circuit. If an isolating transformer is used, it should be bonded to the control panel frame. The equipment
ground is not required when the isolating transformer is used. Do not fuse control transformers above
their rated current value because these devices are current limiting and an oversize fuse may not blow
under short circuit conditions.
Remote Emergency shutdown switches
A manually operated remote shutdown switch or circuit breaker shall be located just outside the boiler
room door and marked for easy identification. Consideration should also be given to the type and location
of the switch to safeguard against tampering. If the boiler room door is on the building exterior, the switch
should be located just inside the door. If there is more than one door to the boiler room, there should be
a switch located at each door. Where a boiler is located indoors in a facility and not in a boiler room, a
remote emergency shutdown switch shall be located within 50 feet of the boiler along the primary egress
rout from the boiler area. The installer shall be responsible to install the remote emergency shutdown
switch(s) and to verify that it is suitably marked.
4.9 Miscellanious installation guidelines
Software & Safety
Programming controls, when used, shall provide proper sequencing of the above controls to insure that
all conditions, necessary for proper burner operation, are satisfied. Included in a programmed control are
pre-purge and post-purge cycles to remove accumulated gases.
Flame Safeguard
When installation is complete, Safety Controls will stop fuel flow in the cases of: ignition failure, main
flame interruption, mechanical draft failure, circuit failure, as appropriate for your installation. The
controls on the burner and boilers are designed to prevent fuel flow when any of the boiler conditions are
outside intended limits of pressure, temperature, and water level as is appropriate for your system.
Venting of Gas Controls
Venting of gas controls should conform to recognized installation standards. It is best to check with the
authorities have jurisdiction to determine your specific requirements.
4.10 Boiler stack connection
A flue gas connection is located at the bottom centerline at the back, just above the condensate drain of
your boiler. The stack connection is slip-on. The flue gas connection is not designed for support. The
breaching and chimney shall at minimum be the size of the boilers stack connector. When installing a
boiler where the exhaust is tied into other systems, a professional should be consulted.
INSTALLATION AND MAINTENANCE OF THE STACK SHALL BE IN COMPLIANCE WITH THE AUTHORITIES
HAVING JURISDICTION.
Furnace pressure:
The pressure drop between the burner and the stack connector at high fire.
Содержание Triumph 1000
Страница 14: ...14 TRIAD Boiler Systems Inc West Chicago IL www triadboiler com Handling Options ...
Страница 16: ...16 TRIAD Boiler Systems Inc West Chicago IL www triadboiler com 2 0 Boiler Component Identification ...
Страница 20: ...20 TRIAD Boiler Systems Inc West Chicago IL www triadboiler com Model 300 500 Model 750 1000 ...
Страница 27: ...27 TRIAD Boiler Systems Inc West Chicago IL www triadboiler com 2 6 Example wiring diagrams ...