could result in equipment o...

Страница 3: ...hould only be mixed with dry nitrogen for pressurizing units Failure to follow these instructions could result in death or serious injury or equipment or property only damage WARNING Hazardous Service...

Страница 4: ...rmission Trane reserves the right to revise this publication at any time and to make changes to its content without obligation to notify any person of such revision or change Trademarks All trademarks...

Страница 5: ...8 Pre Installation Inspections 9 Repair Recommendations 9 Mechanical Failure 10 Electrical Failure 10 Two Types of Motor Failures 10 Removal and Installation 11 Removal 11 Compressor Replacement Tand...

Страница 6: ...1 step Unloading with solenoid not energized Digit 10 Design Sequence Factory Assigned Digit 11 Motor Protection Type 0 Internal Line Break Digit 12 Compressor Connections Variation 0 Standard Compres...

Страница 7: ...ion Some conditions will result in oil levels below the sight glass Off After several minutes theoil levels should be the same in each compressor and should be visible in the sightglass This is the be...

Страница 8: ...system charge exceeds 3 pounds per ton crankcase heaters are required If required heaters must be energized for a minimum of eight hours prior to starting the compressor to insure that liquid refrige...

Страница 9: ...ngs may not be of the same length Adjust as necessary for even unit lift Table 2 Compressor weight without oil charge Model Weight lb Weight kg CSHW 047 050 052 056 83 8 38 CSHW 052 2 86 39 CSHW 058 0...

Страница 10: ...rs using an acid test kit Use Trane Part Numbers CHM00414 and 45006 Two Types of Motor Failures Light If oil test kit is negative and oil is only slightly discolored treat in the same manner as a mech...

Страница 11: ...compressor Cut the refrigerant lines in a convenient location that allows reassembly with slip couplings Then unbraze the line from the compressor and reuse it when the replacement is installed WARNIN...

Страница 12: ...and shipping For single applications this equalizer port will need to be brazed shut with a 1 125 tube and cap If the replacement compressor requires a full oil charge then the compressor can be tipp...

Страница 13: ...of the refrigerant system iv Reinsert the tube into the compressor connection If the tubing does not stay fully inserted it must be restrained to prevent it from backing out of the compressor connecti...

Страница 14: ...order to protect themselves from potential electrical mechanical and chemical hazards MUST follow precautions in this manual and on the tags stickers and labels as well as the following instructions U...

Страница 15: ...equipment or property only damage Use only dry nitrogen with a pressure regulator for pressurizing unit Do not use acetylene oxygen or compressed air or mixtures containing them for pressure testing D...

Страница 16: ...ng the evaporator Verification Before Start Up Follow the instructions in the unit Installation Operation and Maintenance manual If there are no instructions available use these guidelines Before star...

Страница 17: ...ly when the compressor is operating Do not overcharge the unit Recommended system full load superheats unless specified differently in the unit Installation Operation and Maintenance manual is 16 F 20...

Страница 18: ...eat sub cooling oil sump superheat voltage and amperage Check all of the following on a regular basis System operating conditions System refrigerant charge level Oil levels and oil color Check electri...

Страница 19: ...mum of eight hours or it is defective Mechanical damage to the compressor has occurred Check compressor amperage It may also trip the compressor motor protection module or other unit electrical protec...

Страница 20: ...on Operation and Maintenance manual for possible diagnostics codes and corrective action Also check for Defective unit controls maximum 12 starts per hour Compressors cycling on safety controls Unit o...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...are committed to using environmentally conscious print practices Trane by Trane Technologies NYSE TT a global climate innovator creates comfortable energy efficient indoor environments for commercial...